GOODMAN CMA80905CXBA FURNACE. INDUCTION BLOWER NOT ENERGIZING. GETTING 3 "BLINKS" FROM DIAGNOSTIC LIGHT (LOW PRESSURE SWITCH OPEN). THE A/C WORKS & THE BLOWER FAN COMES ON WHEN THE STAT IS IN THE HEAT MODE WITH THE FAN SWITCH ON. WHILE THE FAN IS ON , THE DIAGNOSTIC LED STILL BLINKS A CODE OF 3. THIS IS NOT A CONDENSING FURNACE. I BYPASSED THE STAT (W & R)TWISTED TOGETHER---SAME RESULT---DIAG LED COMES ON STEADY, THEN FOUR CLICKS, AND BACK TO THE CODE OF 3 BLINKS. CIRCUIT BOARD???? OR 120VAC NOT


Answers :

The pressure switch is closed before the draft motor closes it.the board is telling you that this is not right.pull the wire(either) off of the pressure switch to see if furnace tries to light.if it does,you should replace the pressure switch.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

GOODMAN CMA80905CXBA FURNACE. INDUCTION BLOWER NOT ENERGIZING. GETTING 3 "BLINKS" FROM DIAGNOSTIC LIGHT (LOW PRESSURE SWITCH OPEN). THE A/C WORKS & THE BLOWER FAN COMES ON WHEN THE STAT IS IN THE HEAT MODE WITH THE FAN SWITCH ON. WHILE THE FAN IS ON , THE DIAGNOSTIC LED STILL BLINKS A CODE OF 3. THIS IS NOT A CONDENSING FURNACE. I BYPASSED THE STAT (W & R)TWISTED TOGETHER---SAME RESULT---DIAG LED COMES ON STEADY, THEN FOUR CLICKS, AND BACK TO THE CODE OF 3 BLINKS. CIRCUIT BOARD???? OR 120VAC NOT


The pressure switch is closed before the draft motor closes it.the board is telling you that this is not right.pull the wire(either) off of the pressure switch to see if furnace tries to light.if it does,you should replace the pressure switch. ... Goodman Air Conditioners

I have a furnace 90+ . I have no power at the t-stat..no led, blank screen, and the blower will come on. The furnace is tied into a control panel. I can jumper the the unit at the furnace to have the A/C to come on. It will go thru shut down cycle and stop. 5 min. later the blower comes on.I've cut power to see if it will reset the board, no change in operation. control board has 24 volts with status light on but other lights off. All limit switches closed. I,m in need of sugestions Thanks.


Either a thermal switch is open or the pressure switch is closed at start up the system checks all of these before sending power to the T-Stat ... Air Conditioners

I have a suburban lp furnace and duotherm air/heat pump roof unit. duothern thermostat. 20 amp breaker kicked ( reset breaker) & furnace quit. NOW furnace fan comes on but does not light, and the front AC will not work either, when in the COOL position on STAT the unit blows warm air instead of cold. I replaced the Thermostat and a Tech guy checked the board in the furnace and it was OK. He also switched the board from the rear air with the front and nothing changed. Rear air and heat pump works


I'm not sure what the problem may be but you could try calling All\015\012Seasons RV Appliance Parts & Service. There number is\015\0121-800-344-0673 they have helped me in the past. That and there tech\015\012calls are free so it wouldn't hurt ... Dometic Rooftop RV Air Conditioner

When I set tstat to call for a/c, compressor outside comes on. Blower on furnace does not. When I manually rotate fan limit switch on furnace wall, blower comes on, blows cold air, and then goes off when I release the fan limit switch. I have a Honeywell 83251008a low and high voltage transformer, and Honeywell (I think) limit on off switch. I also noticed the 2 wires coming from the Honeywell Gas regulator are off. They were connected at the onset of the problem. I am not sure where to re


Sorry, you mean gas valve control? when you have only 2 wires, usually it doesnt matter which terminal as there,s no polarity differentiation at that locationYou should never rotate this dial by hand, you will bend the helix inside and fan will not o ... Air Conditioners

My 1996 Coleman Evcon furnace doesn't want to start. The fan comes on, but the burner doesn't light, then the unit turns itself off and the green led is blinking 3 times. What does this indicate? Thanks. Rod


... Air Conditioners

Its a trane unit model# TUE060A936K3 in cooling mode condensor comes on the indoor fan does not in heating mode every thing comes on but the blower fan does not there is not a led light blinking code lable on the unit i it looks like its giving 4 blinks pause and repeat 4 blinks etc. what does this mean


Hi,\012Either the vent is blocked or the pressure switch that tells it that the purge blower is running is not working right...for some reason that switch is not making contact and so it will not let it light..\012\012heatman101 ... Air Conditioners

I have a Coleman Presidential 7670 furnace in a mobile home. customer said it came on a couple of times by itself. I ran new wire, fan won,t shut off. Replaced fan switch, fan still won't shut off. Replaced t-stat, same problem. This is an older unit and has no board it has a fan switch a low limit switch, i,m guessing the other is a high limit and a fan relay. I have no schematic and am very frustrated can anyone help me please. Thanks. Brian from california


Brian, it sounds as if possibly the fan relay is stuck however, if the fan will not shut off I would suggest the following, Follow the wires from the fan to the relay on the relay disconnect the fan wire there and see if the fan shuts down if so t ... Air Conditioners

I have a 1985 Bryant central air Furnace model 395BAW048095 with a White Rogers 36E gas valve. The flue is metal and there is a fan within the furnace to create a vacume at the base of the flue pipe conection that turns on when a call for heat comes from the thermostat at startup to ignition. The spark fires but no gas is released by the valve for the pilot to lite. Added information: The blower fan is set to continually run, I replaced the pressure switch (306621) and the limit switch (HH12ZB18


... Air Conditioners

Heat does not come on. Furnace light blinks 3 times, indicating faulty pressure switch. I jumped the pressure switch, which caused the ignition filament to light up. However, it quickly shut off again. No gas comes out so the blower never starts up. Have checked the lines, they appear to be clear. Furnace is only about 6 years old. Any idea what is causing this and how to fix it?


Hi,When jumpering the pressure switch ...you need to let the blower start and then apply the jumper... the brain needs to see the proper sequence or it will not allow the gas valve to open...and when it shuts down the jumper must come off ... Air Conditioners

Coleman mobile home furnace Model #7966-756 will not turn on. The pilot light is lit, there is power coming to the step-down transformer inside the furnace. The reset switch is in the right position. It worked fine when i turned it off last spring, just wont start back up now. The blower fan will not even come on when i switch it from the auto position to the on position on the thermostat. Any ideas?


I had a similier problem, Check your neutral ground? also alot of power companies will come out and do a basic check of the voltages going to the furnace, and can offer advice for free. ... Coleman Air Conditioners

Rooftop air, when stat calls for cooling, fan comes on but no compressor. If I switch the stat of & on a couple of time manually, the fan and compressor both come on. Does this sound like the start relay going bad?


Good place to start checking for voltage, in and out of relay when triggered. ( careful, if not experienced with electrical, you have capacitors nearby that can zap you real bad if not familiar with them.) ... Dometic Rooftop RV Air Conditioner

I have a Coleman Evcon gas furnace model# DGAT095ADA last year I replaced the T-O-D #60T82 - 313675 fan switch and works fine. This year the unit started fine, but slowly started taking longer & longer to heat up, then finally not heating up enough to trip fan switch. Manually tripping fan switch resulted in some warm air through system, but not enough to heat a house. Gas comes on and is blue what would be my next course of action ?


... Air Conditioners

I have a U-42 Janitrol gas furnace that will not start the exaust fan nor will it light the burner but the blower fan will come on. I have two identical units. I've swaped the exaust fans and the unit that was working strarted the other exaust fan - put the known working fan in the non-working unit and it still didn't come on. I switched the thermostats and still no positive results. Any suggestions?


... Air Conditioners

When I switch the T-stat to (fan on) the blower won't come on unless I move the Fan limit up close to the 100 degree mark and then I move that limit back down close to 130-135 degree and after approx. 10 seconds blower shuts off. I'm not sure where that fan limit is supposed to be set at, it was originally set around 130-135. It's a 2 wire limit and the range is 100-140. I know the stat is sending signal, I get 24v on green term. at fan center relay. Thanks, Dave


To help you we need more info. What thermostat and what furnace or air handler. There are two circuits involved. One is the green wire or g terminal that switches the fan relay into high speed for ac. The other is the w white that actuates the fan cy ... Air Conditioners

I have a GE Zoneline model#AZ38H09DABM2 with a remote t-stat. The indoor fan runs constant. The compressor cycles as necessary. I have swapped t-stats with the other room, no change. The dip switches are in the correct position for using remote stat. It seemed to start this after some storms had come thru. I've come to the conclusion that one of the circuit boards is probably bad. But which one, and is this assumption correct?


I think you're right about the storms effecting some damage. I can't figure out from the diagram which circuit board would be bad, since there are two boards on this model. Here is a link to some diagrams on this model:\015\012 ... Air Conditioners

Carrier 58STA error code 31. the inducer fan worked last night and after several attempts of turning on and off the furnace switch i was able to get it to entually fire up. Today the inducer fan won't even come on and i am getting an error 31. Is it the fan, pressure switch, blockage or circuit board?


... Carrier Air Conditioners

My Frigidaire FSA 12 PA5C : - indoor unit shows a blinking ELECT LED + TIMER LED always ON + OPERATE LED ON - no fan working(no air coming out off indoor unit) - outdoor fan not working Please help. Any RESET button somewhere ?


... Frigidaire FAS184 Air Conditioner

If the condenser fan motor goes out, will the furnace fan still come on? my ac just stopped working, no fan either. breakers are good, took the doors off the furnace red diagnostic light says normal. 103 high for sunday tomorrow...


... Carrier 38CKC036 Air Conditioner

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

Ac works fine with fan in on position when fan is switched to auto position the fan stops and ac continues to run. the furnace will not start unless wires are disconected from control board and jumped.one extert said to replace control board and t-stat. that was done and still the same problem. this is a rv ac and furnace. thanks


What happens when you switch the wiring for the fan and the AC? ... Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

Furnace stopped blowing cold. 'Stat works, blower works. Went outside, condensing unit fan does not run, motor is excessively hot to the touch. Fan blades spin freely. I pulled the disconnect and switched the stat to fan on / no cooling for now but it's 94 degrees today... HELP! :-)


Hi!!\015\012\015\012Replace motor fan and capacitor, it is a very simple task. Turn breaker OFF. Then all you have to do is remove about four screws from the top grill, about four more that fasten the motor fan assembly, unplugg electrica ... Carrier 38CKC030 Air Conditioner

I have a 15 year old HVAC system that uses a Carrier Weather Maker 8000 furnace. When we returned from vacation last week, we noticed that the furnace blower motor would not turn on. The A/C compressor and condenser fan would turn on, but not the evaperator/furnace blower fan. I started a component test, but the LED just continuously blinked rapidly. The code associated with this is "Line voltage (115V) polarity reversed or twinning problem. How do I fix this?


The control board seems to be detecting reverse polarity, and my first thought is that the relay contactors are oxidized, but you could also have a bad startup capacitor, and/or control board.\015\012The only reason I say control board is becau ... Air Conditioners

I have a Sta Rite Max E Therm pool heater and when I start the unit, the fan kicks on but the heater never does. After 45 seconds or so, I get a " Service Heater" light. The circuit board had leds for limit switch, pressure switch, air sensors, etc, but none are lit. The ignition contol module has a blinking red led which the manual says is a "ignition lockout" issue. What is an ignition lockout? Do I need to replace the HSI Ignitor? Or could it be something other than ignitor? Thanks


Hi,How many times that light is blinking?Is it 3 times sequence?Let me know,so that we could proceed.Thanks!! ... Air Conditioners

Sanyo Condensing unit. blower fan doesnt come on unless unit runs,but unit only runs for about one minute and shuts off. led #6on cond. unit blinks and led on evap. coil #26 also blinks unit needs to be turned offon for it to restart.


First, the condensor fan is only supposed to run when the unit is on. As for the one minute run, then needing reset...this sounds like a "safety out". The air conditioner knows something is wrong and tries to protect itself. Being low on Freon wou ... Sanyo Air Conditioners