My fan on my heat pump turns off every time the compressor turns on. What could cause this. Could it be a faulty reversing valve? Fan relays? Bad thermostat? I am out of ideas and nothing has worked yet.


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

My fan on my heat pump turns off every time the compressor turns on. What could cause this. Could it be a faulty reversing valve? Fan relays? Bad thermostat? I am out of ideas and nothing has worked yet.


... Amana PTH123B35AE Air Conditioner

A Nordyne air handler, model B3BV-030K, with 4 wire thermostat. Thermostat and AC works fine in "cool". Switch it to "heat" and nothing happens.No fan, no heat.(I have built in heat strips -resistors). I jumpered (on the nordyne circuit board-input from thermostat) from R to W. (24 volts from R to W, which should start the heater. Nothing. No relay "click" like when AC comes on. If i jumper R to Y, AC comes on ok. Does this sound like a relay gone bad on the circuit board? Or what? If relay bad,


Do you get heat when you jumper R, G & W? ... Ruud Central System Air Conditioner

Intermittently my gas furnace fan doesn't shut off,so it blows cold air.If you turn down the thermostat until you hear it click,then wait until the fan stops,you can then turn the thermostat back up. And it works again for awhile. so far We have replaced the flame sensor,the thermostat,and now the circuit board. Any Ideas??? The model no.is GNE 075B12A1 seriel no L9840 79850


Look inside the unit where the fan switch is located and flip it in the other position. this is a fan switcch! ... Ruud Central System Air Conditioner

HONEYWELL RTH230B thermostat: we just installed the honeywell rth230b. The fan is working, but it's not turning on the outside unit. We pressed down on the thermostat slightly and it triggered the outside unit on for a split second, but it wouldn't stay on. After reading one of your forums, we disabled the blue wire, and made sure red, green, and white were in correctly. (we don't have yellow). Any ideas? The fan and vents are blowing cool air, but the house is 83 degrees and climbing (because t


Hello,what you have to do now from here is that check the capacitor if the maize i.e (wire)_ that pass current over to the compressor is well fix because this well the unit get is own supply to the over load then the relay sec ... Air Conditioners

I have a Trane XE 1100 Heat Pump. It is not cooling. My air handler blower works. The outside fan does not. I changed out both capacitors. When you turn unit on you can hear the relay activate. Then only a hum. Is the fan motor bad or the relay? How do i test? The light on the module blinks once a second which is normal operation. Thanks


Probablly the fan. Do this test. Move the fan side to side. and up and down. Any more than 1000ths inch play and that motor is bad. When the bearing gets thin the rotor will rub the stator and lock up. This is called polling out. If the motor is stif ... Air Conditioners

I have a Coleman Evcon Air Conditioning Unit....for the FAU ...I have to remove both front panels and manually have to turn the fan to get the unit working...my question is....would this be some kind of problem with the relay between the thermostat and the FAU ? when I spin the fan blades by hand...it doesnt seem like it is rubbing...I have never experienced this problem...can somebody please help me??? I would truly appreciate it ! :)


Hi,\015\012\015\012As you rotate the fan blade it start workin.This is not a realy or thermotat problem.The problem is with the motor of the fan.Replace the motor and it will work fine \015\012\015\012Thank You ... Air Conditioners

Duo Therm 58935.602 Will not turn on with thermostat, but when wires are crossed at unit, both compressor and fan work fine and unit works, replaced 2 relays and transformerd


... Dometic Rooftop RV Air Conditioner

Coleman mobile home furnace Model #7966-756 will not turn on. The pilot light is lit, there is power coming to the step-down transformer inside the furnace. The reset switch is in the right position. It worked fine when i turned it off last spring, just wont start back up now. The blower fan will not even come on when i switch it from the auto position to the on position on the thermostat. Any ideas?


I had a similier problem, Check your neutral ground? also alot of power companies will come out and do a basic check of the voltages going to the furnace, and can offer advice for free. ... Coleman Air Conditioners

Goodman GSH130301AB heat pump with Braeburn 1200 multi-stage thermostat - both less than 1 year old and installed in new construction. Heat can be set at 60, fan on AUTO, with room temp at 70 and heat will kick on and stay on. When this happens, turning thermostat to OFF does nothing - system continues to blow heat - and I can only shut it off by flipping the breaker. This only happens now and then - typically works fine. All wiring appears to be correct though reversing valve for cooling is


The reversing valve wire needs to be on the o terminal.nothing will be on the b terminal on the thermostat ... Goodman Air Conditioners

Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you ... Amana PTH123B25AJ Heat Pump Air Conditioner

The ac runs and does not stop. the thermostat will turn the ac off but the temperture setting doesnt work. I have already replace the thermostat. Is there some other type of relay on the unit that may have went bad?


Was it doing this before you changed the Tstat? ... Dometic Rooftop RV Air Conditioner

I have the Nano Max cfi 14000e. Worked good for 5 years 3 months. When turned on seems as if compressor comes in, fan goes high and compressor kicking out and fan back to low. No signs of any fluid leaks, is this a staarter relay type problem, bad compressor.


... Amcor 14000 Portable Air Conditioner

We had a Honeywell 5220D installed by a HVAC company in April. Now my AC runs fine during the day and at night about 10PM the inside fan continues to run the thermostat is not yet at temp and the outside compressor fan does not run until the sun comes up. I have checked to see if it was in economy mode and it is not. The temp inside will warmup 6-8 degrees buy morning and the unit will come back on some time after we have gone to work. any ideas? Thanks Gary [email protected]


Make sure the temper differ in cool mode are set 40-90 this is also a programable feature of this t-stat , by the way it also has offsets in the heat mode you might want to check this as well and make sure they are set check all wire connections for ... Honeywell Air Conditioners

AC, Fan-Auto, Fan-On... nothing works. the request from the Thermostat doesn't engage anything. Thermostat Dispay works. How do I know if it is getting the 24volts from the relay? I presume the display wouldn't work if the 24v from relay wasn't there. I have two separate systems in the house. So therefore, I pulled the thermostat off the base and tried it on the faulty system. No luck. Still same issue. Perhaps it's the Honeywell base itself? what electronics are in there that could fail? How ca


Open the air handler. Locate the low voltage transformer. One side is 220 volts input. The other is 24 volts output. Take your VOM and touch the test leads to the input to verify 220v in. Then touch the other 2 leads to verify 24v out.If you ha ... Honeywell Air Conditioners

Turned AC thermostat to Cool today - AC didn't come on. The last time we used AC (March 2009) it worked fine. I can hear the AC Relay Board, inside the trailer, click when switching from Cool/Off & Off/Cool. Any ideas? Thanks.


Just clicking is all your getting from ceiling assembly? No other modes work such as fan, or furnace? If that's the case, check your circuit breakers to make sure it didn't trip. ... Dometic Rooftop RV Air Conditioner

I have installed a UPM model THM101B thermostat on my Intertherm model E3EB-015H electric furnace. I wanted the feature of turning the blower "ON" without the heating elements. I picked up the green 12v for the fan relay. Once the power is restored the furnace comes on even though the temp setting is low and the only way I can turn the furnace off is by disconnecting the green fan relay wire? The jumper has been properly set in the new thermostat for electric furnace operation.Right now I feel t


... Intertherm Air Conditioners

Turned on the a/c for the first time this year and no fan. The compressor turns on but no fan. The fan works when turned to heat and t-stat cranked up. This is a BDP CO. 2085C02135. Is there a relay or limit switch that only works with cool?


Depending on the thermostat you have, there may be an issue there. Some stats have a subbase that controls the fan for AC. I would like to know the model of your stat ... Air Conditioners

My central heating unit in house will not turn off. Thermostat sends signal when temp is reached but heat and fan keep running, I changed fan relay but no change, have to turn off breaker to get if to go off, when breaker is turned back on it is off as long as thermostat is at temp


Definately a relay - but i suspect inside the controller itself.Replace the thermostat(controller) unit.Thanks for using FixYA!! ... Air Conditioners

Hi i recently purchased a used convair portable supacool 9 air conditioner the first time i switched it on it appeared to work ok but the next time i turned it on it is working on normal fan mode but when i turn it to air conditioner mode it is doing exactly the same as on normal fan mode the compressor does not appear to be working and is not making the extra noise that it was the first time i have tryed all the switchs including the thermostat but there is only a very simple to use set up any


... Convair Portable Air Conditioner

I have a Goodman Split Air Conditioner and the outside condenser fan was not working. relay tested ok breaker wasnt tripped, then discovered 1 leg of the 220 line was out. Replaced the breaker, cleaned the unit turned it on, cooled the house 2 degrees then it stopped working. Turned the stat off ,pulled the 220 block waited 10 minutes, turned it back on and it is currently running. Can the relay and/or start-run cap behave in this kind of intermitent way ?


Run cap may be badthumbs up ... Air Conditioners

I have a goodman gsc13 ac unit about 4 year old. When the temp gets around 90 or above outside the fan on the unit starts but the compressor does not. I had service check it out but that day they were here it was in the 80's and it worked fine. I replace the thermostat to make sure that wasn't the problem. Interesting if I turn the unit off at the thermostat and wait 15 minutes and turn it back on it will run fine. But the next time it tries to turn on automaitcally it will just be the fan o


The hum you hear is the 24v transformer which is powered form the air handler inside have you tried a hard start kit or had cap checked ... Air Conditioners

Changing from Intertherm thermostat to a Honeywell Thermostat. My sequence relay wont work. the wire is on the A/C fan blower side. How do you get the relay to work?


... Intertherm Air Conditioners

The fan on my central ac will not turn off when I turn off the thermostat - keeps running. I think it is the fan relay possibly? Model is 38CK048 - does anyone know the relay part # and repair manual


Did you change the stat ? try that first ... Carrier 38CKC042 Air Conditioner

Compressor does not run. On turning the AC on, the compressor does not run. The blower fan does though. Checking the relay panel, the relay for the compressor does not engerize. a temporary solution is to put a switch across the contacts the compressor on and then the thermostate is set so that the AC should work, the fan comes on and the unit works as usual. The only exception is that the temperature must be controlled manually.


Hi, if you are energizing the contacts on the contactor, and the compressor runs, the thermostat is faulty. This is what energizes the contactor coil that you have. You need to check to see if you have voltage to the coil on the contactor. You need t ... Coleman Mach 15 Air Conditioner

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners