Having problems with your Air Conditioners ?

Amana #PTC153b50AJ ser 0410686783 Customer heard a pop in unit and it went off. Breaker was tripped. Reset breaker and unit runs in a/c mode but does not heat in heat mode. This is not a heat pump but electric heat strips. Unit says there is a manual reset for the heat but we have not located the reset. We turned power off to the unit to reset fault etc and still no heat. The flashing light just blinks once every 4-5 sec. Could use some help in diagnosis Thanks DK


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Amana #PTC153b50AJ ser 0410686783 Customer heard a pop in unit and it went off. Breaker was tripped. Reset breaker and unit runs in a/c mode but does not heat in heat mode. This is not a heat pump but electric heat strips. Unit says there is a manual reset for the heat but we have not located the reset. We turned power off to the unit to reset fault etc and still no heat. The flashing light just blinks once every 4-5 sec. Could use some help in diagnosis Thanks DK


... Amana PTC153B50AJ Electric Heat Air Conditioner

10yr Vulcan Central Heating unit. Had tech come out and said main fan unit was faulty. I replaced myself and still not working. I discovered the O/Temp manual switch had cut off power. When I reset the switch the unit comes on and all works except for my fan which then the unit heats up and cuts off.


I have the same problem, heating unit will not ignite, it trips out, i go into the roof cavity and remove the top of the unit (4 screws) and there is a motherboard, it has a Green light flashing what tells you the type of fault it has, mine has 3 Fla ... Air Conditioners

Have a problem with my Intertherm air conditioner not coming on so I put a new thermostat on it. Nothing comes on fan nor heat nor air. I reset the breaker but still nothing and the unit model is a E1eb015ha? Anyone know if there is a reset button on the unit or where I can start looking to see if there is a problem.


Turn the thermostat off and check for 24vac between R and C on the thermostat. If there is no C then to G or W. If you don't have 24vac go the transformer and check for 24vac on the secondary. If it isn't there then check for 120vac on the transforme ... Intertherm P3RA-048K Air Conditioner

My fridgedaire window unit A/C and heat won't come on. I had replaced an outside light fixture a couple of weeks ago and had turned off the circuit breaker that affected this unit too. Now the unit won't come on AT ALL. I've unplugged the unit, then flipped breaker off then on again. Then plugged back in and hit "Reset" Button on the plug, then waited at least 3 min. as instructed, but still no power. The light on the plug doesn't even come on when I hit the test button. Could it be a faulty cor


Plug a light into the outlet used for the A/C, if the light does not come on when reset then the circuit breaker that provided the power to the outlet need to be reset or replaced. ... Frigidaire FAS257S2A WallWindow Air Conditioner

Hello I have Sharp Air con/Heating AY-XPM9FR with a floor/wall unit and a higher wall unit that are supposed to work in conjunction with each other. I have never had any problems until we had a power cut and now the timer light on both units are flashing and I can't get the units to come on and heat (it's cold!!) I have the manual and have tried to reset the timers using the remote control but still no good.


Hi Helen, i want to know the age of your Sharp Air con/Heating system. If its more than 1 year and you using it regular basic , then i suggest you change the battery or the remote control first then try . If the same thing happens then follow the ins ... Air Conditioners

I have a GE Split-Type room air conditioner model number AA1AH24EWI.I used it last summer but now it wont turn on.Have changed the remotes batteries and checked if it is sending signal(looking through digi camera to see if its sending) and still nothing works.Have turned it on at fuse box etc still nothing.is there a reset switch on the unit itself


Check power is indoor. And also for long time no use cases, please remove batteries from remote and re fix it when it is on use. Keeping with old batteries for long time with no use will affect the remote. Please check with other remote. It doesn't m ... GE Air Conditioners

Got a pyrox comfort control ducted gas heating system cant heat house above 19 dec have to keep hitting reset button every 10 mins, have cleaned the filter still doing the same, have heard the comfort control model have lots of problems. Unit is roughly 6 years old.


On the reset switch there should be a temp. cut out take a temp. reading and see if it is realy getting as hot as the switch is rated for maybe the switch is bad ... Air Conditioners

Hi Guys, I work on a mine site and the temperature on my Mitsubishi model MSZ - 25GEVA split air con has been set and I cannot change it via the remote control. In any mode i.e. cool/ heat if you push the temperature buttons nothing happens. The remote works fine ON/ Off/ Fan etc but they've locked the temperature so it can't be changed. Even if I push the reset button the temperature still remains pre set. I'm of the thought that I might need to remove the batteries and hold done specific bu


... Mitsubishi MSZ09UN Air Conditioner

Th 132 af floor heating controller not working. the unit is nearly 3 years old and until now ihave had no problems with it. i put the controller to holiday mode in the spring and recently noticed there is no display on the unit.the supply has not tripped, i have removed the display from the backplate whitch it connects to hoping it might reset and come back on but no joy the display is still blank! any ideas


... Honeywell Air Conditioners

I have a Kriesler heat pump and the remote control has stopped working and therefore i cannot operate the unit. I have changed the batteries and pressed the reset button on the remote but the screen on the remote is still blank


... Honeywell ER150B Air Conditioner

I have a dometic roof mount ac unit with the single zone digital thermostat . It now shows error code E1 on the display. Reset the breakers, checked all connections , Etc and still displays same error. Error code is lost connection between thermostat and control box. Checked control box and all connections seem fine and NO burnt smell. Any ideas?


It could have the sensor wire not plugged all the way or maybe a broke sensor wire from console to condenser control ... Air Conditioners

I have a 10 SEER heat pump about 16 years old, yesterday I notice that the outside unit was making a loud click noise in the heating mode. It's very close to the defrost electrical curcuit board. The unit still was putting out heat inside but decided to turn off the unit and use the emerg. heating. What could that loud clicking sound be? concern, Gilbert


Depending on make and model sounds like a check valve clicking. It can sound like it is coming from that area. You say your unit is 16 years old. Honeywell did servey on unit 10 years and older and found out they loose 25% effeicency after 10 years. ... Air Conditioners

Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you ... Amana PTH123B25AJ Heat Pump Air Conditioner

I replaced my outside unit with a 3 ton goodman heat pump unit. My old unit was a 3 ton bryant and the compressor burned up in it. I left the old unit under the house since it seemed to be in good condition. the pump worked fine on ac to start off. But then you had to switch it in heat and back to ac for it to work. So the tech replaced the expansion value and put filters in both lines. I still have to switch it back to heat to get the ac to work. The tech told me that i would have to repla


You said it had rwo filers on the line. I know one is a liquid line drier. If you have one on the suction line it need to come out ASAP. The trash in the line can be removed by running in cool.pump down unit replace drier. While the unit is pumped ... Air Conditioners

3.5T/10yr.old ELEC. cooling was ok until I switched over to heat. Unit failed to activate compressor until I touched the reset. once started via reset the unit worked thru initial cycle but often fails to restart without reset. called service and they enfused R-22. issue not corrected, called serviced again and high pressure side exceeded 400 when 250 normal. service recommended replacing unit believing there was a stoppage in the fluid line. Subsequently I replaced the filter in the air handle


It sounds from what you just described, that your problem was the dirty filter to start with.\015\012Then the tech added charge to the system, which i'm sure that he now has it overcharged.\015\012Try removing some of the refrigerant unti ... Ruud UBHC Air Conditioner

I have a GE Zoneline 5500 PTAC that doesn't throw any heat. The electronic display appears normal during operation, I hear a clicking when the unit is turned on and the fan kicks on but it just blows cold air. The unit was set to the highest heat setting and the air filters were cleaned and unplugging and restarting but still no luck. I haven't tried using the override dip switch to bypass the heat pump, becuase there is a total of 3 of these units in our condo; one in each bedroom and one in th


Hi,\015\012Just for giggles and grins I would switch that one to coll and see if the compressor runs in cooling... that will tell you if it is the compressor or the reversing valve that is bad...It may also jog the reversing valve and get it to ... GE Air Conditioners

Hi, I have a samsung aqv18ja series split type air conditioner (cooling and heating) wall unit. the unit was install in 02/12/2009. By "one hour heating and air conditioning". In this short time service the outside compressor has been replace, the system has check and recheck,for cooling leak. the inside unit fan motor has been change. but the problem still exists. The inside unit fan continues to run when the unit is "off" and with the remote off.


Simple, check in your remote. There is an option button "Blow". Just press it. Your unit gets completely off. Please write back if helpful? ... Samsung Air Conditioners

We have a Vulcan ducted heating unit model HX100, recently we have experienced problems with the unit where is it not heating the house, the unit goes on but blowing cold air. We have had a couple of technicians to repair it and still not working. One fixed the switch pressure & the other the flame sensor connection. We have been advised that we may need a new unit or repair the board. As we have an illness in the family, we would like to know whether we need to purchase a new unit as p


\015\012We had the same problem with our carrier heater 4 year or so ago. We had a technician and electrician try to resolve the problem. What the tech suggest was to replace the main component ... Air Conditioners

I have a Tempstar model NFCP3600A1 (style # FCP3600A) ICP Heat Pump. Starting last week, the unit kept heating well over the set temperature. I swapped out the thermostat thinking it went bad, but it still continued heating and the "off" wouldn't work at the new thermostat either. Next, I checked for shorts in the thermostat wires and they seemed OK. I then replaced the TI 26FC-2 circuit board. Once the unit heated the house to the set temp, it continued running up to 75 degrees. "Off" and lowe


... Air Conditioners

I have a new Rheem heat pump. The cooling works fine but won't blow hot air in HEAT setting. I have reset the breakers for heat pump and air handler, changed filters and pulled batteries and reset the Braeburn 3000 thermostat. Still blows cold.... Any other suggestions?


If this is indeed a heat pump you rthermostat should also have a emergency heat setting does it work on that setting... a heat pump on heat wuns the outside unit and has a recersing valve that changes the refigerant flow ..is the outside runnigndurin ... Air Conditioners

Our bonaire evaporative unit will not switch on. l rang customer service and they advised l reset the unit as we recently changed the batteries l did the reset but the unit still does not work and after doing this we have now also lost the cool fresh air from the panel can u help.


Try reset the controller. turn off power to the unit then remove batteries from controler. press the power button on the controller to remove residual power. turn on the unit then install batteries. turn on controller within 4 minutes of turning on u ... Mastercool 67471 Evaporative Cooler Air Conditioner

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

Hi - our Siemens RDJ10RF remote thermostat controller fell off the shelf and went off as the batteries came loose. We put the batteries right and reset the thermostat remote, but the heating will not come on. Do we need to reset the boiler and how do we do it? The water still heats up, it is just the heating that doesnt respond to the thermostat anymore.


... Air Conditioners

One of our Fedders AEY12F7F through-wall AC/heater units has stopped heating (AC still works fine). Unit is about 4 years old. I know it has a separate heating coil (it's not a heat pump). Is there a fuse I should check first? (where?). If there isn't, or if that isn't the problem, do I assume the heater component needs replacement? If so, is this something that a skilled handyman could do? Is a manual available? If we need professional help, is someone recommended for the Portland,


Hi - there is a fuse inside the unit and if replacing it does not solve the problem, it could be a problem with the heating element itself. The heater looks like this: ... Fedders AEY12F7F Wall/Window Air Conditioner

My heat pump will not come on in HEAT or A/C. I thought I might have a simple defrost control board problem, but still no go after replacing the board and the defrost relay. I checked the pressure switch and it is not tripped. I've checked all the circuit breakers and they, too, are all set. I've checked the outside unit using the "test" switch inside on the start relay and the unit will come on, but won't stay running on it's own. When I select HEAT, I wait the necessary five minutes for the un


Hi; Need more info. How old is the equipment,look on the outside unit data plate it will give the built date usually in the top right corner. Also heat pumps can run with a faulty defrost board. I would check for control voltage at the secondary side ... Ruud UBHC Air Conditioner