Evaporator Coil I have a Goodman A/C system (2 systems...1 for 1st floor, 1 for 2nd floor). The one for downstairs is 3.5 ton. the one for 2nd floor is 3 ton unit. Installed when house was built 5 1/2 years ago. The upstairs unit has had the evap coil replaced once, and repaired a leak once - 6 months ago. The downstairs unit has had the evap coil replaced twice -and is now leaking again. Model for the air handler is ARUF042-00A-1A. Goodman part# for the coil is P140142. Can I replace this coil


Answers :

Yes, just count how many pins per inch and replace with the same number of pins per inch.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Evaporator Coil I have a Goodman A/C system (2 systems...1 for 1st floor, 1 for 2nd floor). The one for downstairs is 3.5 ton. the one for 2nd floor is 3 ton unit. Installed when house was built 5 1/2 years ago. The upstairs unit has had the evap coil replaced once, and repaired a leak once - 6 months ago. The downstairs unit has had the evap coil replaced twice -and is now leaking again. Model for the air handler is ARUF042-00A-1A. Goodman part# for the coil is P140142. Can I replace this coil


Yes, just count how many pins per inch and replace with the same number of pins per inch. ... Air Conditioners

I have a 2.5 ton ac outside. the indoor unit downstairs in the basement is a goodman. a new a coil was put in about a month ago. which is a goodman product. ive heard goodman is not a good product. a


The inside coil and outside unit should be matching in tonages another word if you have 2.5 ton outside the inside sould be the same. it don't matter what brand name or who made it. ... Goodman CKL36AR36 Air Conditioner

I have a 4 ton Ruud HVAC system that is two years old. It is a 13 SEER unit. It is tilted slightly to the front of the evaporator to aid in draining the condensate. Two days ago, my daughter came home after being gone for a week. My wood floors are buckled and she has a large amount of mold in her bathroom cabinets. I had my HVAC man go by and he told me that no condensate was coming out of the evap unit. I asked him if it was blowing too hard and possibly blowing the water down the duct. He sai


1. Why would you tilt the evaporator to let the condensate come out never heard of this before it should flow at a level state.\015\0122. I think you have a problems in your condensate drain. ... Ruud UBHC Air Conditioner

To whom it may conern, I live in a 2 bedroom/ 1 bath 760 sq. ft apartment with a 2 Ton A/C unit. We had trouble with our a/c unit and the maintence (which is A/C licensed) replaced it with a 410A unit. He only replaced the outside unit and it did not want to cool. The manufacturer of the unit said that it already came with the right amount of refrigerant. So he cleaned the coil inside and it didn't work. Then the manufacurer of the unit recommended to change the coil which he did and i


He has really screwed it up you got problems you cant just replace the outdoor unit if he knew his job he would know that also those systems uses two different kinds of refrigerant oil and 410a must be pulsed in alittle at a time. I woul ... Air Conditioners

We installed a 4 ton downflow coleman air handler with evap coil Model number 1854s2m we did not change out the outside unit. the outside unit is a 13 year old 3 1/2 ton intertherm condenser the system is only generating a 10 degree delta T. My question is, this coil came with a factory TXV I am trying to find out is this a 10 seer or 13 seer coil is it compatable with the outside unit.


You have a missmatched system, for it to work try removing the orfice on the high side txv it is not allowing the evaperator coil to fill with refrigerant properly coleman and intertherm dont like each other since they control a large market in the ... Air Conditioners

I have a Carrier 4 ton unit model number 661CJ048-A which is charged with R-22 capacity is 9,25lbs. It has developed a leak at the evaporator coil. It has rust on the coils which from what I understand means the leak is there. Now currently it has only 3.25 lbs of R-22 left in it. I want to replaced the coil, but until I do I want to replace the R22 with R-134A, and be able to use the AC unit, until I can afford to puchase the coil, which I found one for $720 from a company in Florida. Do I need


First your system is 22 and 134A is a auto AC refrigerant. I have never seen it used in residential ac. I have been in AC business for 45 years. The new refrigerant is 410A or Puron. But you can not use it. Your outside unit is set up for 22. Mix 134 ... Whirlwind FH-778 Air Conditioner

Is it ok to replace outside unit of central air and heat and not the inside air handler ? The upstairs A/C( over 10 yrs old) is not keeping up with South Texas heat. The temp upstairs climbs to 84-86 degrees by the afternoon and takes 4 or more hours after dark to cool back down. I have cleaned the entire unit outside- no help. I have replaced the downstairs unit 2 yrs. ago and it works fine. I don't want to replace the upstairs air handler if I don't have to---much more cost.


I'm assuming you have had a competent Air Conditioning contractor look your unit over.if you trust your A/C contractor, why don't you work with them towards an answer? I would get an air flow and sizing analysis, a full equipment service/performance ... Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

I have an 8 year old 2 1/2 ton carrier compressor unit. I have already replaced the running coil and contactor. I now want to clean the coils and fan blades on the motor. I have never had reason to remove the top grill. I looks as though the fan motor is attached, and I don?t want to do anything stupid ?if I can help it? or damage or disconnect any of the wires. what is the proper way for me to access the inside of the unit so as to be able to spray off any debris that may be on the coils. So fa


Hey Bernie, it is possible to remove the 4 screws on the grill that the motor is mounted to (not the bolts holding the motor to the grill)and pull up and twist so its upside down and have someone else hold it as to not put to much stress on the wires ... Carrier 38CKC042 Air Conditioner

I have a Carrier 58DX080CC Forced air furnace that is leaking water onto the floor, but otherwise works perfectly. A service guy told me I need a new Coil, but it probably wouldn't pay to repair it, and that I should replace it. His quote to replace was about $6K. I found the part, Z7-58DX080CC-91CW at United parts supply for $890. The unit was manufactured in 1988 and is 90% efficient. What should I do? Buy the part and hire somebody to fix it? Buy a new one? The new price he quoted wa


Hi,If you are running a high efficiency forced air furnace then check the\015\012drain hose and make sure it isn't blocked or crimped. These furnaces\015\012tend to take a lot of humidity out of the combustion air (air from\015\012outside ... Air Conditioners

I do not know what ton condenser unit i have.It is a Concept High Effiency the model number is SB3OSA-4D Can you tell me what it is? I had the furnace and ac replaced about 6 years ago and was told the condenser was fine . Well now it's gone out and i found this one but I understand it's about 15 years old and i'm trying to see if they will match up. The unit i have is a Bryant 3 ton.


Unit you are describing is a 2 1/2 Ton ... Air Conditioners

Model ck42-1a compressor won't come on. I replaced the intake filter about a month ago. It was a pleated filter and was real caked when I replaced this month. Can that cause the compressor to go out? I have two units and the pipe coming in to the house is cold on the good unit but not on the bad. Could that be anything but the compressor? Low freon or a-coil freezing in the house?


The fact the filter was very dirty and the door partly open allowing non filtered air to enter the system leads me to a possible dirty evaporative coil on the furnace. That can cause poor airflow and iced up coil reducing airflow even more. In the lo ... Goodman CKL42AR42 Air Conditioner

I have a 11 year old, 2.5 ton trane package unit at my home. the tech added refrig 3 weeks ago because the unit was freezing up. coils still freezing up. air coming through vents only getting down to 70f. tech came back last friday. trane said there must be something (trash) in lines. tech evacuated system, purged lines and recharged. air from vent only gets down to 74f now. compressor seems to be working fine. i just thawed coils with water. they were frozen completely.


After the tech added refrigerant, did the coil freeze up after he left, or was it a day or more before it started freezing again and are you running the unit on high cool? You either have a leak, which would usually take some time to leak out enough ... Air Conditioners

My parents had a frigidaire eletric heat pump installed 2 years ago. almost right away a soured water smell came out of the vents. service tech sprayed the coils and installed a black light. did not help. service tech said frigidaire did have this problem with some of its units. so the unit was replaced. new unit done fine for about 6 months. now the smell has came back mainly when the cooling is on. any suggestions. i dont believe it is the unit. they had a gas it pump before.


I feel that the gas lis leaking from a very minute hole which gets enlarged when the unit is cooling (it gets hot and enlarges). And it could be leaking from anywhere. A quick temporary remedy is to seal the possible leaking points with super glue or ... Frigidaire Air Conditioners

Hello, my HVAC is constantly freezing, even after freon is added. I was told that I have a leak in the coils and need to chance the air handler - the outside unit is about 10 years old - air handler about 18 years old. I would like to get only the air handler for my R22 outside condensing unit. My question is if in the future can I use this same 3.5 ton air handler with a new 410 condensing unit once my outside unit needs to be replaced. In other words can a Goodman air handler be used firs


I'm new at this and I can't tell how old the post is but I'll contribute anyway.You probably have fixed the problem by now. I wonder what part of the system is freezing up. I don't have a lot of experience but I know you can get frost where there ... Goodman CKL42AR42 Air Conditioner

Hi. I have an older house that is about 1100 square feet. It currently has a 2 ton AC unit with a "2 ton" coil. I would like to replace the condensor with a gently used one from my neigbor that is "3.5 tons." Can I do this?


No a/c systems should not be over sized. an a\\c unit does 2 kinds of heat removal latent and sensible.latent heat removal is the removeal of water from the air sensible is the actual cooling of the air. a larger than neded a\\c system wont run as lo ... Goodman CKL60AR60 Air Conditioner

Have a R-22 Rudd ait handler. Replaced the compressor with a 1.5 ton Goodman unit. My home is 1300 SF in NJ On hot days during the peak of the day the system seems to stop working for a period. The Compressor fan still runs but the compressor is not. My air handler fits the cubby hole and I am limited for space, as I considered replacing it. A tech has suggested replaceing the TSV valve with an adjustable and set it to 8. He also said there are supplemental coils that could be added to the com


If your home is 1300 square feet 1.5 tons is not going to cut it you should have at least 2.5 ton A/C unit. sounds like your system is to small. let me know if this helps you out. ... Ruud UAKA037 Air Conditioner

I have a blown BDP 7.5 ton Condsor unit. The old unit is R22. I want to replace it with a new BDP which has R410A. Question: I am being told that If I flush my old R22 Air Handler Coil & install a TXC valve. I can run the new R410A unit on the old handler. Is This True ?


I've done what you are describing - "however" you could void the warranty on the new condenser - by not having 'matching' coils (inside/outside). I would do some serious checking with whoever you are buying the new condenser from. \015\012\01 ... Air Conditioners

Evaporator coils on 12 ton unit are leaking on to floor


... Air Conditioners

How to replace a evap coil on a carrier package unit-Out the top?This thing is leaking refrig-only a little over a year old,wht is the best procedure for replaving the coil


Hi, the coil will need to be taken from the top, or by removing a side panel. Its located on the return side. The freon will need to be recovered unless the unit is dry. You can use a close quarter tubing cutter to cut it as close to the coil inlet a ... Air Conditioners

I have a Lennox CH23.51 series coil unit using R22 freon installed one year ago. Compressor is 9 years old. Down the road when replacing compressor (R410A ), will CH23.51 unit be compatible after changing out a valve?


This evaporator core is R-22 / R-410A compatible. The Thermostatic Expansion Valve (TXV) is for R-22. If retrofitting to R-410A, a new TXV metering device would be required, but the evap. core itself could be re-used (as long as y ... Air Conditioners

I have two compressors-one for the upstairs and one for the down stairs. Both compressors are working but the air flow for the upstairs basically does not come out. You can hear the unit running but no air upstairs. Down stairs the air is working. Is there any way to turn the airflow up or adjust it to send more air upstairs. I had the capacitor replaced in the down stairs compressor a few weeks ago and for the upstairs about 1 1/2 years ago. when the air downstairs started working a few d


Hello,Thanks for using FixYa.I suggest that you try to have the fan that routes air upstairs checked. Its possible that the motor is already going bad.I hope this helps. Thanks and good day.HotRatchet ... Air Conditioners

I have 2 cental a/c units in my home. The 2 1/2 ton unit cooled great until abut a week ago. Now I cannot get it too cool lower than 78-79 degrees and it runs constantly unless I turn the themostat higher than 79 degrees. The freon level is correct, the coils are clean and so is the filter. What do you think the problem could be??


I like this one it challenging first do you know the refrigerant pressure?should be at least 65 psi for r-22 has any thing changed in the ducting? is the fan turning the correct direction?dan ... Air Conditioners

I have a 23 year old Goodman 4 ton HVAC system that has done well but is needing more repairs more frequently. I am looking to replace the unit but anything I install will be placed on credit which is not ideal as we recently dumped a lot on our credit to adopt a child. We live in mid/north Georgia in a 2 story with basement that we partially finished. The second floor is hotter than the main floor but is mostly offset by leaving the fan ON instead of AUTO. Anyway, our serviceman recommended a R


A 23 year old unit will be a major energy hog.You will see a massive improvement even with a less efficient unit,but go with the energy efficiency.The price of fuel is going to keep going up,and you will be using the furnace for many years.I'm in Ohi ... Ruud UBHC Air Conditioner

I am the person with the Amana AC. I gave you the model and serial numbers awhile ago. I am wondering if this helps you to come up with another solution. Every repairman that's come out has told me the unit is working fine and there is nothing they can do. My duct work has recently been cleaned. The coils have been cleaned. They said they just do not make AC's to last long anymore. I am not buying that. My unit was working fine until the valve broke. I have had the company that replaced


You must have a heat pump. The valve in question is the reversing one?A whole lot of folk don't know how to replace them. You gotta place a wet rag on the valve and have a wickedly hot *** torch with brazing knowledge to do the job right. Once ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"