Does the RUUD UBHA14J11SFAA air handler have a filter which needs cleaning or replacement? I change the cold air return filters regularly but have never serviced the air handler in the ten years it has been running.


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Does the RUUD UBHA14J11SFAA air handler have a filter which needs cleaning or replacement? I change the cold air return filters regularly but have never serviced the air handler in the ten years it has been running.


... Ruud Central System Air Conditioner

Always running I just bought this house with an existing Ruud system installed and have noticed that the air is ALWAYS running. It never pushes the heat past the set temp to make it turn itself off it just runs at the set temp forever. Needless to say this is a killer on the electric bill and I am seeing if I can fix it hear before having to call in someone to service it.


Some newer high efficiency units using variable speed DC motors are designed to maintain a temp and wonrt shut off by design. Does it maintain a temp you desire ? It may be normal hard teling without seeing it. ... Ruud UBHC Air Conditioner

I have a Thru-Wall Carrier 18000 btu Air Conditioning Unit Model KCA 183 P. This was installed in our mobile home in August 2007 but never used as there was only 30 amp service. The previous owner has either lost or missplaced the Operator's Manual, and as we have just now upgraded to 60 amp service, would like to use this unit. We can get it to run, but as it is digital we aren't sure what the icons represent, and how we should set it. We would love to be able to get the Operator's Manual


... Carrier Air Conditioners

My house is 1308sq foot living. My outside unit is about 4yrs old, the air handler is about 3yrs old. It cools decent but when I have family over (appx 10 people or more) the a/c keeps running and never cools down. Is there anything I should be doing like cleaning the coils every so often in the handler? Or clean out the lines where the water drains? I change the filter usually monthly..


Yes, change the filter every month or so, more if you have pets. Spend the extra dollars and get filters you cannot see through! If you can see through it it is worthless to start with. You should see if it gets dirty and needs changing. You may have ... Goodman CLQ36AR49 Air Conditioner

I have an APAC Sundowner installation in my home at Glenorie NSW. We have owned this house for 14 years and it has been serviced in that time and generally runs well - I expect the original installation would have been completed when the house was built in 1992-93. The house is a north facing single level homestead, with a dark green corrugated iron sloping roof, so the ceiling space gets quite hot even though we installed rotating air extractors ten years ago. The ducting is not in good s


Hi,I would most definitely contact the HVAC company and go over the work with them first before finishing the painting...That leaves you more options...Also check to see if they can just "re-insulate" the existing duct work... ... Carrier LCA061P Air Conditioner

I have a goodman 5 ton a/c model gsc130601bc, it isn't cooling, keeps tripping main 60 amp breaker, blower is running at air handler. Tstat is calling for cool and contactor Is pulled in, it has a service breaker close to unit. I checked 80/5mfd capacitor with field meter, checks 79.5/4.9 mfd


... Air Conditioners

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


Have you hard wired your fan motor to verify that the motor and or the capacitor are good? If you do a continuity test of the motor leads(with electricity off of course) you can see if the motor has open or grounded windings. ... Ruud Handler Air Conditioner

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


We tried to bypass at the Tstat. Thanks for your time and interest. ... Air Conditioners

Air Conditioning I have a ruud system with the air conditioner outside and the air handler upstairs in the attic. My systems appears to be running, and I can feel cold air at the vents, but I can barely feel it. Like there is no flow. The fan outside is running and the unit in the attic is running. I have no clue what the problem is. The large coil coming from the heat pump outside is cold and has condensation on it. It also seems to have a little ice. It has been extremely hot here in Ge


Open the access panel on the air handler in the attic and take a look at the evaporator coil. If you have no airflow, and you just changed the air filter, then you probably have a buildup of airborne crud on the coil that's blocking airflow. \015\01 ... Ruud UAKA030 Air Conditioner

Outdoor AC unit runs for about 2 minutes after air handler shuts off


Hello, it is possible that the new thermostat has some type of time delay built in it. But typically this would shut of the outdoor unit first and then the air handler. ... Air Conditioners

I have a Dometic 15,000 btu, ducted air conditioner in my 30 ft fifth wheel. It seems like the unit has never cooled very efficiently. Dealer has checked out. I noticed yesterday, outside air over 100 degrees, that the air conditioner would put out good flow of cool air, but once in a while compressor would stop running even though not close to thermo setting. Fan would continue running. Any suggestions?


Not sure what the pressure sensor should ohm at but i would suspect a faulty sensor if everything else checks out. Its very common for these sensors to exhibit issues when they get hot. Also you may have a filter in the system that may be restricte ... Dometic Rooftop RV Air Conditioner

We are having a problem with the central air. The thermostat was replaced with a regular house thermostat. Now the air conditioner stays running until it trips a breaker. When the breaker trips, it is not because there is an overload of things running at the same time because we dont usually run much during the day. It usually runs fine at night; much better than in the daytime. Today, we cleaned the breathers/filters on top of the camper thinking that there might be a build up or something m


Breakers are thrown by the build up of heat. And over time breakers do get weak try changing your breaker. Use the same size its plenty big. be careful and dont get bit by the electricity. ... Air Conditioners

I have pane air handler, split sistem. When it runs air conditioner it also runs emergency heat at same time. If I tern the sistem off the emergency heat is still on. It blow worm air. How can I solve this problem? I changed kontrol board for new one, but it did not help. help me please...


You have a stuck relay.\015\012Locate the relay that powers up the heat strips and verify that it is closed when power is disconected.\015\012\015\012If it is, replace the relay.\015\012 ... Air Conditioners

Lawn mower cut control cable going to outside unit. a 3 amp fuse was blown inside air handler. spliced cable togerther, color to color and replaced fuse. air handler will run but compressor does not come on


Can you take an A.C. voltmeter and see if you have 24v.a.c at contactor on outside unit, if not recheck for same at control board inside to see if the same then you can start isolating the trouble ... Ruud Central System Air Conditioner

I have a Goodman CKL24-1k air conditioner. I live in a townhouse in Louisiana on the 2nd and 3rd floors. I set the temperature to about 73 degrees during the day so I can sleep bc I work the graveyard shift and the temperature never reaches 73. It stays between 85-90 on the 3rd floor where my room is located. The unit will run all day and never shut off. this air conditioner equip to cool and split level apartment about 960 sq ft?


... Goodman Air Conditioners

In heat mode thermostat set for 68 and room temp on thermostat reads 68, but unit contines to run. The air coming through vents is cool air. Unit never shuts off, runs constantly. This is the case when outside temp is 30 degrees or 45 degrees.


Could be under sized unit or fan relay on unit. ... Goodman PHKJ024-1 Air Conditioner

My air handler runs but does not cut out, once it reaches the temperature set in the thermostat the external unite kicks off but the fan in the air handler does not stop running.Looking for a relay or switch that's hanging up but not sure. Please help.


If you have old thermostat and it worked when you switched to scheduler, try reinstalling it to see if problem persists. depending how it was wired, shut off sensor may disable furnance controller (not air handler). odd thing is handler runs nonstop ... Ruud UBHC Air Conditioner

Carrier central air 38ckc060301 problem, unit will not start, air handling blower runs, can hear hum at outdoor unit. I turn the unit off at themostat. let sit for ten minutes, turn back on at themostat, unit starts and cools. Will run through serveral cycles and then not start until I repaet process, any thoughts?


... Carrier Air Conditioners

Intertherm furnace We have an intertherm furnace that won't complete a heating cycle. I have to hit the reset button until eventually it will or won't. In the winter months we have to have it serviced pretty regularly (we live in Alaska). The service guys say that it gets sooty and they have to clean the eye (something like that). They can't come up with a reason for this other than the combustion air is not clean. It pulls air from inside the home and we don't smoke so I don't think we are real


On the oil burner is an air intake adjustment that will adjust the air flow that will reduce the soot. It sounds like they are not adjusting this properly. ... Intertherm P3RA-048K Air Conditioner

Condensing unit continues to run after air handler is stopped. Problem is intermittent. Thermostat replaced. Suspect air handler relay. which one?


When this happens, most often you'll have a stuck contactor coil on the condenser. If you buy it , it should cost $20---to 15.00 and you can add if you turn off the power (240volts) and the furnace power! ... Goodman Air Conditioners

2 weeks ago one of my units stopped working properly. It got warm during the night even though I heard the unit running. I shut it off and called for repair service. They changed the thermostat and it worked again,until 2 night later same thing. I called another repair service and he found that it needed freon. For the last 2 weeks it has been cooling fine even with Fla.hot temperatures of 85-90 degrees. Last night same problem unit running and not putting out air thru the vents. Shut it off for


Sounds like the coils inside the air handler/furnace are freezing up. likely cause is the freon charge is incorrect (probably undercharged). it may have been correct when the tech did the work but some may have leaked out. it is slightly possible too ... Goodman CLJ36AR42 Air Conditioner

Hi,I am really hoping to find someone to help me if possible. I have a one year old carrier infinity 4ton 17seer condenser and a 5ton variable speed air handler. I has worked fine but now i am getting a SYSTEM MALFUNCTION on the thermistat. When this message appears the air handler continues to blow and only the fan on the condenser continues to run but NOT the compressor so it is not cooling. At times it begins cooling again but then later stops cooling and shows the same malfunstion message. I


Hi,\015\012If this si what I am thinking it is, it will be very hard to find and prove.... \015\012The compressor windings have aflat spot and if the motor stops at the right place it will not atart. The voltage goes way up and kicks out ... Air Conditioners

I'm having a problem with my heating and air system, my heat only works on emergency heat ( and run 24/7) if i turn it to regular heat it only blows cold air. i dont think my outside unit fan is turning( i could be wrong about this one) how can i fix this problem so i dont have to run my emergency heat all the time


If your Heatpump's fan isn't running but your compressor is, your fan motor is out. If nothings happening at all ensure your getting power to heatpump (ex: breaker tripped, fuses blown on outside power switch, or fuses blown in breaker box?) ... Air Conditioners

I have an old RUUD central AC unit that started blowing hot air. I set the thermostat to off and set the temp gage higher than air temp to turn the unit off and save money, but inside blower unit runs constantly. I'm trying to save money to have it serviced, but noticed my electric bill was higher that last month when the ac was working. The bill was about 4 times higher than the winter when ac is off and the gas heat kicks in. Can the blower running constantly cause this power usage and what is


HelloOkay did you check your thermostat to see if you have the fan switch on auto? The switch must be on auto or the fan will continue to run. If the thermostat fan switch is on auto then there is a malfunction in the thermostat probably ... Air Conditioners

My air stops running inside before it get to the temp. Its set for but the outside unit keeps running and after a minute or two the air will start blowing inside again but the outside unit never turns off until it gets to the desired temp but because it stops and starts so often inside it takes a long time for it to reach the desired temp. Inside


You have a possible thermal overload problem in your furnace blower motor dirt will cause this problem when it doesnt allow air across the windings of the blower motor if not dirt the motors going bad and getting hot use a shop vac and eliminate dirt ... Goodman CKL36AR36 Air Conditioner