I am replacing a white rodgers thermostat with a honeywell rth3100c. i have matched my wire as e (brown) to e w2 (white) o aux y (yellow) to y g (green) to g o (orange) to o l blank r (red) t r b blank c blank now i have a blue wire which was hooked up to the x1 on the old thermostat. where does this wire go?


Answers :

Blue (C) or sometimes (B) should be your common wire. Look at your schematics and locate common. Your Brown wire is (E) and is emergency heat, white wire (W) is Auxilary Heat, green wire (G) is fan relay, red wire (R) is power, yellow wire (Y) is Cooling and orange wire (O) is reversing valve.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I am replacing a white rodgers thermostat with a honeywell rth3100c. i have matched my wire as e (brown) to e w2 (white) o aux y (yellow) to y g (green) to g o (orange) to o l blank r (red) t r b blank c blank now i have a blue wire which was hooked up to the x1 on the old thermostat. where does this wire go?


Blue (C) or sometimes (B) should be your common wire. Look at your schematics and locate common. Your Brown wire is (E) and is emergency heat, white wire (W) is Auxilary Heat, green wire (G) is fan relay, red wire (R) is power, yellow wire (Y) is C ... Air Conditioners

I have a tempstar with 6 wires. Green, Blue, Red, Yellow,White, and Orange. I am trying to install a White Rodgers 300 thermostat and letters are not matching up. The thermostat has G, A, RC, RH, O, B, Y, and W. I don't know where to hook the blue wire which was labeled C. Unless it goes to RC and the red goes to RH could you please help? Thanks


You need to verify the function of each wire with Tempstar then cross it with the WR stat. Call the techline if you need further assistance 18002842925. ... Dometic Rooftop RV Air Conditioner

My plan jane evcon thermostat is not wired right. The furnace works fine. The air conditioner will only come on when you push the lever up hotter than it is in the room instead of cool. It will then run, but runs and runs and will not shut off. There are 4 wires, red that is hooked to screw with B by it because the blue wire has a piece of paper on it with a Y and is hooked to the Y screw, white that is hooked to one with W and green wire is hooked to the screw with G. little short red wir


Hi,\015\012Okay....two things to check on...\015\012make sure that the terminals and the wires are matched in the t-stat and the furnace board...R-R Y-Y G-G W-W ....if everything matches up then you have a fried t-stat... What you are say ... Air Conditioners

I am replacing a White Rogers 1F58-77 with a Honeywell RTH2300. When I removed the old stat the wire colors are white, red, orange, green, yellow, and blue. G- green wire Y- Yellow wire R- Red wire W- White wire O-Orange wire X1- Blue wire I hooked up all the wires except the blue. Instructions with the Honeywell unit said not to hook up the blue wire if there is an orange wire to hook up which I did. The problem, when I light off the A/C (heat pump) the compressor comes on but the


Yes you did correct. Tape of f blue wire. On your thermostat you should have el/gas turn top el and fan should work Russ ... Air Conditioners

I am installing a Mars 1/3 hp fan motor. It has a black wire,red wire, blue wire, yellow wire and (2) brown wire that go to a capacitor. May Furnace has Black power wire, red wire (speed) and white common. What wire is the common to the fan motor?? I hooked it up with black to black, red to red, and white to the blue. It ran fine for 5 min then it thid my breaker in bresker box???? If the blue was not common how could the motor run at all??


Hello, Typically your common wire will be white, high speed- black, medium speed- yellow, medium low-blue, red- low. The motor could still run for a short time if it was wired wrong but will either trip a breaker or go off on it;s overload when it's ... Air Conditioners

A duo therm thermostat (p/n 3105058) was removed because it would not operate the air conditioner/heater in a firan fireside camper. it was knocked loose from the wall damaging it.the thermostat is for use in a six wire system.the camper wiring consists of of two bundles; one bundle of two conductors (red and white wires) and a bundle of four conductors(red,blue,white & green wires).the thermostat also has a high/low fan switch. the camper owner bought a white-rodgers model 300 thermostat to rep


A. Remove the cover of the thermostat.b. Connect the RED wire from the air conditionerto the “RC” terminal on the thermostat.c. Connect the “YELLOW” wire from the air conditionerto the “Y” termina ... Dometic Rooftop RV Air Conditioner

The heat strip was never hooked up, there is three wires on top of the heat strip, grey, brown, and white , the thermastat is only hooked up with green yellow and red. There are two wires not hooked up a white and blue. There is a blue that is not hooked up on the unit. this is a package unit. I know that the three wires activate a relay to turn on the strip, and the white goes to both the grey and brown relays if they are some sort of relay. So I hope you can help me. drew


Hello! Please give me the make, and model # of your unit.Guru...............saailer ... Air Conditioners

I am replacing a white-rodgers thermostat with a blue wire connected to a terminal label '4'. The only other reference to a '4' terminal is in the honerwell installation manual which says that if there is both an r and 4 terminals on the old thermostat it was incompatible. I returned it for a ritetemp guaranteed to be compatible though I'm still not sure what to do with the blue wire. on the old thermostat the red wire goes to rc, the yellow to y, white to w, and green to g. Does blue just go t


Blue just goes to B ... Air Conditioners

I have an older Carrier Heat Pump which I am trying to update the thermostat control with a Hunter model 44550. The problem is that the wiring to the current thermostat is as follows, G= green wire, R= red wire, W2= blue wire, O= orange wire, Y= yellow wire, E= grey wire and C= white wire. If I am reading the schematic correct for the Hunter thermostate I am to wire as follows Green to G, Red to RC, Blue to W, Orange to O, Yellow to Y/Y1, C cap it as batteries are used. It does not tell me


JUMPER STAYS BETWEEN RC AND RH SO YOU HAVE INCOMING POWER FOR BOTH COOLING AND HEATING. THE WHITE WIRE YOU SAID C IS COMMON AND SHOULD BE USED IF POSSIBLE TO COMMON TERMINAL ON NEW STAT . IF THERE IS NO COMMON, THEN CAP IT BUT YOU'LL BE CHANGING BAT ... Carrier Air Conditioners

Thermostat with 4 wires, red, green, white and blue; no yellow wire to connect to new thermostat


... Air Conditioners

I need the wiring diagram for this thermostat, there are four wires that are hooked up red,white,blue for yellow and green. They connect to a honeywell relay that has five connection, y,g,w,c,and r, do i connect them the same way as colors match


On the fan relay hook up the red to r terminal the white to the w terminal and the green to the g terminal , now the blue needs to hook up to one of the two wires going to the outside condenser unit and the other going there goes on the c terminal . ... Carrier TSTATHCP Programmable Thermostat Air Conditioner

When i hook up a thermostat to the transformer to operate the furnace I have 4 wires, a red, white, green,and a blue one. they go to the board which has the letters r, c, w,y,and g. which color wire goes to what screw on this board.


Hi,I'm sure that the first thing that you see is that you have five terminals and four wires....so.... you need to have a t-stat that has it's own internal power or it is battery operated...This way you do not need the "C" at all.... ... Air Conditioners

I have a coleman evcon model number is DGAT070BCC the serial number is941259684. I need the to know the wiring color for the thermostat. I have red, blue, yellow,green, and white. so I can hook up my thermostat..


Ok what is this?Heat pump?gas heat? electric heat? what brand thermostat are you using?Why do you need a blue wire?Some facts Most thermostats come prewired for gas heat. so if you are using electric heat you ... Air Conditioners

Condenser outside Aight,,, so i finally got power to it outstide,, now, to get it to work i had to bypass some wires,,,, from thermostat to furnace and then to outside we wind up with red and white wires.... both hace power,,, now,,, the white connects to and follows a blue wire.... blue wire goes down and inside this white tube lookin thing... this thing is attatched to copper pipe,,, another or possibly same wire comes out,,, thats where the power stops and fail to turn the motor on,,, what is


You could br=e low on r-22. sounds like the thing is a pressure switch ... Ruud UBHC Air Conditioner

I have an amana rha36b2a heat pump and am trying to hook up a new thermostat. It's a pro 1 iaq t905 programable thermostat. I have hooked up the green yellow white and red (and ran a jumper wire from rh to rc). I also ran a jumper wire from W to Y. I ran the brown wire to C. The thermostat works great for heating but won't cool. When cool is chosen the heat comes on. Help! I know the O and B on the thermostat are the heat and cooling changeover valves but what should I do to connect them if that


... Air Conditioners

I need the wiring diagram to wire a thermostat to the outside unit. Which wire goes where ? My Thermostat has four wires, green, red, white, and yellow. My Outside unit has three wires that are not connected ... a red wirte to a transformer, a yellow wire to what appears to be a relay, and a blue wire to the relay switch. Thanks.


The thermostat wires are this, Red is 24 volts hot, Yellow is cooling, Green is fan,indoor, and white is heat.The outdoor unit wires up to the indoor units terminal board, not the thermostat.The red will go to the R or red 24 volt wire at the furnace ... Air Conditioners

I have a Trane Heater/AC unit no heat pump with a thermostat model 802AS32DAA that has seven wires. I am going to a five wire heating/cooling thermostat. What do i do with the two extra wires? old thermostat red wire-RC slot (24 V from A/C) white wire-W1 (???) yellow wire-Y (A/C Compressor) green wire-G (A/C Fan) black wire-B (?????) Blue wire-Y2 (????) orange wire-W2 (24 V to Furnace new thermostat therminals G Rc Rh Y/O W/B Y1 Can you tell me what wires to connect to each


From Honeywell : "If your old thermostat had Six or more wires, the replacement you have is Wrong!" ... Air Conditioners

Replacing the thermostat, took the old one off without marking the wires. Hooked it up by color and we get the furnace when we put it on cool. wires are green, red, yellow & blue (ground wire)on the wall. The new thermostat wires are red, yellow & green. Can you tell me which wires go where correctly?


The normal wiring for stats is white=w=heat,red=r=24volts,green=g=fan,blue=c=common,yellow=y=cooling.\015\012see what ties into your furnace board and match the terminals. ... Honeywell Air Conditioners

I have a Janitrol Heat Pump Thermostat HPT-18-60 and need assistance connecting my new Honeywell RTH7500D thermostat I have a Goodman Heat Pump System Indoor Unit Model#AWB24-05C REV D Outdoor Unit Model#CPLE18-1 Here is the wiring of the old thermostat Y-Yellow Wire G-Green Wire R-Red Wire O-Orange Wire W2-White Wire E-Blue Wire C-Black Wire Where should each of these be connected to the new thermostats terminals?


... Air Conditioners

I have a Intertherm P3rA-042K that runs the ac at the same time as the heat strips. I have a Honeywell RTH3100c I have the red wire at R the Yellow at Y the Green at G and the W2 at aux. I had a jumper between Aux and E like the manual said but it makes no difference. Also for some reason it was hooked up before with a blue wire joined with the red at the unit and the blue going to B at the thermostat. I removed the blue as i saw no use for it and it still doing the same thing. The unit froze up


Red, green, and yellow should all be from AC unit. What other wires do you have there, and are they separate from red , green, yellow? ... Intertherm P3RA-042K Air Conditioner

Th6220d1002 Need to wire new thermostat Base board heat using red & white wire. AC American Standard Air Handler using red, white, green, blue. Both units have their own transformer Thanks


... Air Conditioners

I'm installing a Honeywell RTH7600B programmable thermostat and replacing a Honeywell T87F2873. The new one calls for a Red, Green, White, and Yellow wire, while I only have a Red, Green White and Blue. How should I connect the new thermostat?


Every thing the same except take your blue wire and replace the yellow for it. So when you hook it to t-stat goes like thisRed to R White to WGreen to GBlue to Y ... Air Conditioners

Suburban sf30 rv unit.. I had a new board and limit switch installed. The service tech said it was working. I marked the wires when I removed the unit. I re installed the unit conecting the wires the same as when I removed the unit. I have 2 blue wires, 1yellow and 1 red coming from the furnace. There are 3 thermostat wires 1 grn, 1 wht and 1 red---The power source are 2 solid white wires and 2 blk and wht striped wires, there is power to the unit. I am at a loss as to why it will not work. T


... Dometic Rooftop RV Air Conditioner

I have a carrier air/heating unit with pump. It has 8 wires. Brown,blue, white, yellow, green, black, orange,and red. I'm trying to install honeywell thermostat. The wires from my unit are suppose to go into these honeywell (RTH3100C) thermostat slots. hONEYWELL WIRE SLOTS E Aux Y G O L R B C The only thing i have to go on is the wire colors from my wall which were not labeled or coded in any way. I am not sure about the model# of our unit because it is so old that the model# has faded away the


Turn the power off to the air handler. Open the control cover. Write down what color wires go together at the wiring terminal. All 8 wires are probably not used.\015\012Post the findings here.\015\012In most cases,\015\012E= brown-e ... Carrier Air Conditioners

Ruud contour acheiver 90 plus trying to replace bad thermostat with Nest there is a black wire which goes to a "V" Not sure if this is also a power wire? the other wires are red to 24 V; blue to 24 C; Green to G; yellow to Y1;White to w Any help to connect to Nest second generation thermostat?


... Air Conditioners