Having problems with your Air Conditioners ?

Hi All, I have a carrier reverse cycle airconditioning unit and about a week ago the digital thermostat blanked out. I spoke to an aircon repair tech and he suggested that the fuse is blown at the air handler and suggested that I can probably replace the fuse myself. My question is where is this fuse located in the carrier units, do I have to open panels or is it in a box like a fuse box in a car. I have no issues checking the fuse if I know where to find it LOL, The model of the unit is


Answers :

It will be inside the unit main panel. Turn main power off and remove the main front panel. The fuse will be located on or near the fan control board. Typically they are a flat agc type fuse. 3-5 amps. The problem will be that if the fuse is blown -there is a reason for it. They don;t just wear out and blow. Look for frayed wires around the outside unit and in the thermostat to make sure you dont have a short. Otherwise, you will just blow the fuse you replace.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Hi All, I have a carrier reverse cycle airconditioning unit and about a week ago the digital thermostat blanked out. I spoke to an aircon repair tech and he suggested that the fuse is blown at the air handler and suggested that I can probably replace the fuse myself. My question is where is this fuse located in the carrier units, do I have to open panels or is it in a box like a fuse box in a car. I have no issues checking the fuse if I know where to find it LOL, The model of the unit is


It will be inside the unit main panel. Turn main power off and remove the main front panel. The fuse will be located on or near the fan control board. Typically they are a flat agc type fuse. 3-5 amps. The problem will be that if the fuse is blown ... Air Conditioners

When I turn my electric a/c to heater it makes a repeat tac sound quite loud. An a/c tech opened the metal box on left side where the fuse is located and said that the board and relay needs to be replaced. My a/c heating unit is an American Standard made by Trane model TWV036B140A1. What do you think it might be the problem? What are the technical name or numbers of the parts the a/c tech is referring to? Where he or I can buy it and for how much? What is the guarantee? Thanks. Tommy reply2t


It sounds like the tech was referring to the blower relay. The blower relay on this unit originally had a small circuit board mounted to it. It's only purpose was to allow for delay off-time of the blower at shutdown. In other words, once the command ... American Standard Air Conditioners

Goodman a/c j41 fan not running, turned off and on at fuse box, took a look at the box next to a/c unit and opened the box on the wall and pulled the plug and pulled the plastic panel off, there is no fuses. So i put back together and turned the a/c unit on, now at thermostat the snowflake is no longer flashing, some cold air coming out of vents, but outside a/c unit fan still does not run.


First you need to disconnect all power. Try spinning the fan blade, if it spins freely, then try moving the shaft from side to side to see if there's any side play. If not then the bearings are OK. If there seems to be some drag when your spinning th ... Goodman CKL42AR42 Air Conditioner

I have a duo-therm roof top unit. The fan or a/c will not come on. I opened the connection box and ckecked the fuse on the printed circuit board. Fuse good. reinstalled fuse and unit came on. Turned of t-stat and waited a long time and turned it back on Nothing.Pulled the fuse and reistalled and the unit started. Whats the problem?


Hi; You still have a loose connection somewhere. I have found just recently a problem with a customer with the same problem He had burnt wiring at the compressor terminals. Also check to see if the fan on top of R.V. is running when the inside fan is ... Dometic Rooftop RV Air Conditioner

Our inside unit Coleman EB20B (outside unit Goodman GKL 49-1) keeps blowing the in-line 3 amp thermostat fuse. We've rewired the wires in the wall, rewired the contactor wires, and the contactor was broken so we replaced it. We're still blowing the fuse. Could we have reversed the thermostat wires at the contactor? Or could the short be in the Blend Air box-this box is coupled to the thermostat wires? Thanks Ken Rohm


Hi,Mark\015\012 all your wires using tape or by writing it down to ensure you will be \015\012able to hook them back up exactly the way you found them. Remove all the\015\012 wires from your board again. Tape off the ends so you don ... Coleman Air Conditioners

CARRIER AIR CONDITIONER/HEAT PUMP PROBLEM WOULD NOT RESPOND TO THERMOSTAT. UNIT IS AT LAKE HOUSE WHERE WE DO HAVE BAD STORMS. IN CHECKING, INSIDE PART OF UNIT HAD BURNED UP THE TRANSFORMER BUT NOT BLOWN THE FUSE. REPLACED TRANSFORMER . . . COULD SMELL AND THIS TIME TRANSFORMER STARTED TO MELT AND BLEW FUSE. SOMETIMES THE FAN WOULDN'T EVEN COME ON WHEN JUST SWITCHED FAN "ON" AT THE THERMOSTAT. QUESTIONS: WHAT WOULD KEEP BURNING UP TRANSFORMER. WE REPLACED WITH EXACT TYPE THAT WAS ORI


What I have always been told is if your 24 volt side burns out check the high volt side if the hi volt side burns out check the low volt side.A quick way if the primary side is burningout due to a problem with the low volt side:1 MA ... Air Conditioners

The unit set the breaker off in my house, i reset the breaker but the unit will not come on...the breaker box has been replaced,the capassitor has been replaced, the brown item with the red, yellow, purple green wires has been repalce.. when i turn the breaker on in the house it keeps blowing the fuses in the breaker box


Oull the fuses out of the disconnect by the condensing unit. Then, reset the breaker. Does the breaker stay on? If so, your incoming power to the unit is OK. If it trips, you have a short somewhere. If your OK with power from the breaker to the ... Goodman CKL60AR60 Air Conditioner

I have a 10 yr old Armstrong AC..today I found that the evaporator coil has a small leak, replacement cost $750. The unit uses R22. The repair company suggested a heat pump, should i decide to replace the entire AC unit. ($3700) Location is Lincoln NE. Repair or Replace?


DEAR FRIEND,\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012ngfam1 here for you!\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012\015\012I am happy to ... Air Conditioners

My GE Zoneline Air Conditioner stopped heating. The AC is just fine. I think it might be a fuse? The previous owner replaced the fuse on the Master Bedroom unit before we moved in. I can't seem to get in touch with him to find out the kind or location. Cany you help? Where is the fuse located and what is the part number?


I can not supply part numbers without knowing which fuselink or thermostat relay is nbad.To access the heater you must unplug the unit. Then remove the grill covering the top part of the evaporator. That is the cooling coil towards the front of ... GE Zoneline AZ25E12D3B Air Conditioner

My amana window unit blew a fuse in my fuse box I replace it now thw window unit won't come on


Candy, if the fuse blew in the first place, it was either overloaded or the AC unit has an electrical short in it. However, it may not come on now, without turning the Master Switch on the AC unit OFF and unplugging it from the outlet. Wait 10 minute ... Amana Air Conditioners

Mitsubishi MXZ- 3A30NA 20 Amp fuses blown at disconnect, replaced, energized no responce fuses did not blow, no LED lit on PC control Board. Page 41, 10-6 Troubleshooting Flow of Tech Manual, Outdoor Unit Does not operate. (LED display: display off) Input power to Noise filter board good. output power to reactor not reading 240VAC between legs TAB1 and X-64 pin located on contactor on noise filter power board, however I do get 120V each leg to ground. Replace noise filter power board? I removed


Have you checked the reactor board for a defective M.O.V. thyristor that way have a burned spot on the side of this component that normally would have, due to a lightening strike,over-voltage or under-voltage,if they open they will kill one leg,or po ... Air Conditioners

Carrier 38CK036330 Hi,  I totally know nothing about air conditioning. It's getting so hot in LA and we really need help since our house has a 18-month old child. We have a Carrier 38CK036330 central unit, and it's not cooling the house as we'd like it to. It's already about 13 years old and we are looking for a new one to replace it. The question is we cannot find this model anymore, or do we have to replace it with the same model?? What model or brand would you suggest for a 1350 square feet h


The model numbers change.You have a 3 ton system.The make and model that you replace it with is not nearly as important as a quality install.Do your homework on picking a contractor that you can trust.Have them do a load calculation to make sure a 3t ... Carrier 38CKC060 Air Conditioner

I have a Carrier 38tra048340 ac 4 ton unit outside, heater in attic. Thermostat is Totaline P374-1100. Power went out than back on after a few hours due to vehicle crashing into power pole. AC was running at time of power outage. Power came back on, ac would not come back on. Checked house circuit breakers, none tripped off. Turn ac 40amp breaker and heater 20amp breaker off and back on. Voltage ok. Checked fuse box by ac unit on wall, fuses and voltage ok. Went into hot attic to check for powe


Blank screen sounds like a fried thermosat. Abrupt outages can affect certain types of thermostats. Make a jumper wire and jump across R and G. See if you get any action from anywhere. If a fan or compressor kicks in you know you have a burned out th ... Carrier Air Conditioners

Cental air unit stopped working, I replaced the capacitor which had blown apart, but the unit does not restart. It works when I push in and hold the button on what I believe is the relay where the power comes into the panel of the unit. Is there another fuse or reset button that needs to be reset within the unit. Any suggestions? The model # is AC1BN036-A and it's from about 1995.


You shud test the relay with multimeter for any shorting out or restricions.\015\012locate it and test it, if it is not beeping or showing zero its defective and you gotta replace that relay if its good, well you gotta locate the shorting out i ... GE Air Conditioners

Carrier Infinity AC indoor unit in the garage is leaking water on the floor. There is no ice on the coils, The drain is not clogged. There is no water in the coil area. I turned off power to the indoor and outdoor unit and it continues to leak water. I finally shutoff the water supply coming into the house. The leak then stopped. The unit is on a wooden box approx 3 feet above the floor in the garage. The only water seen is on the floor. I open the side of the A/C unit an


Hi,It seems as though you have an unrelated water leak.... Often the water supplies are copper tubing....Copper tubing and concrete do not get along well...but hey it lasts till the warranty is up....and they can't see i ... Carrier 52CQ315 Air Conditioner

Hi: I have a Carrier 38CMC42300 AC unit which will not turn on and the air handler is blowing hot air. The 40 amp breaker for the AC unit trips right away when reset. Could this be a condenser or motor problem? Note: an assessment by a service tech has recommended the whole unit be replaced (it's 8 years old). Any suggestions are welcome.


Hi,Your compressor or the start components are bad...\012\012Here is a tip about troubleshooting your air conditioner...There are many things that can cause your air conditioner not to cool... ... Carrier 38CKC036 Air Conditioner

Goodmorning,Our Carrier remote air conditioner doesn't want to come on.It hasnt been used since summer, I replaced the batteries in the handset & reset the remote, the unit beeps thru every mode change but the wall unit on green light is lit but blinks on & off. The motor unit outside isnt coming on at all. Do you have any suggestions as to what maybe cusing this problem. Model RFL-0601EH


Hi there,\015\012\015\012Can you please check look for the factory sticker on the Aircon unit (preferably wall unit & outdoor unit).\015\012\015\012Will try to help once I have those details.\015\012\015\012Cheers, ... Air Conditioners

Gas furnance would only operate for about 3-5 minutes then turn off. Replaced gas valve on furance for a Rudd comerical A/C 4 ton unit model UKKA-A048JK10E. Now the blower fan turns on but the igniator and gas does not come on as before. LED light (flashes 5 times) on board indicates flame roll out switch is open. Need manual to locate roll out switch, does it have a reset button or does it need to be replaced?


The rollout switches will be located at the ends of the burner assembly and will have a manual reset. they must be manually reset to ensure that the problem has been corrected. Most units will go into a soft lockout for a time and eventually a hard l ... Ruud UAKA042 Air Conditioner

My Carrier AC outside unit will not tuen on. All fuses and breakers are good, and I can hear a humming coming from the solenoid. When I disconnect the wires from the house unit to the solenoid there is a clicking of the valve. I have taken out the solenoid, could it possibly need to be replaced? thank you!


... Carrier 38CKC042 Air Conditioner

Compressor on Ruud Unit UAMA-042JAZ and its fan won't run. Electric comany said low voltage circuitboard problem. Suggested replacing the fuse on the circuitboard. I could not find a fuse, where would it be loacated?


The units has what you call a contactor which is actually a relay but it does not look like a relay. You can get a none conducting material to depress it. and the compressor should run and the fan. Be very careful since that contactor has exposed par ... Ruud UBHC Air Conditioner

No heat, no ac. Power apparently not getting where it needs to be. Checked the fuse in the unit (5amp) still good. I have non-fusable boxes located next to furnance inside (crawlspace) and outside unit. Breakers are on What other problem am I not looking at?


Hi, you do have a power problem, that's for sure.If the indoor unit has a non-fused box, and condenser also, it would have to be at the main breaker. That's the only power source you have that supplies power to everything is the main breaker. If you ... Air Conditioners

I have outdoor Goodman compressing unit, model #cple24-1c. The breaker tripped and I was told to take out the connector located in the box by the unit and reset the breaker. The breaker did not trip again. I was told to replace the electrical whip because we had alot of rain recently. Is this right?


No, the electrical whip should be able to handle all weather, moisture, and even immersion. The only reason to replace a whip is if it has suffered some kind of physical damage. I recomend keeping an eye on it and if it trips again, have a pro come ... Goodman Air Conditioners

OLD 5 TON CARRIER ROOFTOP a/c KEEPS BLOWING A FUSE. We tried changing 2 capacitors... we tried a new transformer too, but it started smoking so we put the old one back in. The unit ran fine for a few days and then blew the fuse again. Suggestions????????


Hi there,Check for any short circuit on the unit. it seems that there was a problem on elec circuity on the ac.Btw.. may i know the model # of the AC ... Air Conditioners

My Goodman Mfg AC unit is blowing fuses on the control board inside the blower/air handler unit. This fuse supplies 24V to the outside compressor unit. Originally, there was a 3 A fuse in it. I replaced it with a 5 A fuse that lasted for a year. Now it has blown. I suspect that the solenoid actuator coil on the outside compressor unit is becoming lossy and drawing more amperage in the hot weather and my solution is to replace that component. Does that sound right?


This must be a diy board ... Air Conditioners

Planning on replacing my Federal Pacific circuit box. It is a 24 breaker box. I just checked it to find that it is rated to handle up to 125 amps. Few days ago, an electrician checked the box and suggested a 100 amp 20/40 Siemen box. Until today, I did not catch the amp difference between my old box and what he has suggested. I have a call into him. Doesn't make sense to me to go to a lesser rated box. If anything, I would think that a replacement should be a larger amp box, ie 150 or 200 amp.


You do not need to replace the main circuit breaker with less rating, it may trip during peak loads due to lesser current carrying capacity. If you are planning to replace the main circuit breaker with higher rating, you must verify first if the main ... Air Conditioners

A detailed question is important to get you a relevant answers