Having problems with your Air Conditioners ?

I have a Pinguino Pac CT 110 portable air conditioner vented out a window. When I run it, the floor on the sides and in front of the air conditioner get very wet, although it is dry directly underneath. It doesn't seem to be leaking or blowing water, so what can I do to fix this problem?


Answers :

The only part of the unit that has water is the condensation tank, try to inspect thoroughly or observe the said part. Also check if the drain hose is snugly fit .
You can download owners manual of your unit at http://www.delonghiusa.com for your reference.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Pinguino Pac CT 110 portable air conditioner vented out a window. When I run it, the floor on the sides and in front of the air conditioner get very wet, although it is dry directly underneath. It doesn't seem to be leaking or blowing water, so what can I do to fix this problem?


The only part of the unit that has water is the condensation tank, try to inspect thoroughly or observe the said part. Also check if the drain hose is snugly fit .You can download owners manual of your unit at http://www.delonghiusa.com for you ... DeLonghi Pinguino PAC T100eco Portable Air Conditioner

My air conditioner doesnt blow cold air turns on and blows but the air flow seems to be only a little house gets hotter and muggy


This is most commonly cause by a lack of freon in the system. Unfortunately, the only solution to that is to call your local A/C company and have a certified technician come and charge your system. The reason you need to call a professional is beca ... Air Conditioners

Air conditioner runs for a few hours and it works - it cools the house. Then it stops cooling - the fan still runs but it doesn't blow out cool air any more. It seems like it's overheating or something. It will blow out cool air if it has not been turned on in a while but once it's on too long it stops. I was told it could be the fan motor and the a/c guy changed the fan motor today but that didn't fix the problem. Now he says it might be the compressor or that I need a new system. I'm jus


The things I would check:\015\012Is the system properly charged with freon? Sytem may be overcharged.\015\012Is the compressor out on internal overload at the point of failure? If the overload isnt tripped and the compressor is having tro ... Air Conditioners

My Fujistu AST9LSACW split system air-conditioner wont blow cool air. the outside unit AOT9LSAC doesnt seem to be working at all. The power light stays on but the timer light flashed about 15-20 times a minute. please help...


There are two things you can check outside before calling a service technician. The first is the breaker to the outside unit. There is a breaker or disconnect near the unit. If there is nothing wrong with the electrical supply, check the refrigera ... Fujitsu Air Conditioners

Air conditioner comes on fan only. the compressor doesnt seem to be coming on. the is no cool air blowing. the unit is brand new and was jusy installed.


There will be option in remote to on the fan and compressor separately may be you would not have on-ed the compressor through remote or else there would have been any loose connection in the wire which connects the compressor ... Friedrich Air Conditioners

I recently replaced my thermostat to digital and the air conditioner works great but the heat doesnt seem to get hot enough like it is blowing out room temperature air. when i replaced the thermostat there was an extra wire (orange) that didnt have a terminal to go to. I'm not sure if someone forgot to hook it up or if thats the problem with my heat?


Sounds like you got the wrong thermostat.\015\012The orange wire is for the reversing valve, which reverses the flow of refridgerant and changes the system from cooling mode, to heat mode.\015\012\015\012If your thermostat has no te ... Ruud Central System Air Conditioner

Bryant air conditioner - outside unit will not run - before it quit running, air temperature in house rose from 65 degrees to 75 degrees. Inside fan continued to blow - air smelled like a car air conditioner that ran out of Freon. Bought Freon - need to know where to add it. The heat pump model # BF-163S bi directional but also coming from unit is another line that runs same direction with same type of valves. Air conditioner model # 697CN030 - B


... Air Conditioners

I had power blink off for a couple of seconds and then came back on. The Amana air conditioner RCC30A2E seem to be On but no cool air was blowing. I check breaker it was ok. I preceeded to check thermostat, I notice 24v was not present and by bypassing the thermostat the air conditioner still was not blowing cool air. I went outside and notice the fan was not rotating.


Check for fuses in the 24v wiring. Was anything running outside? The 24V X-former is located in the air handling unit. check for voltage on the air handler. if present, check output voltage at X-former. You should have 24V ... Air Conditioners

I have/had 2 GE 8000btu wall air conditioners and at 3 years old, both of them within 2 weeks of each other had stopped blowing out cold air, just now the way a fan would blow. It almost seems to me that GE has purposely made these air conditioners to stop working properly at a certain time so I should buy new ones. I replaced one of them already with another brand, now I have to replace a 2nd one. I can't really afford to do this. Is it possible that they have both run out of Freon? Otherwise I


I doubt the freon would be gone its a sealed system unless someone was pokin the coils kids love to bend the fins for some reason could need a capacitor is the compressor starting ? humming ?running ... GE AJCQ08ACB Air Conditioner

I have a frigidare FAM157S1A Air Conditioner, when plugged in the fan blows air but not cold air. Compressor not working, I pushed control panel to cool air, blows cold air for a few seconds, then unit blows the breaker. How do I fix it. It has been only used for two weeks and this started.


Your compressor motor is no good Time to replace unit ... Frigidaire FAH085N1T Air Conditioner

Sharp 10000 BTU 38db portable air conditioner blows cold air for 2 minutes then blows warm air for 5 minutes then turns off for 20 minutes then repeats this process. How can I fix this problem to blowing only cold air? The filter is clean, water is drained, good ventilation.


Sounds like the unit has a low charge and is cutting out on a low press safety. This is more then likey not something you can fit yourself most of this units are not really serviceable with out cutting the lines open and adding a valve. If the unit i ... Air Conditioners

My Ruud Air Conditioner Model UAMB-048JAZ is not blowing cool air. The fan blows, but it doesn't blow cool air. It worked this morning, and now it doesn't. I found a red reset button and pushed it, but nothing seemed to change. Can you help me? Cheryl


3 things it could be:\015\012\015\012#1 problem with AC units - dirty coils, this leads to many other problems and is caused by neglecting to change filters monthly. You can buy coil cleaner commercially, but it is not the coils you see ... Ruud UAMB Air Conditioner

My air condition inside unit seems to be freezing up and the air stops blowing through the vents after I turn it off it sounds like ice melting. after a few hours I can turn it back on ,it will blow throuh the vents again there is a fan on yhe front of the inside unit it is making noise. is that a exhaust vent not the one that blows air through the vents. how can I fix this myself


When does it make the noise, when on AC or heat?? 2 things if the fan is on the ac unit itself that's not the one that blows air thorugh your vents, if its the one inside the furnace that is the one that blows air through your vents, but remember th ... Goodman CKL60AR60 Air Conditioner

I have a Jayco trailer with a Coleman 7300 Rooftop air conditioner. The unit is 13 years old and it doesn't put out the cold air it used to. I have cleaned the filter which improved the air flow however still not blowing cold air. Is it time to replace the air conditioner or is there something I can do to fix it.


Hi,from your problem its obvious that the problem is from the compressor.its bad and needs a replacement,however this requires the services of a technician and it will cost you a lot of money,however in the nearest future another problem may arise fr ... Coleman Air Conditioners

Our ager air conditioner seems to revert to timer all the time and starts to blow cool air but soon after it blows hot air and dosn't stop


To reset your prior time setting, remove battery from remote and re set it.Now you can operate as you like. ... Haier Energy Star ESA3183 Air Conditioner

Hi, two days ago I bought a Danby Premiere DPAC13009 portable AC unit. It worked on the first day reducing the temperature from 32C in the room to 26C in a few hours. Although now there is no cold air coming out of the AC and only the fan is working. I verified the two hoses and the exhaust is working good, lot of air is blowing out. Although, no air seem to be sucked in from the intake hose. I checked and I don't see any obstruction. Could the compressor be dead already??? thank you


Comperssors have a thermal overload. If there is a starting problem or low on freon the conpressor will shut down until cooled off. Try restarting and listen to compressor. ... Danby Air Conditioners

Air conditioner i have an electra classic 10 split unit. it seems to be blowing cool air one minute then switching to blowing hot air as if the heater suddenly turned on.


It sounds like the reversing valve coil is faulty or the relay or contactor that supplier power to the coils is faulty and needs replacing ... Air Conditioners

I have a danby 4 season home comfort unit model #DPAC7599 it doesnt seem to blow hot air only warm air and it blows very cold air out of the back of the unit.


... Danby Air Conditioners

I have a Fujitsu Plasma Inverter Split System Air-conditioner, but unfortunately do not know the model number. For some reason, after exactly 30 minutes the louver's which direct the airflow either up or down reset from the position I have set them in (via the remote control) and blow directly onto me. No matter what I do I can't get the louver's to stay 'set' in a single position which wont blow directly onto me. Changing the airflow from left to right has little to no effect, as most o


... Fujitsu Air Conditioners

Conia air conditioner reverse cycle - not blowing cold air; checked setting its correct.. it seems to blow cool air, but house is not cold. It was working fine last summer, not sure of problem.


If you feel cool air near blower, you have to service your unit completely. Because it's giving cool but not removing heat from room due to coil and air filter blocking. Helpful? ... Air Conditioners

Air Conditioner was working fine last summer but outside fna not working. Not hearing any sound at all. I can move the fan amanually and it seems fine. There is an electrical box next to the main electrical box on the back of the house with 2 fuses in it but I can't tell if they're bad. I thecked the thermostat and it apears to be fine. The air conditioner furnce kicks on and blows air out of the registers. It's just the main unit outside that's not working.


There is a relay in the outside unit. Check for 24 volts a/c at the two wires coming from the furnace. also there may be a mouse nest in the control comartment where the relay is and they tend to chew up wiring insulation and sometimes wires get disc ... Carrier 38CKC042 Air Conditioner

Air conditioner Artic King window air conditioner is blowing cool air but not cooling off the room. What is the problem. It worked last year and we can't seem to cool off the room....


You need to check the evaporator to see if it needs cleaning. You can check this by taking a dollar bill and see if it will hold it in place while running. Inadequate airflow will cause poor performance. Unfortunately ,this is something that would re ... Kenmore 72059 Air Conditioner

Delonghi pinguino PAC 250 U air conditiooner blows hot air. reset button must be constantly pressed in order to get normal cooling. also timer does not seem to be working


... DeLonghi PAC85 Portable Air Conditioner

I have a fujitsu reverse cycle air conditioner,it wasnt working(not blowing cold air only room temp air like a fan).air con tech came over,re-gassed it,tried air con that day,worked fine.didnt need to use it for a few months,re-tried it,no cool air again,i am thinking of a leak.My question is the air con is about 10 years old,if cause of problem is a leak,is it worthwhile fixing it(i would need to pay someone parts and labour,could not do this job myself),or to just bite the bullet and get a rep


Hi,\015\012\015\012The A.C is 10 years old which is a ideal shelf life for the A.C. If there are any leaks I would never ever try repairing it at home becuase if there is a leak then that means that the entire GAS which helps in the cooli ... Air Conditioners

Our air conditioner does not seem to be blowing any cool air...it basically just seems to be acting like a regular fan


The compressor is probably not runnng.\015\012The Main reasons that this will happen\015\0121 - A bad run capacitor (silver or metal capacitor)\015\012It’s either shorted, grounded or open.\015\012If it’s shorted a ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1534 seconds