Pace Air 24HPEW-HEC Unit will not heat, though heat mode comes on, dehumidify and cool mode work, and fan works as advertised. Fault Code E4 presents at startup. Manual is off site. What is this code telling me?


Answers :

If unit displays "e4"

1? Check whether the winding resistance and
operation current of the compressor are normal.
2?Check whether the high and low pressure is normal
when the unit is running.
3?Check (whether the coil pipe sensor is normal)
whether the contact of the inserter on the circuit
board is well, the coil pipe temperature sensor is
fixed, the evaporation of the indoor unit is well,
the key is to check the evaporator temperature
detected by the coil pipe temperature sensor has
reached the cooling or heating temperature.
4?Check whether the surface of the condenser is too
dirty, it should be cleaned when it is too dirty.
5?Check whether the capacitance of the outdoor motor
and the fan is damaged, it should be replaced when
it is damaged.
6?If the above items are normal, the electric control
board should be replaced.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Pace Air 24HPEW-HEC Unit will not heat, though heat mode comes on, dehumidify and cool mode work, and fan works as advertised. Fault Code E4 presents at startup. Manual is off site. What is this code telling me?


If unit displays "e4"1? Check whether the winding resistance andoperation current of the compressor are normal.2?Check whether the high and low pressure is normalwhen the unit is running.3?Check (whether the ... Pace 12ACXWHEC Split System Air Conditioner

GOODMAN CMA80905CXBA FURNACE. INDUCTION BLOWER NOT ENERGIZING. GETTING 3 "BLINKS" FROM DIAGNOSTIC LIGHT (LOW PRESSURE SWITCH OPEN). THE A/C WORKS & THE BLOWER FAN COMES ON WHEN THE STAT IS IN THE HEAT MODE WITH THE FAN SWITCH ON. WHILE THE FAN IS ON , THE DIAGNOSTIC LED STILL BLINKS A CODE OF 3. THIS IS NOT A CONDENSING FURNACE. I BYPASSED THE STAT (W & R)TWISTED TOGETHER---SAME RESULT---DIAG LED COMES ON STEADY, THEN FOUR CLICKS, AND BACK TO THE CODE OF 3 BLINKS. CIRCUIT BOARD???? OR 120VAC NOT


The pressure switch is closed before the draft motor closes it.the board is telling you that this is not right.pull the wire(either) off of the pressure switch to see if furnace tries to light.if it does,you should replace the pressure switch. ... Goodman Air Conditioners

My LG LAN125 mini split heat pump occasionally shuts down in cooling mode while displaying the code CA. The LG tech tells me there is no such code. When this happens, I have to cycle power off and back on to the unit. Simply turning it off with the remote does not work. Any ideas?


Wash out your outside coil and monitor the outside fan. sounds like a lockout due to dirty condenser or intermittent motor operation. Could mean condencer air problem. ... LG LS-L1210CL Mini Split Air Conditioner

Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you ... Amana PTH123B25AJ Heat Pump Air Conditioner

My hotpoint eg900x fan oven has a problem. the fan oven no longer heats up, fan is working but no heat. oven works in normal mode


... Air Conditioners

My outdoor heat will not operate. It is a Carrier 38YRA042330, with a Carrier Thermidistat thermostat and a Carrier Air Handler 40FFKB005300. I have an H5 error code on the thermostat will I put it in Heat mode and raise the setting to call for heating. I changed the air filter on the air handler when I realized the heat pump was not operating. The air filter was pretty dirty. The system will operate in aux/emerg heat mode, with the fan in Auto or On mode, and will maintain the thermostat


You need to go oside and look for a red reset button on the unit. you tripped the high ressure switch when you let your filter get that dirty. go check on this and when your done if it still is not working then ask me more. ... Carrier Air Conditioners

The heat pump and fan stoped working the thermastat red light is flashing a code 2 blower fan and emergency heat working in the house.


Hi,Here is a tip about troubleshooting your air conditioner...\012There are many things that can cause your air conditioner not to cool... ... Air Conditioners

GE Zoneline HP PTAC A3B688DAALW1 WIRING DIAGRAM? Found a 6" L white wire with 1/4"F stake-ons loose from center terminal of Compressor capacitor 20/5uf going into the back wiring compartment. Not sure where it came loose from. There is a black multi stake-on terminal block up inside behind the capacitors. Attached it there to a unused spade but now fan does not run the indoor fan when in heat mode (compressor or elect. heat). Before the fan and electric heat worked but compressor just buzzed try


... GE Zoneline AZ55H07D Air Conditioner

Intermittent heat I have a Carrier (Payne) unit (FA4ANF030) with intermittent heat output. The air works as does the fan when in heat mode, but usually no heat. Sometimes it will suddenly begin to put out heat normally and will function fine...until it doesn't. The thermostat was old, so I replaced it first. Seems to make no difference at all since it works exactly as before.


Check wiring of heater, it may have loosed connection or corroded connection. ... Air Conditioners

Ruud 300 thermostat in heat pump mode and I don't have the manual to get it out of that mode. It was working fine then switched to this mode. No more cold air. I live in Florida so I don't have a heat pump installed. I remember I had to switch to Electric mode but its a buncha codes. How do I switch it? Thanks


Hi,\015\012Here is the complete manual for your thermostat...\015\012\015\012Click here\015\012\015\012 ... Air Conditioners

I have a AZ38H15DADM1 that works fine in heat mode and in AC mode it works great until it reaches the temp it thinks it should be, then it cuts off and never cuts back on without me physically turning the knob to the fan for a minute or so and then switching it back to AC. Any suggestions??


... GE Zoneline AZ38H12DAD Split System Air Conditioner

Fujitsu inverter ASTA24LCC aircon wont work on heat mode. Two flashes of red and green lights, followed by five flashes of red light and sequence continues with a pause between. Other modes, fan, cool etc work.


Check that the gas is not leaking, that would be the most likely cause. ... Fujitsu Air Conditioners

Cycleing, ok it sound like the heater fan kicks on then off , on then off, on then off, just like that . it will do this on heat cold or in off post. the ac and heat seam to work but i dont get the on off cycleing ! its not the ac blower but like a fent fan for the heater ! had a ac tech tell me it may be my main bord! carrier modle # 58RA (VJU one of these is next not sure witch)050 board # HK42FZ009 S/N 3197A13382


You are referring to the inducer motor that is kicking on and off. It is probably a limit switch that might be triggering it to go off and on over and over. It could possibly be the board but I highly doubt it since the ac works just fine. It can ... Carrier Air Conditioners

Hi there I have an lg reverse cycle aircon model LWC122RH-2 and the heating seems to work fine on it at however when I try and put the cool mode on it desn't seem to get very cold and the cool light does not come on also the defrost light doesn't come on but the heat light and the fan light and timer lights all work and come on ...please help


... LG Heat cool Window Air Conditioner

Its a trane unit model# TUE060A936K3 in cooling mode condensor comes on the indoor fan does not in heating mode every thing comes on but the blower fan does not there is not a led light blinking code lable on the unit i it looks like its giving 4 blinks pause and repeat 4 blinks etc. what does this mean


Hi,\012Either the vent is blocked or the pressure switch that tells it that the purge blower is running is not working right...for some reason that switch is not making contact and so it will not let it light..\012\012heatman101 ... Air Conditioners

I have a Rheem heat pump/air handler; it draws 2.9amps with only the fan running, 13amps when the heat pump is running and 38amps with the heat strips on. My question is why the unit draws that many amps when in heat pump mode? Isn't all of the work being done by the compressor outside?


You gave us some good clues, and figures to work with-- THANKS!!To answer your question: Your unit switches the one compressor, from cooling, to heating, by reversing some valves-- Same compressor-- just routing the refrigerant i ... Air Conditioners

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


... Air Conditioners

I have 2.5TON heat pump that works fine in ac mode but does not heat only have heat in emergency .condenser fan does come on when heat is selected


The heat pump is either wired wrong on the low voltage side or the reversing valve is sticking. these need checked by a tech. if you are showing emergency heat then your thermostat is meant for a heat pump and that is also a good place for the tech ... Air Conditioners

Nordyne AC Hello, Our Nordyne DT5QD-042K quit cooling the air. It sounded like the compressor was starting and heat was building up however the fan on top was not turning. It did spin freely and showed no sign of bogging down. Power was present at both leads from the capacitor. Ohmed lead to lead and had resistance, nothing going to grnd from either lead. Last September I had to install a booster capacitor and all worked OK (the fan was operating at that time). I am suspecting the fan mot


... Air Conditioners

My Ruud heat pump fan stops after running a minute. It is 10 degrees out now and defrost mode seems to work fine. It makes a humming sound when the fan gets stuck. Sometimes if I take a ruler to it, it will unstick and starts spinning but not other times. cover over the fan motor feels very warm, almost hot to the hand. I've shut it off totally for now.


Hi,The capacitor for the fan motor is bad...replace the capacitor and you'll be good to go...\012Here is a tip about troubleshooting your air conditioner...\012There are many things t ... Ruud UBHC Air Conditioner

I own a SH09BWHA air conditioner, and it stopped heating, this is the second time it happens, last time the tehnician just reset the codes, I got the codes now but I don't know how to enter them. Can you tell me the steps to put my remote control intro code resetting mode?


... Samsung Air Conditioners

Will not switch to cool mode. heat and fan work fine


I work as a maintenance directo at comunity with 96 ptac units and this is a very comun problem. normally it is do to the capasitor getting bad or the overload switch just saing may help. ... Air Conditioners

My Panasonic heat pump HE9LKE (flagship model), stopped working last weekend, and after 'check' gave off an H97 error code. "Check the outside fan". It was freezing outside, and both front and backside of the box were frozen, but not totally covered in ice. Ice has been removed, but to no success. Any ideas to get the heat pump started again?


H97- Outdoor fan lock abnormality. Check fan motor rotate freely. If hard replace bearings or motor. If rotate freely, out door PCB faulty. Replace it.Helpful? ... Air Conditioners

I have a DeLonghi CF210 and I'm getting the "E3 Fault" code on the main screen. It will not power up in Air Conditioning mode, but the fan mode will run. I saw where someone suggested it is a voltage problem, and have tried it in several outlets to no avail. This problem happened to me about a week ago and I turned it off for a while (10-20 minutes), then turned it back on and it worked again for a week before giving me the E3 Fault error today. I do not have the financial resources to sen


Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power ... DeLonghi CF210 Portable Air Conditioner

My indoor unit on my heat pump will not shut off. The electric heat keeps running, and the fan keeps running. It only happens when it is really cold, like 25deg or below, above that and it functions fine. The outdoor unit shuts off, but the indoor stays running. I do HVAC work, but I have never seen a problem like this. I have switched the stat out, and its just so strange. I figured the relay may be stuck, but if I turn the stat off, it turns off shortly after which tells me it may not be the c


I would venture to say your stack relay is getting stuck. either that or you have a short in your low voltage wiring somewhere that is not always making contact....or it may be making contact through another median...like ice or frost. Remember ele ... Intertherm P3RA-036K Air Conditioner