The heat pump is not working properly. i think the problem is in the switch mechanism. when the heat is on and the thermostat is turned up it blows cold air. sometimes the compressor turns on and off. if you turn the other switch to the off position, then turn the thermostat up then turn it back to heat. it will blow hot air. if you then turn the thermostat down, wait till it turns off, then turn it back up, it will blow room temp air and sometimes the compressor will turn on.


Answers :

Hi,
\012The problem may be the switch, but it sounds more likely that the contactor in the outdoor unit is bad and is not making all of the time...then the compressor will not always run...
\012To figure it out you will need to catch it at a time when it does not owrk and then follow the electric back till you find out why there is no power...
\012It would be best to have an electrical meter and have this done by an experience person so that you do not get shocked...
\012
\012heatman101

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

The heat pump is not working properly. i think the problem is in the switch mechanism. when the heat is on and the thermostat is turned up it blows cold air. sometimes the compressor turns on and off. if you turn the other switch to the off position, then turn the thermostat up then turn it back to heat. it will blow hot air. if you then turn the thermostat down, wait till it turns off, then turn it back up, it will blow room temp air and sometimes the compressor will turn on.


Hi,\012The problem may be the switch, but it sounds more likely that the contactor in the outdoor unit is bad and is not making all of the time...then the compressor will not always run...\012To figure it out you will need to catch it at ... Air Conditioners

Reset button for Ruud Achiever 14 heat pump/AC compressor? My Ac/heat thermostat was blowing fan on and would not turn off. I switched it off at the circuit box, and bought a new thermostat RTH221, wired it and it would not blow cool air when on cool nor warm air when on heat. Called the 800 number for Honeywell and tech said I had wired it correctly, to check outside and see if the compressor was running. It was not. This Ruud unit is only 8years old so I'm wondering if a reset button has


... Air Conditioners

I have a honeywell PA404A pressure control switch on my home gas steam heating system. I'm having a problem with the switch turning off the system. It will only come back on if I turn the top screw all the way out, then back down to approx 5psi. At this point the heat will turn on but when the thermostat shuts down the system it will not turn back on when calling for heat unless I adjust the screw again. Also, the switch will only turn on the system when set at 5 on the dial on the inside. Any i


This may be caused by accumulation of sludge in the steam trap (the looped tube that connects the pressuretrol unit to the boiler). the sludge restricts the pressure from reaching the diaphragm in the pressuretrol unit. So it gets a false reading. ... Air Conditioners

I turn the thermostat down at night. When I get up in the morning I turn it back up. The heat kicks on for a minute or two then the unit starts blowing colder air. If I turn the thermostat to the OFF position, wait until I hear all blowers stop, then turn it back to the ON position, it will start blowing HOT air again. Some times I have to perform this cycle 3 times to get it to keep blowing hot air. Any ideas as to what is shutting the furnace off? Thanks, Wayne


Theremostat switch problem. Replace it. ... Air Conditioners

My fedders aircon compressor does not turn on again whenever its thermostat turns it off. what i had to do is unplugged the power cord and turn it on again to work. i already replaced the capacitor. what i observed is that the big normally open rely does not switch on. maybe a board problem? if i turn it off and turn it on again, only the fan rotates and not the compressor. i had to unplug the power and put it back again for the compressor to run again.


You have a time delay build in on the pc board of 3 minutes. If it takes longer than 3 minutes check your compressor overload protector, Maybe the compressor is overheating, check your coils for proper air flow. ultimately if the compressor checks ok ... Fedders A6X05F2D Air Conditioner

Honeywell digital non-programmable thermostat rlv310.i have radiant ceiling heat ...just installed....thermostat function works properly...question is in regards to display function....in a 24 hour period, the display has gone out as if going into a screen saver mode....in both times, hitting the buttons does not restore the display.....i've had to go to the switch box, turn off the breaker switch and then turn it back on for the display to reappear...in both cases, when the display reappears, t


... Honeywell Air Conditioners

Honeywell thermostat T8400c started flashing, heat/cool was off. Display flashes all icons (heat and cooling icons, temperatures, everything) and on the oppposite flash, the setpoint is displayed. The fan comes on when turned to ''ON'' but heat or cool does not when in ''auto''. The compressor can be turned on outside at the switch, but appears to have no freon. Heating & cooling worked within 2 weeks prior to this issue. Any help would be greatly appreciated.


Based on the simplicity of this particular t-stat, I really think that it is bad and needs to be replaced. They do not make this particular model anymore. I have included a link to the operators manual for the stat. Good luck!\015\012\ ... Air Conditioners

My heat pump continues to blow air almost right up until the compressor kicks back on. It makes the room feel cool because it is blowing air that is no warmer than room temperature. The a/c is a Miller model number PCZD-030KB and the thermostat is a Honeywell model number T874R. They are both over 15 years old. Should i simply replace the thermostat? And is there any rule of thumb as to what thermostat i should replace it with or will any do?


Any thermostat will work, I recommend digital thermostats. Ones that you can program are a plus, it will save you money as well as help the environment. It is normal for your blower to continue blowing well after the heat stops, this is called cyc ... Air Conditioners

GE zoneline heat pump/ AC unit wont blow any hot air? When you turn the switch to high heat and the thermostat all the way on it blows ice cold air. Its like the unit is just blow the cold air from out side into the room. help


... GE Zoneline AZ55H07D Air Conditioner

There's a Frigidaire heating and cooling unit in the attic, and the thermostat is a White Rodgers (programmable). Air is blowing, but it is not HOT, though the thermostat is set at a high temperature. I have turned the switch to OFF, but the fan continues to blow. There is another compartment (as the heater lies on its side) that indicates that it's to only be open for servicing. I'm think that there is some sort of RESET button needed. Recently, new insulation was added to the attic.


Is this gas or electric heat?I can help you with all of it, but I need to know where we are working from.As for the blower running, it's either caused by the Auto-Manual switch being put in Manual, or, there is a time delay fo ... Air Conditioners

I have a ruud achiever 10 model UPKA-018JAZ with air handler in attic. Was wondering if this is a single stage heat pump or a multi stage? trying to connect new thermostat, air conditioner is working but when turn on heat only the fan comes on and the compressor outside never comes on to warm..but compressor does come on when switch to cool..


This may be as simple switching the thermostat to electric, under the cover is a gas/electric dip switch. Hope that helps. ... Ruud Matching Split Air Conditioner

We have a Rheem Imperial 80 that won't heat. We have turned the power switch on and off and set the thermostat to heat. It blows air, but doesn't blow hot air. Is there anything we can try to do to fix it, before calling a professional?


Hi,Here is a tip that will help you try to figure out why your furnace is not working.Basic Furnace or Heatin ... Air Conditioners

Hello :) We have a frigidaire 12000 btu in wall unit. It was working fine lastnight but when we got up this morning (we had it set to heat -on 69 degrees) it was making a buzzing sound. I have tried turning it off for a few then turning it back on. It seems as though the fan will blow slightly but the heat ,compressor nor the air will kick on. what do I need to do?? Thanks for your help !!


1. Switch off the AC first for a few hours2. Remove the power connector 3. See that the Compressor is cool first4. check the air tube and the blowers5. Reconnect the same and connect the power cables6 ... Air Conditioners

There's a Frigidaire heating and cooling unit in the attic, and the thermostat is a White Rodgers (programmable). Air is blowing, but it is not HOT, though the thermostat is set at a high temperature. I have turned the switch to OFF, but the fan continues to blow. There is another compartment (as the heater lies on its side) that indicates that it's to only be open for servicing. I'm think that there is some sort of RESET button needed. Recently, new insulation was added to the attic.


Unless you have and oil fired furnace, there is not a "reset" button. Most likely, the problem will need to be investigated and addressed by a qualified service technician due to the general complexity of HVAC equipment and a plethera of different p ... Air Conditioners

I have an AR32-1 with an emergency heat switch on the thermostat. The heat pump runs and runs and runs and blows cold air when it's freezing outside. If I turn on the 'emergency heat', nothing happens. We do have three 220V breakers in the panel box. One is labeled 'heat pump', the other two are labeled 'furnace'. What could be wrong that the 'emergency heat' does not work?


... Goodman Air Conditioners

I have an Amana central air/heat unit. Model PHCB10C1 Serial # A040900070 Manufacture # P1219409C, Cat # 81K95. The problem I am haveing is the unit will not kick in(heat). When I turned off the main pwer and let off for about a hour and turned back on the unit ran fine for a couple days. Now the unit will not kick in at all even after turning the main power off and on to reset the unit. I have a brand nre thermostat in the house. When I turn the fan from auto to on the fan runs and blows out


... Amana Air Conditioners

Have a Amana a/c heater central furnace. Model number PGA30R0452A. The a/c part works fine. The heater part does not turn on sometimes. We have to keep turning it on and off to get to work. No matter what you hear a slight humming when we turn it on just it doesn't always blow air out of the vents. It also does not always kick back on once the temp. has dropped and should start heating the house again. We have programmable thermostat. Any suggestions to whats broken or breaking. My husband woul


When you change from cooling to heating the fan will not come on immediately. A solenoid valve is energized (check that it is working) and operates a reverse valve, changing the gas flow in the system. It takes a few minutes for the system to build u ... Air Conditioners

I have an intertherm electric furnace FEH-A020, with multispeed blower installed when A/C added. My problem is blower operation. at the end of the cooling season with fan set to auto operation the fan ran continuously. Now that I've turned the unit back on for heat the blower will only function with the switch in the on position (continuous operation), in auto mode the heating elements come on with the signal from the thermostat (Honeywell CT3400), but the fan does not. I checked the fan relay p


The model of T-stat you gave comes up as a discontinued model on Honeywell's web site, but it looks to be a manual stat that type of stat would have to be wired with a summer winter switch with electric heat, allowing it to turn on the fan with a cal ... Intertherm P3RA-048K Air Conditioner

I have a LUXPRO PSP600 digital thermostat and when I switch it to heat it automatically comes on. The hot air is blowing fine. However when it meets the temperature that is set, the heater turns off but the furnace in the basement for air circulation doesn't turn off. It keeps running. (The fan with the furnace in the basement kept running.) Any help would be greatly appreciated. Thanks in advance!


My nokia cant play youtube video ... Ruud UBHC Air Conditioner

I have a frigidaire window unit model fra256st2, when I first turn it on the unit blows ice cold air for 1 to 2 minutes then the compressor kicks off. I have to wait 5 minutes then switch it from cool to fan only then back to cool again in order for the cOmpressor to Kick on for another 1-2 minutes.


... Frigidaire Air Conditioners

I have a 2000 Mercury Sable OHV 3.0L V6 engine. I drive the car every day to work without turning the AC on and it does fine. As soon as I turn the AC on, it starts to over heat. I already changed the thermostat, and temperture switch. I suspect the next thing I have to change is the compressor. what else can it be.


Your A/C Works, so its not the Compressor. Don't Ask, change the water pump and do also a pre-fllush, with a good Radiator Flush, and do a full flush-out of the cooling system that will take care of the entire Engine Block and water ways, in the proc ... Air Conditioners

I have two heatpumps up and downstairs and two furnaces (piigy back). At times my pump outside freezes up and cold air blows in the house. I was told that I needed a kit to tell my furnace to turn on when it gets to cold for the heat pump. It will cost 400. This is the third time they came out. 1-nothing wrong. 2-New thermostat 3-Need kit. Is this something I can do? Amana Heat Pump RHA36B2A


Hi,\015\012A couple of things... First your furnace should be 2nd stage on a 2 stage thermostat and if the heat pump don't keep up your furnace should be coming on anyway...If you get a Honeywell Vision Pro 8000 series thermostat for 2 stage he ... Air Conditioners

Hi I have a Lennox heat and air conditioner roof top on my unit. What's happening is,the heat turns on for a about 10 minutes then shuts off, the only way to turn it back on is to turn off the thermostat, then turn it back on, but will keep doing the same. Oh and one other thing, the filter warning is showing on the thermostat, could it be as simple as changing the filters? Any suggestions anyone?


You are right, you must change the filters, since it isno longer working normally. May this help you. ... Air Conditioners

The air conditioner has a flashing red light on the thermostat. The heat is not working. The fan will turn on if switched to ON, but will not engage if just on AUTO. Even when the air is blowing, there is no hot air. It is about fifty degrees in the house right now. - I checked the breakers, and put everything through a power cycle, nothing is having an effect.


... Hunter 30124 Air Conditioner

I just moved into a new place and it has the RTH230B thermostat installed. I turned on the furnace, set the thermostat to "Heat" then the fan to "Auto" and used the up and down arrows to set the temp to 72 degrees. The temperature seemed fine for the first hour or so. However, the heat and fan stays on full power and continued to heat at full power well into 80 degrees on the thermostat screen. I could only shut it off by turning off the actual furnace switch. I first tried reducing the temper


From what you learned from your neighbor, I would say no. Certainly, sounds like a manufacturing defect to me. ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1117 seconds