Error Message I have a DeLonghi Pinguino PAC L90 portable air contitioner - last night there were thinderstorms and the electricity went out for a second. Now the unit flashes a message "Fsomething (looks like an L with a line through the middle)". I have unplugged the unit for several minutes but the message still flashes when I plug back in. No response when I depress any of the buttons on the unit. Is there a reset button hidden somewhere? Is there a more serious problem? Help!!


Answers :

It's actually "Ft", which means "Full Tank".  The instruction manual says to drain the internal safety tank through the drain hoses.\015\012
\015\012To drain the tank, open the cover on the rear of the appliance.\015\012Pull out the 2 drain hoses, take off the caps, and let all the residual water flow out. \015\012When all the water has been drained, place the caps back on the hoses and put the hoses back inside.\015\012
\015\012It also says you need to clean the filters and let them dry thoroughly before putting them back.\015\012
\015\012This is also the procedure for "End of Season Operations."\015\012
\015\012Hope this helps!
I have a DeLonghi Pinguino PAC L90. When the Ft message comes on I drain the 2 hoses on he back and replace the caps. Each time I have returned to find a large puddle of water under the unit with the Ft message on. Help it is ruining my floor.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Error Message I have a DeLonghi Pinguino PAC L90 portable air contitioner - last night there were thinderstorms and the electricity went out for a second. Now the unit flashes a message "Fsomething (looks like an L with a line through the middle)". I have unplugged the unit for several minutes but the message still flashes when I plug back in. No response when I depress any of the buttons on the unit. Is there a reset button hidden somewhere? Is there a more serious problem? Help!!


It's actually "Ft", which means "Full Tank".  The instruction manual says to drain the internal safety tank through the drain hoses.\015\012\015\012To drain the tank, open the cover on the rear of the appliance.\015\012Pull out the 2 drain ... DeLonghi Pinguino PACL90 Portable Air Conditioner

Goodman a/c j41 fan not running, turned off and on at fuse box, took a look at the box next to a/c unit and opened the box on the wall and pulled the plug and pulled the plastic panel off, there is no fuses. So i put back together and turned the a/c unit on, now at thermostat the snowflake is no longer flashing, some cold air coming out of vents, but outside a/c unit fan still does not run.


First you need to disconnect all power. Try spinning the fan blade, if it spins freely, then try moving the shaft from side to side to see if there's any side play. If not then the bearings are OK. If there seems to be some drag when your spinning th ... Goodman CKL42AR42 Air Conditioner

My fridgedaire window unit A/C and heat won't come on. I had replaced an outside light fixture a couple of weeks ago and had turned off the circuit breaker that affected this unit too. Now the unit won't come on AT ALL. I've unplugged the unit, then flipped breaker off then on again. Then plugged back in and hit "Reset" Button on the plug, then waited at least 3 min. as instructed, but still no power. The light on the plug doesn't even come on when I hit the test button. Could it be a faulty cor


Plug a light into the outlet used for the A/C, if the light does not come on when reset then the circuit breaker that provided the power to the outlet need to be reset or replaced. ... Frigidaire FAS257S2A WallWindow Air Conditioner

I have a Sharp portable room air conditioner model CV-P10NC. The power plug RESET button and TEST button will not click in order to check out the power plug as the unit will not turn on. They did test O.K. at first but the unit would still not come on. Can the power plug back be taken off to check out the fuse inside - or since it is a type of built in circuit breaker maybe it does not have a fuse inside ? The instruction manual states that " This air conditioner uses a fused power plug". The un


The fused9G.F.C.I.) cord you speak of is probably the G.F.C.I. built onto these units by design, can you or someone you know get access inside the unit and :Hot-Wire" the units cord and,bypass the power cord ( Just To Test the Unit)and see if it stay ... Air Conditioners

Have a amana window ac unit. It has triped the breaker. When i turn the unit off and plug it back in, it still trips the breaker. I took the cover off and disconected the control panel and it still triped the breaker. I then removed the power to the capasitor and pluged in the control panel and the breaker did NOT trip (stayed on). Do I have a bad capasitor. If i replace it will i need to dead short it out. Or will it self drain by diod?


Chances are that you may have an bad capacitor also there are chances of short circuit ....So use an continuity tester and check whether oyu have any short circuit and then replace it... ... Air Conditioners

I have a Sharp model number AF-S125FX that shuts off and I get the E1 message . I have cleaned the filter and tried the E 1 solution that was listed for a differant model number and have had no luck. unplugged the unit,pressed the power on and held until it went through the steps ,unplugged again,plugged the unit in again ,powered it up and it will run for about five minuets then shut back off


Please check the relay of the comppressor and also the capacitor of the compressor. Check also if there is any issues in the controller section that can bring in the errors.\012open and tigten all connectors, take a test on relays to manually s ... Sharp Comfort Touch AF-R120EX Air Conditioner

Good morning, Panasonic Ac unit model CS-PC30EKF, stops working after five minutes and the timer light starts flashing. The only way to switch back on is to switch the unit off and on again, however the problem is still happening. Please advice on problem Regards Cliff


First the thing that's causing the thermostat to act up Could be the thermostat being bad. The blinking does it continue for hours on end and nothing runs? If so the thermostat LOCKED OUT. Now what caused this???I proceed wit ... Air Conditioners

Had a power outage a while ago for 24hrs, so I went around and turned everything off and once the power came back on I went and turn the heating back on at the mains switch. Now it is coming up with "hailing master networker!", it's a Brivis unit HE20E. Have tried turning mail off and leaving 5 mins. Message is still there.


Pull the controller off the wall, press 3+5 buttons down, then replace on wall while still pushing buttons in.... a group of 5-6 bars will appear, then when it says type in address -turn dial to 1. this will re set it. ... Air Conditioners

My MovinCool Classic 26, is not working it is showing on the led screen, flashing FAIL HP, what do i do to get it back going. I reset the plug and it comes on for a few seconds and quits and show same message. please help.


Hi dbarnard2025,Just  a guess here, but have you checked that the filters and coils are clean?regardscol www.digitalcontrols.com.au ... Movincool Classic Plus 26 Air Conditioner

My window unit fell out of the window and hung by the power cord that was still plugged into the wall. I was able to grab the cord and pull it back up. I reattached the power cord and now every time i turn on the power it trips the breaker. is this the shorted power switch where can i get one.


Its most likely is not the switch. It is most likely the cord though. Due to the excess strain on the cord it has probably cut through the rubber coating on the wire and connected to the frame and grounded the hot lead. Fix the cord and ... Frigidaire FAX054P7A Wall/Window Air Conditioner

I have three window ACs in my entire mobile home(double wide). One at the back of the house, one in the middle and one in the front. Each one is plugged into its own outlet. If I try to run more than one AC at a time the breaker pops. They seem to all be on one breaker as well as several other items in the house(ceiling fans, alarm clocks, etc..). The breaker has a 30 on it and the AC's Im not sure what they use but the AC units say to use a 15 amp. What can I do to fix it and can I do it myself


Usually when I install a window A\\C I prefer to run a dedicated circuit for the very reason that your encountering. Sometimes if you use a heavy duty extention cord you can find a circuit thats not used very much to plug into. Extention cords run in ... Gibson Thru-Wall/Window Air Conditioner

I have a goldstar air conditioner model R0801E that starts spraying water from the fan outlet after it has run for approximately 1 hour. I have checked the drain and it is not plugged, nor is there any obstruction to it, I have in fact drilled a hole into the 'formed' drain channel on the bottom which leads to the drain nipple located on one back corner. i have tried tilting the unit in order that gravity might assist and it still blows water enough that i can't use it or it will ruin the wall,


Seems i have the problem resolved by doing the following:\015\012\015\012increasing the thermostat setting from 25* C to 29*C, this will reduce the load on the cooling condenser,\015\012ensuring that the vent is set for 'fresh' as o ... Goldstar Air Conditioners

My Mr Slim Model # MSH09TW suddenly is turn off in the middle of the night. Then comes back on for 5 minutes, then stop and blows nothing( with the green light on). I've had the HVAC people service the unit, tested and did a setback, replaced the batteries in the controller and the problem still exists! What needs to be done?


It sounds like the thermal overload it kicking it out. The thermal overload is to keep it from starting a fire. Something is getting hot inside the unit. ... Mitsubishi MSH09TW Air Conditioner

Haier Portable AC (Model #HPRD12XH7) won't turn on, and a red light has appeared. Also, the display shows the text STOP. The machine has been unplugged and then plugged back into the socket, and still the problem is persistent. We've only had this unit for less than three weeks, and I would like to know if it would be easier to just return it or is there some way to fix this problem?


... Haier Air Conditioners

Blinking lights... mega cool, timer, and power light are blinking. I emptied the water out of the ac unit like it says to on the back of it. Lights still blink and I reset the plug. It then will turn on and after a minute or so it blinks the 3 lights again and shuts off. What could this mean?


... Sharp CV-P10LC Portable Air Conditioner

Installed two new 3312020 controlers wired with inst will only pick up zone1 all dip switches off on front unit exept furnice zone 2 on back unit old controlers only had one inside air temp i ordered two new ones still nothing on back unitwhy will it not inl back unit


... Dometic 3312020.000 Comfort Control Center II CCC2 Multi-Zone Kit

Sharp Air Conditioner AC09RLCSYS isnt cooling properly. Very moderate to low cold air from unit. At one point small bits of ice came out of indoor unit when on auto cool. Unit was switched off immediately and then turned back on after a few minutes with no additional problems, however still is not cooling properly. Unit is only eight months old. First used for cooling with no problems and great cold air, then for heating during winter. Now back to cooling and not getting the cold air like p


Unit may be freezing up if blowing ice crystals. Let thaw 24hrs try again. Make sure condensation drain line is cleaned out. ... Air Conditioners

I replaced my outside unit with a 3 ton goodman heat pump unit. My old unit was a 3 ton bryant and the compressor burned up in it. I left the old unit under the house since it seemed to be in good condition. the pump worked fine on ac to start off. But then you had to switch it in heat and back to ac for it to work. So the tech replaced the expansion value and put filters in both lines. I still have to switch it back to heat to get the ac to work. The tech told me that i would have to repla


You said it had rwo filers on the line. I know one is a liquid line drier. If you have one on the suction line it need to come out ASAP. The trash in the line can be removed by running in cool.pump down unit replace drier. While the unit is pumped ... Air Conditioners

E1 error code displays when unit is plugged in I have a wall unit with about 10,000 BTU capacity. Two days ago, it quit working and displayed the E1 error code. I unplugged the unit, let it sit for 10 minutes and plugged it back in. It started right up and worked fine until this afternoon, when it once again shows the E1 error code. What does the E1 error code mean and how do I get this unit working again? [email protected]


Highly annoying issue error code E1. After hours of fan operation, the error code E1 will appear on the seven segment LED temperature display. This error code is intended as a reminder for the user to clean the air filter. However, ... Haier hwr10xc6 Air Conditioner

I left my house and came back and my unit was shut off. There are other things plugged into the same outlet and they are working fine. I checked the fuse just to be safe anyway. I unplugged the unit and clicked the reset switch on the plug, the light is green but i show no power on the unit. Please help! Hot in Houston with no a/c!!t


Hi,\015\012 \015\012If neither the fan nor compressor is running in you’re A/C the possible reasons are… 1...no power to outside unit...\015\0122...bad contactor on outside u ... Fedders AER08F2A Air Conditioner

Hi, I have an 8,000 BTU unit. The unit is about 5 years old. It was running fine, no problems at all. Then whan I went to turn it back on after a few days-nothing. No noise, no air, nothing. It just did not turn back on. Before this happeend it cooled, it reponded to degree changes all was fine. The green light button on the test and retest comes on, but there is not a sound from the unit itself. Its like you would hit a power button that was not plugged in (but it is). This problem occur


After changing or cleaning your Filter, you need to reset the A/C. Follow the procedures below:\015\012\015\012Disconnect the power plug from the power supply.\015\012Clean the air filter.\015\012 ... Sharp AF-S80FX Air Conditioner

My portable a/c continues to leak water from the bottom when in use. I have a hose attached to the spout in the back, but it still leaves a puddle and almost nothing drains out the back. It's a sunbeam sca102rpc1, 10,000 btu model. I have the unit level on a few 2x4's off the ground, so the drain off from the spout is all down hill. but yet the unit must be leaking because the water is in a puddle at the bottom under the unit, not the drain pan.


It sound like the coil inside could be dirty. I have had the same problem with air handlers, when the coil is dirty or the filter is dirty it creates a back pressure and causes the condensation to drip off away from the condensation pan. ... Sunbeam SCA102RPC1 Portable Air Conditioner

My unit is 4 years old. I always turn it off when I leave for work in the am and turn it back on when I get home in the pm. Last night I turned it on at 7:30pm. When I went to the front of the house about 45 minutes later, I noticed the unit outside was trying to turn on but would immediately turn off. I checked the breakers in the garage, turned them off and back on but still had the same problem. The fan inside the house is running but unit outside will not kick on. I looked for a magic


It could be a few things.. It could be the capacitor - which the most economical to replace first..\015\012\015\012If you are not really very mechanically inclined - get a trained pro to come out.. It is very dag ... Air Conditioners

Ductless split system, single zone, gives trouble display. Operation light flashes 6 times rapidly, then both Operation and Timer lights flash 5 times at 1 second intervals, then the timer flashes 1 time at 1 second interval. What do we do? The unit doesn't put out heat. I only feel air when I click the Coil Dry Button, but the Trouble Display continues. Unit will not shut down. I flipped the main switch, connected to the heat pump, on the exterior of the house, but it started back u


What make and model is it? ... Air Conditioners

LG airconditioner LM-2166E2L Split unit. Indoor unit flashing 5 flashes after power surge. Indoor board was replaced , zener diodes were blown after surge.fault still remaining. Please advise James the fisherman


How do you shout it of ... Kenmore 6000 BTU Single Room Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1148 seconds