Having problems with your Air Conditioners ?

I have 4 header split type air conditioner. Time & again it stops and operation and timer light flash altenately and I have to to turn off the power at the switchboard and turn on again to reset. Sometimes this happens 2 or 3 times a day and other times it operates correctly for days. I have cleaned the filters and checked the electrical connections. 2 years ago I had a tech from Fujitsu who came and checked everything and could not find any faults. I am getting a bit concerned as this is occur


Answers :

Hi,
\015\012On the days it happens alot is there a temperature corolation??? Are these days warmer or colder then the days it runs all of the time???
\015\012
\015\012Have you checked the charge on the unit???
\015\012Would there be any power surges or fluctuations???
\015\012
\015\012It would seem also that this may be caused by a faulty sensor... but you will have many sensors between the five pieces of equipment that it could be and it may take it failing completely for you to be able to pin down exactly which it is...
\015\012
\015\012You may be able to narrow it down by shutting off one head at a time and seeing if it still locks out... but that would take many days to make sure that you have found the fault...
\015\012
\015\012Unfortunately there are probably no good answers to be had any time soon here and not without a ton of detective work...
\015\012
\015\012heatman101

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have 4 header split type air conditioner. Time & again it stops and operation and timer light flash altenately and I have to to turn off the power at the switchboard and turn on again to reset. Sometimes this happens 2 or 3 times a day and other times it operates correctly for days. I have cleaned the filters and checked the electrical connections. 2 years ago I had a tech from Fujitsu who came and checked everything and could not find any faults. I am getting a bit concerned as this is occur


Hi,\015\012On the days it happens alot is there a temperature corolation??? Are these days warmer or colder then the days it runs all of the time???\015\012\015\012Have you checked the charge on the unit???\015\012Would there ... Fujitsu Air Conditioners

Intertherm Electric Furnace in mobile home Model# MRAC 2317 SN - 79JE0501 Question: The blower stays running all the time. I have to turn the main breaker off to turn the blower off. The unit is heating when it is running. I have replaced the thermostat about 3 years ago in the summer when I had a AC problem. Would the fan switch on the furnace possibly be the problem? It has an auto & on position on the switch. It clicks when you switch to the on position but does not click when you put i


... Intertherm Air Conditioners

We have a goodman ac/ heat pump it started about 4 months ago and got a musty odor. Service tech came bleached it was for a short period we added a room everything was fine for a short period of time. Have not had the system for a month or so because of the pleasant weather have heat on but no ac turn it on last night and odor was terrible duct has been checked. Orginial system in the rest of my house is fine. We need some advice Thanks Danny England


Dirty sock syndrome. It's caused by high humidity in the duct system and/or home. This could be the result of an oversized system and/or improperly sized ductwork. I would advise getting technician certified by NATE in AIR DISTRIBUTION to come and ... Goodman CLQ36AR49 Air Conditioner

My goodman heat pump has frozen up 3-4 times already this summer. It is a dual system 10 seer (i believe are the terms). Every time someone comes out they can't figure it out because the system is running fine by the time that they come. Two years ago the blower or activator was replaced (maybe the replacement part isn't so good?) The unit is 9 years old. Last year a guy charged it and about a month ago when it was checked the freon was only a little low. I'm SO tired of this issue. Any ideas


After system has been running 10-15 minutes, the discharge air temp should be 18-22 degrees colder than the air being sucked in. If the air is more than 22 degrees colder then the problem is with air flow. Check filters, blower speed, make sure all ... Air Conditioners

I have a lin-stat thermostat. Electric baseboard heaters. There are only a set button and up and down arrows. Turned the breakers off in the spring. Turned them on today and the thermostats will not turn on. Screen is blank. Tried holding set button down, no luck. Neither did pushing the up/down arrows Need help to turn them on. Thank you. Bought house 4 years ago and no issues last year. Also no instruction booklets.


... Air Conditioners

I just had my AC unit checked as part of a duct cleaning package. The final step was the technician checking the freon levels at my outside unit. He attached gauges and told me that my unit is 2lbs low. (The unit is just about two years old). He then hooked up a can of R22, opened the can reaevoir, turned it upside down, opened the handle to the gauges and turned them back and forth for literally about a 5 second time frame. Does this sound like my unit received a two pound fill of freon? Or did


If he only added R-22 for 5 seconds, then no, it did not take 2 lbs. Even if this was possible, the R-22 being upside down, (meaning it was charged in a liquid state), it would flood the compressor and more than likely cause damage. Now, it does not ... Air Conditioners

A/C worked fine last year. Turned it on for the first time this year and the outside unit does not come on. The inside unit fan works just fine. I checked the circut breaker and turned on and off. No change. I revoved the cover and do not see any burnt wires or any problem. Not sure what to do next. I have a meter... what should the voltage be where the power comes into the unit at L1 ect. please help... thx


Check and see if you have 24volts at the contactor outside.if you do you have a bad contactor. if you don't take the tstat off the wall and take a jumper wire and jump out R to Y on the t-stat if i ... Air Conditioners

AMCOR 24,000 BTU split system. Worked fine two years, then today it had no power. Checked circuit breaker, it had popped. Reset CB and went to inside unit - would not turn on or off with remote or hard button. Checked wiring with an electrical tester, and wires to outside unit hot, as well as inside unit. No flashing codes, nothing. Unit won't turn on,even with power. Is there a fuse somewhere in the inner unit or outer unit?


I had this same problem. I disconnected the thermostat wire out side at the condenser and reconnected it and it started working. A couple days later it blew the breaker again this time I found the bus where the L1, L2. GR wire connect at the condense ... AmcorAire UCHW-H24AF2 Split System Air Conditioner

Model G51MP-48C-110-6; I've downloaded a manual and troubleshooting is usually fun for me, but ;( this time. It ran fine last year, not this fall. Have alternating Green & Red code lights (FAST); I have checked thermostat; (and completely shut off, restarted power and gas several times too; each time goes back to "normal' simultaneous, slow flash until I turn the thermostat up to call for heat; then FAST, alt. Flash again), good ~25vac signal calling for heat. Have drained condensate from trap (


Apply power to the inducer motor, or check the voltage to it first.a relay or circuit board will control its operation, if the inducers not running, the pressure switch wont close and no operation . ... Air Conditioners

I have a 18000btu LG mini split heat pump installed about 1 year ago in vacation home. In heat mode the unit cycles on and off when room temp is within 2-3 degrees of set point. Cycle on time varies between 35 to 60 seconds (sometimes more). The off time is 2-3 minutes. During this time, I check inside temp with accurate digital themometer mounted at the air intake of the unit and the temp does not change, assume because unit does not run long enough. When I put temp set point more than 3 d


Hello.I think they are on to something with shortcycling on temp sensor.I think it should be sampling the return air instead of (inside coils ?).A 2*f dead band use to be built in (factory installed) to thermostats to prevent on/off, but ... LG LS-L1210CL Mini Split Air Conditioner

AC for my RV won't even turn on, fan, nothing. I have had a few problems this year with it blowing the breaker on my home, but the last time I ran it from my home a month or so ago, it worked fine. Today when I went to turn it on, the fan won't even run let alone the AC. I would agree that the filters need to be cleaned, but not to even turn on, even for 2 seconds? What would you think it is and how would I find out?


You are saying it causes the breaker to trip?( or was past tense?) sounds like there is a short somewhere. that's why nothing comes on ... Coleman Mach III Air Conditioner

Problem I turned on my air conditioner this spring. I turned the switch to cool on and the air conditioner fan not going. I took cover off and got new capacitator didn't work. I took fan motor into electric shop and checked out fine. When I turn switch on the contact switch engages and there is a humming noise. But the fan does not work. the compressor doesn't start up. The model is at least 10 years old. How do we tell what the SER rating is?


Hi,\015\012There are two things to check....\015\012\015\012Do you have power coming into the contactor???\015\012\015\012Do you have power coming out of the contactor???\015\012\015\012If you have power goin ... Air Conditioners

Ruud Silhouette II furnace: comes on and runs for as long as it wants, then turns off. Sometimes turns off at pre-set temp, other times just when it wants. May turn on again, behave well for several cycles, or for 20 minutes. When I get too cold, I go out, downstairs, and thump it near the fan. Starts right up, runs for as long as it chooses. Nearly least energy-efficient kind, v. frustrating. Had trouble-shooter out a few years ago, couldn't find anything. An intermittent short?


Hi ruby. Begin by installing a new thermostat. Preferably one that allows you to program weekday and weekend temps. separately. Joe ... Ruud UBHC Air Conditioner

I have a goodman gsc13 ac unit about 4 year old. When the temp gets around 90 or above outside the fan on the unit starts but the compressor does not. I had service check it out but that day they were here it was in the 80's and it worked fine. I replace the thermostat to make sure that wasn't the problem. Interesting if I turn the unit off at the thermostat and wait 15 minutes and turn it back on it will run fine. But the next time it tries to turn on automaitcally it will just be the fan o


The hum you hear is the 24v transformer which is powered form the air handler inside have you tried a hard start kit or had cap checked ... Air Conditioners

My fan and heater work fine, but today I turned on my air conditioner for the first time this year. It did not feel like it was getting cooler so I went outside and noticed that my outside unit was not working. I went and checked the breaker and noticed it was tripped, so I turned it off and turned it back on (the breaker). Then all orf the power went off to my house. I then reset my whole breaker box and I heard what sounded like my outside unit explode. I ren over to it and it sounded lik


You had a refrigerant release. Probably two lines rubbing together in the outside unit. I have repaired several of these with this problem. It involves repairing the lines by silver solderingthen pulling a vacuum/ purging with nitrogen an ... Carrier 36KCARMS Air Conditioner

I have a newer Bryant 340aav furnace that came w/a new house I had built not even 3 years ago. The house was completed at the end of November & come the next spring it was discovered the installation crew never put freon into the a/c. Fast forward to 2 years after that (March of 2012) I went to turn on my a/c to discover it was just blowing lukewarm air. Had the crew come out again & put in almost 2 lbs of freon. The technician insisted he checked for leaks & found none so I paid him his service


... Air Conditioners

I have a Ruud 2.5 ton 14 sheer air conditioning installed 1 year ago. In January after 3 weeks without turning on my A/C stop working. from this time I try to call the guy who installed but hi not answered my calls. For all this winter months I can lived without a/c, but now in Florida start to be hot again and I need my A/c. Please help me what I should do. I have warranty which alredy expired 2 days ago. Who I should call to report this awful company which sold me this A/c. I bought with warra


Hello Barbara my name is Heath it will be my pleasure to assist you. The first thing you should check is the breaker to the unit in the panel box there should be a 30 or 40 amp breaker for the outside unit check that to be sure it is not tripped. Als ... Ruud Air Conditioners

Model feh-012hr-03 mobil home electric furnace. The unit will shut off according to the thermostat, but will not cut back on . I have to click the breaker off and on several times to cut unit back on.After two years of dealing with this situation, now the unit will not turn on..I can turn the blower on manually.


This is a faulty thermostat or loose connection on a wire...so check them out! If that is not the case then it sounds like it could be a faulty sequencer!\015\012Goodluck and hope this helps ... Air Conditioners

I have a Bryant split system AC that is 18 years old. We have been away all summer (2 1/2 months), during which time the thermostat was set to 80°F. We live in SE Virginia and summer temps are 80's or 90's. We arrived home less than a week ago and turned the thermostat down to 72°F (at all times - we have small children and I am pregnant, so we need the house to be cool 24/7). The system was working fine until this afternoon, when I noticed the house was warming up. The temp had reached 76°


I am a service manager of a richmond va hvac firm and we tell are employess that if a unit is over 15 yrs old and needs over 500 dollors worth of repair to recomennd replacement the reason the leak repair is so much is because the unit has to have al ... Bryant 463AAC008BA Air Conditioner

Hello, I have a Amana Air Command 80 model #GHI90A50, 22 years old. This furnace is on its third ingnition module (last one two yeras ago). The symptom I am trying to diagnose has been ongioing since this latest ignition module was installed. The furnace is short cycling, meaning it runs often once every 8minutes but for less than 3 minutes at a time. The sequence is as follows: Cycle start (small blower turns on), followed by the ignition module illuminating (yellow) for 3 seconds then turns g


If your furnace lights and the gas stays on for 8 to 10 seconds, then shuts \012right back off, then you need to clean your flame sensor with light sand paper \012or steel wool. You might need a new flame sensor, but most of the time th ... Air Conditioners

Central air just stopped running, was running all day. I turned down the thermostat about an hour ago and I heard it come on. I noticed it wasn't running just a little while ago. Looked an the thermostat says it is 78 while the aircon is set for 72. It wont come back on I tried resting the thermostat and checking the breakers. I even switched the furnace off on the side. The furnace is about 30 years old...


Possible you have a bad contactor switch.. Have a tech look at this since it is dangerous due to high voltage and age of unit\015\012\015\012Good Luck\015\012\015\012Dave ... Air Conditioners

I have an electric furnace and heat pump that will at times blow only cold air during the heating season. I have checked the filter and don't believe that to be a problem. I usually have the temperature set to 74 degrees. When the outdoor temp. is extremely cold the axillary heat indicator will be on and still no heat. I can turn the heat pump off by switching to emergency heat and will get some heat from that but not as warm as I think it should be and even that will at times only blow cool


You are losing operation to your heat strips.\015\012\015\012In heat pumps, there is a secondary heat source. Usually electric heat strips. (Sometimes a gas furnace, this is known as a "dual fuel" system)\015\012\015\012The he ... Carrier Air Conditioners

I don't know what model my fan is, but it's only 3 years old and suddenly two days ago the light and fan quit working. We replaced the light switch on the wall-nothing. Took apart whatwe could of the fan to look at the wiring-all intact. We then replaced the battery in the remote and it instantly worked fine again. After putting it all back together it stayed lit with the fan working for about two hours at which time I turned it off using the wall switch. I immediately tried turning it back on a


That may be, because you were using the Remote Control to operate it, but then turned off the wall switch instead of turning it off using the Remote Control.Turn the wall switch back On and try to get the Remote Control to take back over ... Hampton Bay Air Conditioners

Turned it on for the first time this year. After a few minutes it would stop working but all the light indicators are still on. I made sure that the energy saver is off, that is is getting the full 220 volts, and presst the test and reset buttons on the plug. No results. Unplugged it for a few minutes and tried again. Same deal -- would start and then stop working after a few minutes but also noticed a burned electrical smell. Could it be the capacitor or something?


Yes, it could very well be a burned capacitor or a burned wire from over heating, Best advice is to unplug the unit and do not attempt to use it, until it is repaired.To find an authorized service in your area, click on the link below. ... Friedrich Compact Programmable CP24N30 Air Conditioner

Hello, I have a weather king 13pja, its about 4 years old. I have checked everything. the coils are cool, the unit receives the signal to turn on, you can here the click but nothing. Electricity is going to it. the outdoor unit will not run. any suggestions.


... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific