Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Answers :

Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.
\015\012
\015\012Thanks Nicolle

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan


The LG>LW5200ER AC is not listed as a heat providing unit. Click on link and this will give you the spec's\015\012\015\012 \015\012\015\012 ... LG LW5200ER Air Conditioner

We just installed a Samsung AQ12ABMCF heat pump/ air conditioner. Cooler setting works fine but when switched to heat mode nothing happens (outside unit runs, but inside unit does nothing). Anyone had this problem, or is there something that we are missing? Thank you!


I am having the same problem with my unit. it was working for a few years but this season it stopped ... Air Conditioners

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


... Air Conditioners

Hi i recently purchased a used convair portable supacool 9 air conditioner the first time i switched it on it appeared to work ok but the next time i turned it on it is working on normal fan mode but when i turn it to air conditioner mode it is doing exactly the same as on normal fan mode the compressor does not appear to be working and is not making the extra noise that it was the first time i have tryed all the switchs including the thermostat but there is only a very simple to use set up any


... Convair Portable Air Conditioner

The air conditioner has a flashing red light on the thermostat. The heat is not working. The fan will turn on if switched to ON, but will not engage if just on AUTO. Even when the air is blowing, there is no hot air. It is about fifty degrees in the house right now. - I checked the breakers, and put everything through a power cycle, nothing is having an effect.


... Hunter 30124 Air Conditioner

I just had a new compressor installed in my heat pump. My heat pump compressor turns off (I can hear it) in air conditioner mode when the outside temperature is greater than 95F. The temperature inside the house rises quickly in the afternoons during these conditions. It works great when outside temperature is < than 95F. Is there a problem?


It sounds as if it is tripping on high pressure. This can be directly related to outdoor temp. Most residential a/c units will run a maximum capacity over 95 degrees. The compressor should not be shutting down though.The best thing you ca ... Air Conditioners

Bryant air conditioner - outside unit will not run - before it quit running, air temperature in house rose from 65 degrees to 75 degrees. Inside fan continued to blow - air smelled like a car air conditioner that ran out of Freon. Bought Freon - need to know where to add it. The heat pump model # BF-163S bi directional but also coming from unit is another line that runs same direction with same type of valves. Air conditioner model # 697CN030 - B


... Air Conditioners

Ruud 300 thermostat in heat pump mode and I don't have the manual to get it out of that mode. It was working fine then switched to this mode. No more cold air. I live in Florida so I don't have a heat pump installed. I remember I had to switch to Electric mode but its a buncha codes. How do I switch it? Thanks


Hi,\015\012Here is the complete manual for your thermostat...\015\012\015\012Click here\015\012\015\012 ... Air Conditioners

I just had a new a/c - heat pump installed on my 5th wheel. The a/c works well but when I turn on the heat pump it seems to blow air about the same temperature as inside the coach. I seem to hear the compressor turn on, outside temp is around 55 degrees. I had a rv service company come out (was about 75 degrees then) and they said it has no problem and that the heat pumps don't really work that well. I can tell you that I left it on for close to an hour later that night when it cooled down and n


Hi; I hope You called a company that will honor any warranty on the heatpump. Sounds to Me like I would contact the original installer for more help or free replacement.Also at 55 or 75 degrees outside The heatpump should be providing toasty air. Onl ... Dometic Rooftop RV Air Conditioner

I have an NewAir 12000H Portable Air conditioner with a heat pump. The problem is that the heat pump no longer seams to be working. The desired temperature is 79 degrees. the unit never gets above 75 degree. when it actually gets that high it because my heat from the house has turned on. once the heat goes off then the unit goes down to 72 degrees and stays there until my heat comes back on. whats wrong with the unit? is there anything that i can do?


It sounds like the actual control module, the "brain", of this heater / air conditioner has failed and can't sense when to kick on the heat any longer. Have you tried just unplugging the unit for a good 5 minutes minimum and seeing if it will help " ... NewAir Air Conditioners

I have two Amcor AmcorAire UCHW-H09AF2 Split System Air Conditioner units -- 2 years old. One works fine, but the other does not blow heated air (Heat Mode). It is cold outside, but the good unit is blowing heated air at the same time the bad one does not. All other settings are the same. All suggested service numbers, as well as the company number in user guide are disconnected. Thanks


... Amcor Aire UCHW-H09AF2 Split System Air Conditioner

My air conditioner delivers cold air only in spurts. It then goes into fan mode for a few minutes, then to cold air in a few more minutes. It is over 100 degrees outside and the inside of the house is 85 or so. I have the temperature set at 74 degrees. Why does the cold air not pump out consistantly?


Hi,The\012 unit is probably low on freon and so it is running too cold....this \012trips the freeze stat and shuts down the compressor till it warms up The unit will \012need to be recharged or replaced...\012Here is a t ... Fedders AED24E7F Wall/Window Air Conditioner

Great site. I have a Simplicity SPAC 8499-5 Portable Air Conditioner and it was working fine up until yesterday (~2 years old). The unit is running and the fan operational but while the green light for Cool/Dry is illuminated that actually cooling unit for the air conditioner is not kicking in. The system is just blowing air (like in Fan) mode. I have checked the water reservoir and it is empty and placed properly in the unit so the switch is engaged but no AC.


... Air Conditioners

Is it ok to replace outside unit of central air and heat and not the inside air handler ? The upstairs A/C( over 10 yrs old) is not keeping up with South Texas heat. The temp upstairs climbs to 84-86 degrees by the afternoon and takes 4 or more hours after dark to cool back down. I have cleaned the entire unit outside- no help. I have replaced the downstairs unit 2 yrs. ago and it works fine. I don't want to replace the upstairs air handler if I don't have to---much more cost.


I'm assuming you have had a competent Air Conditioning contractor look your unit over.if you trust your A/C contractor, why don't you work with them towards an answer? I would get an air flow and sizing analysis, a full equipment service/performance ... Air Conditioners

I have a new motorhome and the air conditioner only reduces the inside air temperature by 2 degrees on a hot day. e.g. outside air temp 26 degrees inside temp 29 degrees. After 2 hours of a/c running with door and windows shut inside air temp is 27 degrees. Dealer says the air conditioner is ok as air coming out of ducts is 3 degrees as required. I believe a larger a/c is required.


Can you tell me what size/make of motorhome you have? Certainly doesn"t sound right to me, and I've been working on them for over 15yrs. Whether it's a 13,500 BTU or 15,000 BTU, it should be plenty as long as motorhome has any insulation at all. I a ... Dometic Rooftop RV Air Conditioner

I have an Edgestar Portable Air Conditioner AP12000HS. The Air Conditioner works wonderful, however I can't get it to heat, I put the Mode Button on red which is supossed to put the heater on, it will run for a few minutes and then shut off and it does not take the chill out of the room I have the unit in, is there some kind if thermostat internally which can be set? The way it runs now does not do me any good as a heater.


The unit has a built in thermostat in the front control panel, this is what maintains the set temperature, it is very likely that this control is defective, all the controls for the unit are contained in the CCU (central control unit) ... Air Conditioners

I have a Fujitsu reverse cycle air conditioner ASTA09LCC in a house that has been work very well on the heat mode but suddenly the breaker fall down ,,,and after we do the breaker, the air condition not work at all ,,and the green flashing light show up every 20 second and e dont know what to do ,,,pls help me ,,,thanks a lot


... Air Conditioners

My air conditioner Daewoo DWC-100R keeps tripping the switch on power bar ... I just purchased it second hand and was assured it was in perfect working order. I am 65 yrs. old female with no knowledge of air conditioners and a limited money situation. We are in the ;middle of a heat wave and my apartment gets very hot. Can you help me?


Have you tried to plug it directly into the wall Maybe the the power strip you are using is not able to handle the amps needed to run air cond. If thats not it you have a short to ground that needs to be checked out. ... Daewoo DWC-100R Air Conditioner

Hi Expert, my reverse cycle aircon is Samsung model name=AQY09NSBN, only fan is working on the outside and inside unit at the moment, no heat air or cool air coming out of the inside unit, even tried with different temperature setting. Everything was fine till my gutter downspout was blocked and the switchbox outside near the unit was flooded and the aircon was on and off by itself every three seconds, so I turned the aircon off from the main switch outside. I got an electrician to replace the


Hi, and no your warranty is not void due to a flooded disconnect box, this is a lie!! If both fans are running, and you have no heat or cooling, the compressor is not running. This is a heat-pump with a reversing valve. The indoor unit has a control ... Air Conditioners

I have a ruud achiever 10 model UPKA-018JAZ with air handler in attic. Was wondering if this is a single stage heat pump or a multi stage? trying to connect new thermostat, air conditioner is working but when turn on heat only the fan comes on and the compressor outside never comes on to warm..but compressor does come on when switch to cool..


This may be as simple switching the thermostat to electric, under the cover is a gas/electric dip switch. Hope that helps. ... Ruud Matching Split Air Conditioner

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

We have a slim heater/ air conditioner on our wall. It's been in airconditioning mode for the summer. I'm having trouble 1 . it shuts off within seconds of turning it on. I've tried to cancle the timer. Lost the manual. 2. I cant get the fan to blow warm air, the blade to even rotate but it works with cold air!!!ouff... ....the remote is on heat ....temp says 74 on both wall and remote mdl # LMN120HE suggestions?!? We're cold.....


This is a tippical heatpump problem. get the revers valve unstuck. energise the coil to the valve, on and off. make sure the power is on to the coil.(HEATING MODE AT FULL TEMP). if you are not electrical minded leave it be. get someone with electrica ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

Our Mitsubishi Electric Dual Air Conditioner is not working properly, it was pumping out hot air the other day and we have checked that it is not on heating mode and it isn't. Now the air coniditioning is supposed to be on and we don't feel anything coming out. Please help.


Check sure the on the outside unit that the fan is running and secondly the compressor is running,you will not any cold air if the compressor is not running ... Mitsubishi Air Conditioners

I have a 18000btu LG mini split heat pump installed about 1 year ago in vacation home. In heat mode the unit cycles on and off when room temp is within 2-3 degrees of set point. Cycle on time varies between 35 to 60 seconds (sometimes more). The off time is 2-3 minutes. During this time, I check inside temp with accurate digital themometer mounted at the air intake of the unit and the temp does not change, assume because unit does not run long enough. When I put temp set point more than 3 d


Hello.I think they are on to something with shortcycling on temp sensor.I think it should be sampling the return air instead of (inside coils ?).A 2*f dead band use to be built in (factory installed) to thermostats to prevent on/off, but ... LG LS-L1210CL Mini Split Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific