Having problems with your Air Conditioners ?

I have a Goodman 2.0 model no. ck24-1B and would like to change it to a 2.5 Ton 13 SEER R-410A Air Conditioning Condensing Unit. My furnace is a Goodman model # GMS8, GDS8 or GHS8 are they compatible

\015 Is this unit to old to find out about\015

Answers :

If it is a 410a system now you would have to change orfice. if its a r22 system now no way.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Goodman 2.0 model no. ck24-1B and would like to change it to a 2.5 Ton 13 SEER R-410A Air Conditioning Condensing Unit. My furnace is a Goodman model # GMS8, GDS8 or GHS8 are they compatible


If it is a 410a system now you would have to change orfice. if its a r22 system now no way. ... Goodman Air Conditioners

The other day. my American standard air conditioning unit (Allegiance 10 model 7A0030A100A0) would not stop running. The furnace was not running, yet the air conditioning unit was on. I could see condensation on the line running to the furnace. The next day the unit would not even start running. I shut it down, tried it the next morning and the unit ran for about 30 sec and stopped. Could the capacitor need replacing?


Yes, that might be the problem but in this case you need a qualified technician to test system and find real cause of problem. ... Air Conditioners

Amana 90% model #GUCAO45AX30 SER# 0109143635 UNIT MAIN BURNERS LIGHT UP THEN SHUT DOWN IN A FEW SECONDS. DRAIN LINES ARE CLEAR, VENT PIPE CLEAR OF CONDENSATION. I BYPASSED T-STAT JUMPERED R-W NO HELP, INSTALLED NEW FLAME SENSOR STILL SHUTTING DOWN. UNIT HAS TWO PRESSURE SWITCHS OFF INDUCED DRAFT MOTOR, HOSES GOOD CONDITION AND TIGHT. I HAVE HAD PROBLEM WITH WATER IN 2 INCH ABS VENT PIPE, NOT SLOPING BACK TO UNIT, THIS ONE SEEMS TO BE CLEAR. SHOULD I CUT PIPE AT FURNACE AND TRY TO START ?.. MAYBE


Check to see if the flame rod tip is in the flame(like the hot junction on a thermocouple). the pressure switches are a normally closed switch and a blocked flue could cause them to open. the circuit board should run through the safety switches and c ... Amana PTC074B25AE Electric Heat Air Conditioner

I HAVE A GOODMAN FURNACE GMS8 WHAT IS THE LARGEST SEER RATED AIR CONDENSER WILL WORK WITH THIS UNIT.


Seer is not a problem....18 would be fine.depending on the size of the blower,you may have limitations on tonnage of the ac. ... Air Conditioners

GOODMAN AIR HANDLER MODEL CA*F4961*6A*+MBE2000**-1 HAS HEAVY CONDENSATION IN THE TOP OF THE UNIT WHERE THE ELECTRICAL /CIRCUIT BOARD IS LOCATED.THE UNIT IS LESS THAN ONE WEEK OLD. THE COMPANY THAT INSTALLED IT HAS CHANGED THE DIP SWITCH SETTINGS AND TODAY PUT IN LARGER COLD AIR RETURN DUCTS.STILL IS THE SAME.ALSO THE COILS UNDERNEATH HAVE HEAVY CONDENSATION ON THE BOTTOM OF THEM.WHY CANT THEY FIX THIS ONE WEEK OLD UNIT.THE OUTSIDE MODEL# IS SSZ140601A*THE HOUSE IS 2480 SQ FT. THE OUTSIDE UNIT IS


This is not even a repair issue.If it is hot out and it's on quite a bit,there will be much condensation.However,condensation on a circuit board is never good.Since it is only 1 week old and you can see this serious of a potential problem,especially ... Goodman Air Conditioners

Outside unit will not turn on. Inside fan works fine. This intertherm unit is an upright, 6yrs old. Model number unkown. Fan will turn. No hum coming from unit. inside condenser sits on furnace model # E2EB-015Hb. Freon charging is outside on the lines coming from outside unit.


Hi! You may want to start on having the power supply checked. Good cause why the unit won't power up. Have the compressor checked too just to be sure. ... Intertherm Air Conditioners

My goodman central air unit quit working after a storm. The circuit breaker is not blown. The furnace fan kicks on when ac is turned on at the thermostat but unit outside does not operate. Is there an internal fuse or capacitor on outside unit. Thank you very much, Bryan Model CKL36-IF Goodman


1 posible cause.the thermostat supplies 24 volts to the outside unit to control the contactor if you hear a ligth huming on the outside unit this is the being activated. if this is the case then\015\012\015\012 check to see if any ants are in ... Goodman Air Conditioners

I have a heil furnace / air conditioner unit. The heil is model # N9MP2075812A3 serial# L024970895. It has an intl comfort evap coil Model EPD24B15C2 serial# X120393352. It was installed in 2003. I turned on my air conditioning and the furnace keeps cycling on and off. I checked the filter and it is new. It is a gas furnace and the gas valve is blinking stadily which means it is ok. It humms....tries to turn on.....blows for about 10-20 seconds....turns off...tries to turn back on...again and ag


Not sure I understand the description.\015\012You said the "furnace" keeps cycling on and off when you turn on the AC.\015\012But you must have meant the AC cycles, because if the actual furnace went on, that would an extremely seroius pr ... Air Conditioners

Have Coleman-Evcon heat pump system. Model DRHS0421CB. Condensing unit has intermittent no run condition. I replaced the contactor, as it was a few years old. I eliminated the thermostat from the equation by twisting together the RYO wires at the thermostat sub panel. This makes the air handler run and MOST of the time also makes the condensing unit come on as well. When it does run together, it cools great. Suction and discharge pressures are normal. The float switch is ok and no water prese


Elimate the items not needed to test the unit.\015\012Disconnect the defrost power board and set air handler to run.\015\012Disconnect the thermostat and hold contactor switch in closeing connections to the compressor and condensor fan. ... Air Conditioners

This is our first summer to use our Goodman central air conditioning unit and we are having alot of condensation on our windows and doors. We need to know if our service tech installed a unit too small for our home since we never had this problem with the brand that he removed to install the Goodman. Any response will be greatly appreciated!


Your issue may be just the opposite of what you suspect. If the unit is too small, it will run continuously, but may do a better job of de-humidifying the space because the A/C unit has more time to pull humidity out of the air.\015\012\ ... Goodman Air Conditioners

Keeps freezing We installed a brand new Goodman Condensing Unit, Model #GSX130481, Serial #1304691511 and installed a new coil, Model #96-8W4N-0p/96-8, Serial #M0425130485 (Mortex Brand)in the existing Air Handler. The unit keeps freezing up. Can you give any insight on what might be the problem?


Low air flow or low on refrigerant. ... Goodman Air Conditioners

I do not know what ton condenser unit i have.It is a Concept High Effiency the model number is SB3OSA-4D Can you tell me what it is? I had the furnace and ac replaced about 6 years ago and was told the condenser was fine . Well now it's gone out and i found this one but I understand it's about 15 years old and i'm trying to see if they will match up. The unit i have is a Bryant 3 ton.


Unit you are describing is a 2 1/2 Ton ... Air Conditioners

Need recommended sub-cooling and superheat for condenser models # MSS-30-E, 9 seer with Copeland compressor model# SRD6-0225-PFV with indoor evap. coil model # MEVC-30. Also MSS-36-E, 9.15 seer with Copeland model #CRH3-0275-PFV with indoor evap. model # MEVC-36 . Both compressors have a suffix -C1. Both are split units with electric furnaces. This info. would be very helpful. Thank you, David


Superheat should be 8 to 12 degree's. Sub cooling around 18-22. I like to use superheat that way I know the coil is doing all it can do. ... Air Conditioners

I have a Goodman Furnace model#GDS80703AXBC.The unit is one year old and ran fine until the gas got shut off accidently outside at the meter.Unit was cycling with no gas for 2 days.we turned the gas back on and the unit is showing one light blinking for over cycle trys.The unit did eventually start up but it does not fire up after each time the thermostat is calling for heat.The unit has been running like this for about 10 days now.I have replaced the Diagnostic computer, glow igniter,flame sens


The only part not replaced so far is the gas valve. Because the gas valve is getting power does not mean it is opening.You could also have gotten trash(corrosion/scale) in the valve orifice and or the burner orifices.Is there a drip ... Goodman Air Conditioners

My central air conditioning unit model edd2x30ba2 outside unit is on and turning, but the inside unit will not come on it has a lot of condensation on it. is there a reset switch and where is it located?


Turn off power remove cover feel indoor motor if hot bad or bad relay ... Kenmore 72055 Air Conditioner

I have a three year old Goodman Furnac /AC unit Model nuber CAPF030B2C. When I turn on the AC it blows a 3 Amp blade fuse in the furnace. If I just turn the furnace on or the fan only on it does not blow. What should I check for?


I would first look at all the wires and make sure the insulation has not rubbed off somewhere and causing a short, after that it means one component is failing and requires special tools and testing that should be done bu expert who has those tools a ... Air Conditioners

Have a York Stellar 2000 model E1CS024A, serial MAWM027260. Replaced electric furnace last year with Goodman Gas Furnace. Installer disconnected old York thermostat T874R1145 and replaced it with a programmable Honeywell Focus PRO 6000. He also removed the York interface panel in the furnace room and simply connected W-W & BLK-BLK to the outside unit saying that it should work. Needless to say when it turned hot yesterday and I powered up the Heat Pump and requested cool on the thermostat nothi


... Air Conditioners

We installed a 4 ton downflow coleman air handler with evap coil Model number 1854s2m we did not change out the outside unit. the outside unit is a 13 year old 3 1/2 ton intertherm condenser the system is only generating a 10 degree delta T. My question is, this coil came with a factory TXV I am trying to find out is this a 10 seer or 13 seer coil is it compatable with the outside unit.


You have a missmatched system, for it to work try removing the orfice on the high side txv it is not allowing the evaperator coil to fill with refrigerant properly coleman and intertherm dont like each other since they control a large market in the ... Air Conditioners

Need wiring diagram for goodman heat pump for thermostat, furnace and ac unit,model# for ac unit GSH130301AB


... Goodman Air Conditioners

Goodman condensing unit model # GSC130421BB what is the units tonnage?


... Goodman Air Conditioners

I have a Goodman gas furnace (model GMP 108-3). It recently stopped working. It is an hsi unit. The HSI appears to be working - I don't see any cracks or anything. When I flip the switch at the unit, the fan kicks on, the HSI gets hot and then the top burner lights. Problem is that it doesn't stay lit and it doesn't travel to the burners below it. I took out the flame sensor and cleaned it with very fine sand paper, but that didn't seem to do anything. Any ideas?


On your flame travel tube sometimes something gets in that and blocks the path. Now this is what I found one time when same problem happened. I took it apart and found a dead **** roach in the path. Took the bug out and it worked perfe ... Air Conditioners

Furnace is a York Model#p4ugd12n09001a probably installed around 1991. The air condition was working fine. couple of days ago nothing was working. Blower wont tun on, air conditioning unit wont turn on. I did have the fan on the on position on the thermostat so it was always on until it stopped.


Probably a bad low voltage transformer. ... Air Conditioners

Install 2 ton 13 seer goodman furnace coil and condensing leak test with 110 psi of nitrogen overnight good the next day pull vacuum no leaks start up unit charge unit to proper charge check the next day system hadlow reading on suction side ice up


Goodjob, now check the valves stems for leaks.! .....Thank-you-very-much! ... Goodman Air Conditioners

Can we convert a Coleman Evcon model DGAT075BDD, Furnace into a centralair unit by simply adding a condensing unit?


... Air Conditioners

Trying to find what model type of capacitor was used in my Goodman Air Conditioning unit Model CK60-1C, serial number 9806465759


Contact Johnstone Supply either by phone or email ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1431 seconds