Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


Answers :

I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you set on the control panel is within 2-1/4 degrees (or 4 degrees depending on your unit model. Otherwise, the unit locks out the compressor until the electric heat coil bring the indoor temperature up to that level - and then will switch the compressor back on for heat pump operation. So the problem is not the control panel or the compressor, it the electric heat coil. The coil has two manual limit switches on it that may be tripped and should be checked. The coil can be easily accessed by shutting down the power, removing 4 screws around the air outlet, pushing the screen up and sliding the panel out the top. The power wires can remain in place while the limit switches are reset. Hope it works.
I had a problem with the heat not coming on in really cold weather. After much reserch and trial and error I a came to the conclusion that the heating coil was not coming on. The cool will reverse on the first stage, heating coil will come on in the second stage.
\012Take the front cover off of the unit. Unscrew the screws on the wire mesh and the two screws on the front below them. Pull out the wire mesh and put it aside. Slowly lift the heatng coil assembly striaght up. Grab the area you just took the screws out of. Once you get the coil out you will see the wires are conected to some terminals. On top of one of the terminals it the MANUAL RESET. It does not say it but it has a button on top. Mine was the one on the far left. Push it in till it clicks. Reassemble the unit in reverse. Mine works fine now.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you ... Amana PTH123B25AJ Heat Pump Air Conditioner

Amana PTH153B35AK This unit is less than 30 days old, heats fine cools fine, but when i have it in heat mode,set @ 70 or so, as soon as the room heats up, the unit will cycle into a/c mode and blow super cold air for about 5 minutes than return to heating. Sometimes it will reach the desired temp. and turn off like it is supposed to do, but for the most part it just cycles back and forth from hot to cold...Amana has the worse help/service i have ever seen, i was on the phone for an hour,everybod


This often happens if the unit is oversized or to close to a wall or object. ... Amana PTC153B35AK Air Conditioner

I have a 2 year old Duo Therm 15,000 btu Heat Pump AC unit in my RV. The compresser will not come on or even try, in either cool or heat mode, the fans runs in either auto or on position. I have a wall thermastat, all wires & connections at the thermastat and the controll box look good. The units was running fine, with no prior symptoms and then it just stopped cooling. I have a strong electrical background with all the meters, I am just not famaliar with RV AC units. Bud De Fore don


Hello Bud,First of all, is your wall thermostat a digital thermostat, like a 4 or 5 button Comfort Control Center? Is the ambient temperature under 40 degrees?Is your fan still able to run, are you able to control ... Dometic Rooftop RV Air Conditioner

Amana heat pump was working fine. Inside blower still working, outside condenser has 230 at contacts and 24 volts at time delay. unit will run if contacts pushed in by hand. high and low pressure switches are made. not sure about time delay, defrost board or defrost relay. i can by pass all the controls and it operates in cool mode for now. what five devices is most likely to be defective?


Time delay bad Tom ... Air Conditioners

My 8 yr old Amana heat pump, model RHE48A2D with Honeywell progammable thermostat in heat mode has the blower running constantly. When there is a 6 to 8 degree differnce between room temp and thermostat setting compressor runs as it should, the closer it gets to thermostat setting, it will run about 30 seconds, blower continues to run until getting just cool air, about 5 minutes, compressor kicks back on for 30 sec., continues to do this, thermostat shows it has reached set temperature,


Hi, It sounds to me like what you are describing is, that when it is 6 to 8 or so degree difference then the stat says, unit operates as it is supposed to but then before it satisfies the t-stat, it shuts the compressor down long enough to start cool ... Air Conditioners

Duo-Therm park model A/C unit MD# 39045. With the Tstat in the off position periodically I hear the compressor kick on and run for a bit then shuts off. Then turns back on again. All while in the off position. When in the cool mode the ac unit cools fine and shuts on and off fine. Could it be the stat? Bill


... Air Conditioners

I have an American Standard Heat pump. The unit is one piece is is outside. The problem that I have is that sometimes when the unit kicks on cool, the fan motor will not start. The compressor will run, but quickly freezes up. I can put unit in off and wait for thaw and then put back in cool mode and fan will start. Any ideas?


Definitely a low voltage problem then i would look for the obvious like loose connections good luck you might have to call a tech ... Goodman CLQ36AR49 Air Conditioner

Friedrich YM18 230 volt heat pump. The unit has heated and cooled well for about 5 years. Just started heating mode recently and the unit no longer heats. Fan runs OK. Was able to get the heat strip to run for a few minutes (smelled the dust accumulated over the summer burning off). Now, no heating whatsoever. When in the "Money Saver" mode, nothing happens. Fan will not come on and unit will not heat. With "Money Saver" mode off, the fan runs.


... Friedrich Air Conditioners

Carrier 38YXA036320 My Carrier Model 38YXA036320 Heat Pump will not run. Fan and compressor will not start in heat or cool modes. When I select cool, I can stand next to the unit and I hear things being energized but nothing happens except a humming sound.


... Air Conditioners

AMANA AC unit Blows heat in cooling mode


These valves do get stuck. They energize for cool and in the dead postion they heat. Your valve is stuck or not energized. Can you here it click or try to energize. If you dont hee the click you do not have voltage to the valve. The valve is powered ... Whirlwind FH-778 Air Conditioner

Heat pump goes str8 to heating strips compressor does not run in heat mode pump was manufactured in 03 installed in 07 and has sat dormant till now could it be wired wrong it is a ruud split unit with digital non-programable 2-stage heat and cool t-stat


I think that you have the right idea. The wiring is probably wrong. If you can trace the low voltage wires to the air handler. make sure that the Y1 wire on the t-stat is going to Y1 on the hair handler and then to the condenser. The Y2 wire should b ... Air Conditioners

Gas/pack, gas heat, elctric A/c, outside heatpump.3 ton ArcoAire unit. In heat mode fan on top of compressor runs, and fan blows cool air in room vents, the burners do not light.I have plenty of LP gas.No Heat!


The reason why the outside unit is running is because you are running the system in heat pump mode switch the thermostat to aux. or emergency and then the auxillary heat or the furnace will take over for the heat pump. ... Air Conditioners

I have a carrier Modle No. 38YXA042300. I am getting an H5 error message on my Thermistat Control. I have run the Fan only mode and the fan in the air handler unit works fine. On the unit when I ingage the manual override, the condener unit and fan motor runs and cools. The unit will not run when I put the Thermidistat on Cool mode. Can you help me. Andrew Construction Mangement Speicalthes, Inc.


On some carriers they have a lock out feature outside to reset shut down power to furnace for 90secs. and then restart ... Air Conditioners

My AC starts fine. But the compressor will over heat and shut down in higher temperatures (high 80's lower 90's. It has run without issue on some days like yesterday with temps in the mid 80's. The capcitor was changed but has not fixed the problem. If I let it cool down for an hour, it will restart and continue cooling the house until it overheats again. Amps are in the acceptable range. Unit was installed in 1999. Can you help diagnose this problem?


Most likey cooling fins are plugged and also my need new compressor or low on refrigerant or refrigerant oil. Could also have plugged intake filters in the intake. ... Carrier 38CKC036 Air Conditioner

I have a goodman heat pump (gsh 130241AA), it's 2 years old. the heat pump will not come on in either heat or cool mode. this is my downstairs unit, my upstairs unit works fine. the air flow is working fine, just nothing cool with the downstairs unit.


... Goodman Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

Amana #PTC153b50AJ ser 0410686783 Customer heard a pop in unit and it went off. Breaker was tripped. Reset breaker and unit runs in a/c mode but does not heat in heat mode. This is not a heat pump but electric heat strips. Unit says there is a manual reset for the heat but we have not located the reset. We turned power off to the unit to reset fault etc and still no heat. The flashing light just blinks once every 4-5 sec. Could use some help in diagnosis Thanks DK


... Amana PTC153B50AJ Electric Heat Air Conditioner

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan


The LG>LW5200ER AC is not listed as a heat providing unit. Click on link and this will give you the spec's\015\012\015\012 \015\012\015\012 ... LG LW5200ER Air Conditioner

I have a split system sanyo heat pump model # kmh0922. The evap. fan will not come on when called for in fan mode. When i put it to heat the indoor fan will also not come on. The compressor runs but the reversing valve seems to stay in the cooling mode. When it is put into cooling the indoor fan goes off after 15 seconds and will not come back on. (The condenser fan and compressor seem to act normal in cooling.) Any ideas as to what the problem could be? Thank you, Mike


Sounds like the blowers capacitor has gone bad ... Sanyo Air Conditioners

Hi. I recently installed 1.5 T, 3 * Split AC, LG. Whole day the AC works fine and no problem in cooling too. But once in 2 day outdoor unit start making thudding noise continously and does not stop for 4 to 5 second and after that indoor unit stops cooling and just fan runs. No cooling is done after that and room temperature keep increasing. The green LED of compressor in indoor unit is ON, compressor does not work. To achieve cooling again I have to switch off whole unit for like half an hour a


HelloSounds like the compressor is shuting down on high heat.There could be a couple reasons for this.1 Check that proper voltage is being supplied to compressor.2 Freon level may be low.This would be a service call.3 Ba ... LG Air Conditioners

Unit in heating mode only electric heaters run no heat pump, also when in cooling mode unit does not run, Power is on.


I understand that you have a heat pump that doesn't work in cooling mode , and if the thermostat is not for heat pump , it will not work.First be sure you have the right thermostat and then that is wired correctly. Let me know what kind you have and ... Air Conditioners

The heat and fan are running great, but in Florida it's now ac. time. The compressor does not come on. The unit is just blowing warm air. The ac hasn't been used since last November, at which time it cooled just fine.


Hi,Here is a tip about troubleshooting your air conditioner...\012There are many things that can cause your air conditioner not to cool... ... Air Conditioners

Amana ptc094b35am. Whoever knows this I will consider a GENIUS or definitely connected somehow ;-) There is a series of keystrokes on the membrane control panel that will allow the fan to run continuosly when the unit is on (not only when compressor or heater is on) There is no manual switch for this. It must be programmed in the CPU via a menu accessible with a sequence of keystrokes. The only keys are "on,off,heat,cool,temp up/down" I used to have the manual but i lost it. I don't expect much


Dear friend!There is no manual switch in CPU in maximum models. But, definitely there will be fan switch as the customer should rotate for LOW,MED,HIGH . Otherwise, press mode button, if it is, you will find fan symbol. Please check once ... Amana PTC094B35AM Air Conditioner

Hi, I have a 1.5 carrier mini split heat pump. I cant find the model number but believe it was made 2000-2003. This has the remote with the infra red eye mounted in the front of the main unit (like a tv). (There is no other controller as I have seen with other units). The unit is heating and cooling fine, however, it does not seem to be sensing the thermostat. Whether it be in heat or cold, it will turn on and run for about 10 minutes and then shut off and not come again. To get it to run again,


Hi,There are a few things that can cause that kind of problem....The unit could be low on charge and the thermistor on the indoor unit will sense the coil getting too cold and shut it down on a hard lockout....resetting the power resets t ... Carrier 38CKC042 Air Conditioner

Lsn122he/lsu122he runs fine in cool mode but in heat mode defrost symbol comes on and stays on = no heat operation. worked fine this past winter till end of season. note ac mode still works fine.