I have a Yonan split Ac model # kfr-35gw/gx1b split system the problem is the L1 wire coming from the unit outside to the relay is burning what could be the problem I checked the relay and it seems ok could it of been because of a loose connection. If it is the relay then the whole pc board needs to be replaced none of the parts are serviceable which leads to the second problem is I can't get anyone form the company who makes this to respond


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Yonan split Ac model # kfr-35gw/gx1b split system the problem is the L1 wire coming from the unit outside to the relay is burning what could be the problem I checked the relay and it seems ok could it of been because of a loose connection. If it is the relay then the whole pc board needs to be replaced none of the parts are serviceable which leads to the second problem is I can't get anyone form the company who makes this to respond


... Air Conditioners

I have a yonan Ac model # kfr-35gw/gx1b split system the problem is the L1 wire coming from the unit outside to the relay is burning what could be the problem I checked the relay and it seems ok could it of been because of a loose connection. If it is the relay then the whole pc board needs to be replaced none of the parts are serviceable which leads to the second problem is I can't get anyone form the company who makes this to respond


... Air Conditioners

Circuit Board needs to be replace but there are none available. According to the service technician, the problem with the board is the capacitor. Would it be wise to pull out the board and have the capacitor replaced by an electronic shop.


I've never tried that, but a good electronic shop might be able to do that for you; however, it's a risk. \015\012You can also try to contact the manufacturer for a list of their recognized service providers. It's possible the board is availabl ... Samsung Air Conditioners

I have a 10 year old Mitsubishi mxz 325v Multi unit airconditioner that is on the blink. The local service company has been trying to fix it since August and even with the assistance ? of Mitsubishi Tech Support they still are not confident they know what the problem is. So far the following parts have been replaced after dicussion and even an attendance by a Mitsubishi Technician from Tech Support. Main Board and Noise Filter Outdoor Main Board Relay Printed Circuit and Power Monitor Bo


Sadly this is a poor service without a proper sincere logical advice. To spend $2500 for a 10 year old set is surely too bad , as they have finally almost constructed a new set except the body/condensers.\015\012In the first place ... Mitsubishi Air Conditioners

My coleman Evcon model DGATO70BDC 1994 starts up and then locks out. The pilot lights and then furnace runs for maybe 2-5 minutes and all that is still running is the air chamber fan. I am thinking of just replacing all parts that could be responsible the problem. There's not much there as probably you know. There is no circuit board just basic electronic ignition,relays thermo senors and etc.. Any help would greatly be appreciated. James


Does your furnace have an air flow sensor? Blowing out the lowest tube will sometimes clear it and allow your furnace to operate. Lack of differential pressure across the burner will cause a lockout. ... Air Conditioners

I have a Sta Rite Max E Therm pool heater and when I start the unit, the fan kicks on but the heater never does. After 45 seconds or so, I get a " Service Heater" light. The circuit board had leds for limit switch, pressure switch, air sensors, etc, but none are lit. The ignition contol module has a blinking red led which the manual says is a "ignition lockout" issue. What is an ignition lockout? Do I need to replace the HSI Ignitor? Or could it be something other than ignitor? Thanks


Hi,How many times that light is blinking?Is it 3 times sequence?Let me know,so that we could proceed.Thanks!! ... Air Conditioners

When I turn my electric a/c to heater it makes a repeat tac sound quite loud. An a/c tech opened the metal box on left side where the fuse is located and said that the board and relay needs to be replaced. My a/c heating unit is an American Standard made by Trane model TWV036B140A1. What do you think it might be the problem? What are the technical name or numbers of the parts the a/c tech is referring to? Where he or I can buy it and for how much? What is the guarantee? Thanks. Tommy reply2t


It sounds like the tech was referring to the blower relay. The blower relay on this unit originally had a small circuit board mounted to it. It's only purpose was to allow for delay off-time of the blower at shutdown. In other words, once the command ... American Standard Air Conditioners

Blower fan stays running. Fan relay attached to small circuit board (coil tabs [timer?]). Capacitor on small circuit board had ''fallen out'' of ic board. Tried to get replacement board, and was sold just a standard relay - told that relay alone replaced the previous relay -and- circuit board configuration (?). Problem still exists (no change). Also changed thermostat just to eliminate as a possible cause, but seems like problem must be in the fan relay area. Question about the wires attache


... Carrier Air Conditioners

Problem with my Frigidare air condioner the model# is FAM156R1A. Not sure if the pc board needs to be replace? im unable to change any of the settings. I've reseted it and it dosen't fix the problem. Basically none the buttons are there work, but my ac still blows cool. its just stuck on the same everytime.


Yep sounds like the main control ic on the board is bad, replace it. ... Frigidaire FAM156R1A Wall/Window Air Conditioner

We have a GE Zoneline Heat / Cool Model 2800 (with Heat Pump Model 3800). The blower works but no heat. The A/C works fine. My brother works for Marcone Appliance parts. He removed the housing to the control board, and suddenly the heat started working. It stopping the next day. We replace the control board, but no go...it still won't heat. What could be the problem?


... Air Conditioners

I have a whining sound coming from my Air Conditioner in every mode except Fan. I cleaned the back part of the the unit with a duster and the sound continues. I also could duplicate the problem after turning off the unit for about 10 seconds and then turning it back on. Does a part need replacing?


I am assuming this is a window unit. That whining sound probably is the compressor itself. Not much you can do about it but wait till she goes on out and then replace it. They do make a product that can be added to the compressor called Gemline 88 oi ... Air Conditioners

I have a 98 Sunnybrook w/Dometic Furnace-A/C thermostat control. Just the other day, the furnace would keep running and it got very hot in the trailer until I could shut it off. The thermostat was set kind of low, but we needed to keep a little heat on in case we got a freeze. Do I need to replace the control unit which is electronic to correct the problem? I am assuming the thermostat went bad, but am also assuming it is a part of the control unit?! Thanks for your help. Dave


... Air Conditioners

Control board I've got a Bryant Plus-90 furnace, model starts w/ 350MAV. The status code LED on the control board does not come on. Is this a problem with the control board, or is the issue somewhere else? How do I diagnose the problem? If it is the control board, what is the part number that I need? I've found part number 325878-751 that says it works for most model numbers that start with 350MAV. The word "Most" worries me. I can't find the part number on the current board.


Hello, check to see if the board is receiving 120 volts at the L1 and neutral terminals, if you are then the board will need to be replaced, if you are not getting power then trace the wirimg back to where the voltage stops, for example could be a ba ... Air Conditioners

On a goodman model number aruf030-0100a-1a when the unit is off the fan motor will run at about haft speed i replace the board with relay on it but having same problem what i need to do now thanks


Try change the fan sequenser. ... Air Conditioners

Goodman AR60-1 I have a relay that has gone bad, part #T92S7A22-24 and was replaced with a Time Delay Board # PCBFM131, which is completely different. could you assist me with placing the wiring to the correct terminals


... Goodman CKL60AR60 Air Conditioner

Model #UHQA-101B Need help with problem? I just had a relay replaced and the unit is now sputtering ever now and again while the heat is running. The sputtering noise sounds very ******* the system. What areas should I check and how to check them or what to look for? If you could help this would be great.


The first thing that needs to be checked before more parts get damaged is the secondary or control voltage from the transformer. with the system off this should read 25 to 27 volts a.c. on average. low voltage has several possible causes, if you do n ... Ruud UBHC Air Conditioner

Evaporator coil needs to be replace again. Installed w new manufactured home; 09/2005. Replaced 05/30/08. Needs to be replaced again 09/17/09. All due to leaks. Freon was added. Currently has small leak; estimated life is 5 to 90 days. Warranty for part good til 09/2010, but local original installer Weirich Air refuse to replace free of labor charge of Aprox $650.00. Nor will company Nordyne pay for labor. I also feel that Weirich/Nordyne should reinburse me for previous $809.74 labor & service


The manufacture is only required to supply the part free of charge thru its warranty period. the installing company probably would only give a 1year labor warranty and honor the pparts thru the manufacture for 5 years but unless you paid additinal fo ... Intertherm P3RA-042K Air Conditioner

Blower motor my air conditioning goes off as soon as it goes on I have a service contract with my local oil company and my repair man said I need a Bryant blower motor 8539DL 51923EEOS I have been told the part is not available because the unit is to old and they recommend replacing my furnace and air conditoner for over $15,000 I am hoping I can buy the replacement motor somewhere so I can save for the future replacement of my units Is this part available anywhere?


YES!! A universal replacement is readily available for around 200$ or so and the labor for the installation should be about the same. Sometimes it's hard to tell the Tech's and the Sales apart....GL! ... Bryant Air Conditioners

I have a Carrier 58DX080CC Forced air furnace that is leaking water onto the floor, but otherwise works perfectly. A service guy told me I need a new Coil, but it probably wouldn't pay to repair it, and that I should replace it. His quote to replace was about $6K. I found the part, Z7-58DX080CC-91CW at United parts supply for $890. The unit was manufactured in 1988 and is 90% efficient. What should I do? Buy the part and hire somebody to fix it? Buy a new one? The new price he quoted wa


Hi,If you are running a high efficiency forced air furnace then check the\015\012drain hose and make sure it isn't blocked or crimped. These furnaces\015\012tend to take a lot of humidity out of the combustion air (air from\015\012outside ... Air Conditioners

Replacement parts I have a Danby DPAC9006 AC unit, and the flesible exhaust hoses need to be replaced. However, they have been discontinued for this model. Any suggestions for alternates I could use, or where to find discontinued parts?


... Danby DPAC8099 Air Conditioner

Ank youI have a frigidaire model fas296n2a2 air conditioner. It is electronic and has a remote as well. I cannot adjust the fan speed. it only runs on one speed. i already replaced the p.c. control board part # 309901501 and the display control board part # 309901601.this did not solve the problem. any ideas?


Did you install the new main control board yourself or no? I would have a professional diagnose the unit since it is a big BTU sized unit. ... Frigidaire FAS296R2A Air Conditioner

PAID AN A/C COMPANY TO COME OUT AND FIX MY A/C. THE OUTSIDE COMPRESSOR WASN'T COMING ON. AFTER AN HOUR HE DECIDED IT WAS THE ''DEFROST BOARD'', AND SAID HE DIDN'T HAVE ONE ON HIS TRUCK TO REPAIR IT AT THE TIME.IF I GET THE NEW PART, IT DOSEN'T SEEM THAT HARD TO REPLACE, BUT I KNOW HOW THAT CAN GO SOMETIME. THE TOTAL REPAIR BILL WOULD BE $260. IS IT REALLY HARD TO REPLACE THE PART MYSELF? I DO REMODELING WORK, BUT NOT REAL FAMILIAR WITH A/C. IF SOMEONE COULD TELL ME THE BASIC STEPS PLEASE.


The defrost board isn't hard to replace. It just about matching up wire for wire on the unit. BUT and a big but.......if you do something wrong and burn the board up, then you have to buy another. At least this way, you know that he will put the p ... Air Conditioners

My heat pump will not come on in HEAT or A/C. I thought I might have a simple defrost control board problem, but still no go after replacing the board and the defrost relay. I checked the pressure switch and it is not tripped. I've checked all the circuit breakers and they, too, are all set. I've checked the outside unit using the "test" switch inside on the start relay and the unit will come on, but won't stay running on it's own. When I select HEAT, I wait the necessary five minutes for the un


Hi; Need more info. How old is the equipment,look on the outside unit data plate it will give the built date usually in the top right corner. Also heat pumps can run with a faulty defrost board. I would check for control voltage at the secondary side ... Ruud UBHC Air Conditioner

I have a domestic rear a/c that is just a year old. It clicks and changes from heating to cooling and then shuts off. After replacing to control boards we are told that is probably a coach wiring problem. My question is. "could it be a ground problem related to be replaced a/c?


That is a very good place to start because there may be a wire grounding causing the unit to shut off after changing over to cooling mode. It's what one faulty wire can cause, so check your wiring first. ... Dometic Rooftop RV Air Conditioner

Same here Code 46. Had to replace the mother board last year which seemed to fix a similar problem (but code 61 at that time) - condensor tries to start but kicks off several times then code 46 displayed. Need another new circuit board or is it really a thermistor problem?


It could be suction pipe thermistor or the mother board again but before replacing them it may be just shortage of gas because it will trigger either or both code 46 and 61 as well. ... LG Art Cool LA181CNW Split System Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific