Having problems with your Air Conditioners ?

My ruud deluxe 89 furnace is not working. The fan will work but does not blow hot air. When I move swith to Auto I hear the click, but nothing happens after that. I have changed the filters which were very bad and have changed the batteries to the thermostat. Van you help? I was hoping it was only a fuse or something like that. Im not sure where to find the fuse though. Thanks, Brayn


Answers :

The directions on mines says to turn the pilot off for 5 min to clear gas out the pipeline. then turn it to the PILOT position and push down while lighting it, then once its lit turn it to ON. ive tried that but its not working. i dont know if im not doing it long enough. did anyone help you yet? FW

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

My ruud deluxe 89 furnace is not working. The fan will work but does not blow hot air. When I move swith to Auto I hear the click, but nothing happens after that. I have changed the filters which were very bad and have changed the batteries to the thermostat. Van you help? I was hoping it was only a fuse or something like that. Im not sure where to find the fuse though. Thanks, Brayn


The directions on mines says to turn the pilot off for 5 min to clear gas out the pipeline. then turn it to the PILOT position and push down while lighting it, then once its lit turn it to ON. ive tried that but its not working. i dont know if im not ... Ruud Air Conditioners

Hi i have a white rodgers thermostat model 1f58w-58. And I need help! We tried to change the thermostat to a new one, but for some reason the ac would not turn on. So we put the old one (white rodgers) and put all the wires back how they were and it still won't turn on! is there a fuse or something?


... Air Conditioners

Air conditioning unit not running but fan keeps running even though thermostat is turned to off, auto, and temp set to highest position 90degrees. 3 amp fuse keeps blowing on the circuit board in the blower compartment. I replaced it 3 times then installed a new thermostat. no change. I can usually figure it out if I got a little input or direction. Any help would be deeply appreciated. I would much rather have a trained expert easily repair my hvac unit but I can only call the professionals in


If the fuse is blowing then this is generally indicative of a short in the low voltage wiring, isolate the wires on the thermostat and the unit ends, use an ohmmeter to verify that there is no path for continuity with no wires touching, if there is t ... Air Conditioners

I have a GE PTAC I have been working on. Our units are run by a wireless wall thermostat which sure doesnt help matters. Anyway at first I had nothing then got power lighting up on the circuit boards for the wireless. No power going to either the heater or the compressor. Changed out a couple circuit boards from spare parts and got power going to those now but still doesnt operate. I've checked the transformer and the capacitor. Checked the fuse and changed out thermister. Nothing. Any ideas


... GE Zoneline Deluxe Series Cooling & Electric Heat Unit AZ25E07D3B

I HAVE A HUNTER PROGRAMABLE THERMOSTAT AND CAN'T REMEMBER WHERE I CHANGE THE BATTERIES, ITS READING "LOW BATT" PLEASE HELP, THANKS


Pull the unit face straight out and away from yhe wall plate. It plugs into several contact pins so rock genttly if you do. Good Luck, Ned. ... Air Conditioners

York central ac keeps blowing 3amp fuse on the circuit board when the compressor kicks in. thermostat changed with no help. what's next


Sounds like you have short in the low voltge side of the electrical circuit. I would check the thermostat wires outside at the condenser. look for any bare or exposed wires from where the wire comes from the house to the condenser. the thermostat wir ... Air Conditioners

My programmable A/C thermostat shows power but no temperature (just disappered). No A/C. Fan runs continually. Shows ''Lo Bat'' but changed battery--did not help.


Hello,try as much as possible to see that the battery you purchase is of good quality,because we have witnessed the sale of bad thermostats batteries.you can kindly visit the site below for a more comprehensive solution and instruction.\015\012 ... Air Conditioners

I read on the honeywell thermostat T8400C that if the reading went blank, try changing the batteries. The only way i see to get inside the thermostat is to unscrew a couple of screws. However, on the outside it says, "Do not remove screw". How do I change batteries on this thing without removing the screws? Beyond that, what can i check?


This unit gets it's power from the air handler transformer. Check your breakers, then take the front cover off the furnace or air handler and check for a blown fuse. If a fuse did blow, there might be some other problem. Replace the fuse, and h ... Air Conditioners

My thermostat had a blinking low battery symbol in the top left corner of the led screen and the furnce would not stay running as a result. I have changed the batteries and the furnace cut in but will only run for so long before it shuts off and the sign on the screen says heat on but the furnace is not cutting in and the temperature is way below the set temperature for the house. If I keep taking the panel off the wall and reconecting it as if i changed the batteries every time, then the furn


Your thermostat sensor is getting week. Please change your thermostat. ... Honeywell Air Conditioners

The thermostat for the main zone in my house (honeywell model RTH5100B1017) is battery powered and it blinked change the battery for a couple of daye and then went blank. I have changed the batteries twice and It's still blank.


Check any batteries and replace if needed. Ensure that you use only AA alkaline, nonrechargeable batteries.\015\012\011\011\011\011\011\011\011\015\012\011\011\011\011\011\011\015\012\011\011\011\011\011\011\011\015\012 ... Air Conditioners

I have a Honeywell T8131C programmable thermostat. Our power went out yesterday, and now the "Bat Lo" won't go away. We replaced the batteries, but the "Bat Lo" indicator stayed on even after changing to new batteries. As per the troubleshooting guide, we took them out, waited an hour, and then reinstalled new batteries. Still, the "Bat Lo" indicator is still on. How do I get it to go away because I can't adjust the thermostat with it that way?


I tried all the tricks mentioned previously to no avail. \015\012\015\012These are the steps I performed to get it to work:\015\012 \015\0121. Remove batteries and make sure the battery contacts inside the unit are clean. ... Air Conditioners

Carrier 58RAV095-16 will process thru the test sequence properly: inducer fan, ignitor, blower high, blower low, all ok. fuse checked good on controller board. when commanded to supply heat by the thermostat controller in the living space the unit runs with fan only, no gas, no ignition. changed thermostat controller, no joy. Comments: Jan 31, 2010 - thermocouple/ignitor is ok and positioned well. It tests ok too. I changed it last year. I am not getting gas flow so I suspect gas control va


Go to the furnace and turn off the power take the door off you must have a multimeter inhand with the cover off the furnace and access to the gas valve put yor meter leads on the wires going to the gas valve turn the power on and after the ignitor gl ... Air Conditioners

I installed a new honeywell rthl111 series in Oct. 2012. I wired the blue wire to the RC because that was how the old thermostat was wired. The heat worked all winter but when I tried to change over to cool nothing would work. I checked the schematics online and realized I should have installed the blue wire to the B. I checked the fuse in the power panel and saw I had blown it. I changed it and rewired the thermostat the correct way. I tried again and still neither the cool or heat will work. A


... Goodman Air Conditioners

Totaline Thermostat. P474 1035 Batteries died while I was out of town. I thought a simple replacement would have it up and running! Screen comes on and reads the room temp just fine but will no longer turn on the a/c in any mode (manual or auto). I looked at the manual and it gives a wonderful warning "The manufacturer cannot be liable for improper operation of the thermostat if the batteries are not immediately replaced." Help!!! Is there any way to fix it? This is a time I wish I wasn't


Not good news...the manufacturer is issuing this disclaimer because of a reason. I would contact the manufacturer and explain the situation to them, since you couldn't replace the batteries as you were out of town. \015\012Here's a web blog ... Air Conditioners

My goodman air unit wont turn on but has power to the relay and can be manually overridden at the relay but doesnt sound like the air handler comes on. I changed the batteries in the thermostat and even switched the thermostat with my second unit on opposite end of house. I also thought it might be the run capacitor again so I changed that already. Any ideas?


Check the transformer. There could be a chance that the transformer is out. If you mean you can manually turn on the unit by pushing in the contactor switch in then theres your problem The thermostat engages the low voltage side of the transformer ... Goodman CLT24AER24 Air Conditioner

I have a Commercial Thermostat Totaline P/N 0441 that is blacked out and there are no batteries from what I've seen in taking it apart. What can be the problem? Second, I changed the filters but it still shows on the thermostat to change filter. How do you reset that?


... Air Conditioners

The Coleman Mach thermostat in my 5th wheel blows its 2 A fuse a couple of times today and am trying to figure out what is causing this. Please help. I am unable to get the furnace to run even with a good fuse in the thermoatat. When I bypass the thermostat to run the Atwood furnace (red tied to white wire). THe furnace blower comes on and the burner sounds it lights for 5 seconds and then goes out. 15-20 seconds later it reignites and goes out and continues to cycle -- the blower motor


Hi\015\012\015\012Its blowing fuses because of short circuit inside the coleman mach or due to two wires being shorted with each other. You'll need to open up your thermostat system to look for the short circuit and also shorted wires.Ple ... Air Conditioners

Thermostat I have a RV with a coleman unit, unit run fine, but the thermostat blows the 2.5 amp fuse, I change to a 5. amp and it still blow the fuse, it will run for two day some time a week before it blows it out. What can I do.


Several things cause fuses to go. But you ace in the hole is that it works for sometime before it goes out. This suggests that a relay or contactor is not pulling in as it should. I would try replacing the fan relay (if so equipped) and definitely th ... Coleman Mach III Air Conditioner

Thermostat reading My thermostat automatically changed to celsius and I need to change it back to fahrenheit. Please help!


Push up and down at the same time ... Air Conditioners

Ruud thermostat message on digital ruud thermostat says battery power. AC not working. Changed two double A batteries but still not working.


... Air Conditioners

Thermostat problems I have a thermostat 9600 Robertshaw and I have to use the trip switch to start my furnace. Then it reaches the temperature and sometimes it will kick in by itself but majority of the time I have to trip it. I have changed the batteries cleaned the thermostat,and reset it. Is it time for a new thermostat and can I replace it myself. Thanks


Have you confirmed that the thermostat is programmed correctly?Did the thermostat ever control the temperature of the house properly?When you indicate "kick", are you talking about flipping the Auto-On switch back and forth? T ... Air Conditioners

This is a central air conditioning question. I have no power to the "battery-less" thermostat. I have two thermostats in the main house and swapped them out to see if one of the thermostats is bad, but both thermostats are working. There's just no power to the terminal in the living room. I checked the 5amp fuse to the air handler, and it's good. I checked the A/C unit outside and pressed down the contactor, the a/c kicks on. What am I missing?


Are you getting 24 volts from the thermostat to the transformer in the air handler? Sounds like the transformer in the airhandler. You can check it by taking the voltage from the R termianal to C Terminal and should read 24 volts. ... Air Conditioners

I have a comfort control 2200 thermostat. I changed the batteries and the thermostat is set to 80 degrees. The air conditioner stays on and the temperature on the thermostat is stuck at 80 degrees but the house temperature is down to 75 degrees and the air conditioner will not shut off unless I turn the thermostat setting to 81 degrees.


May be the location of the thermostat. Try another thermometer right beside wall thermostat & see what it reads. ... Dometic Rooftop RV Air Conditioner

Cant find where to change the batteries in the remote... There is no obvious place to put them unless we try to bust it open. Help!


Heya Harvey,On the panasonic remotes the batteries are under the slide down part of your remote. Where you slide the face down to expose more buttons keep sliding it down abit more and you should find two aa batts. If this dos ... Air Conditioners

Haier, Model # HWR 12XC5 Started making a noise, smelt electrical wire burning smell then it stopped running. opened electrical box on AC did not see any sign of smoke but fuse was blown, changed fuse turned it on, it started running saw a flash it blew fuse again. can you help! Brian


Hi, whenever a Fuse Blows, one should NEVER simply replace it, without first trying to find out why it blew, Fuses DO NOT spontaneously fail EVER.\015\012\015\012With a problem like this one MUST call an electrician or a Air Conditioner enginee ... Haier Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific