Having problems with your Air Conditioners ?

I just got a new honeywell thermostat and it when i first hooked it up it wouldnt turn on so i check to find out which connections on the thermostat when open i changed my wire to make it correct now when it turns on it doesnt turn off. i only have 2 wire that were on the old thermostat and the new one shows spots for 3 wire do i need to run a 3rd wire to get the furnace to shut off after it reaches desired temp? right now i have to disconnect the thermostatto shut it off.?


Answers :

Hello my name is Heath it will be my pleasure to assit you. If you did not turn the power off to the furnace before rerplacing the thermostat then you may have burned out the board in the furnace. But first if there is a RH/Rc terminal in the new thermostat then try removing the jumper between the two and see if the thermostat will operate properly.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I just got a new honeywell thermostat and it when i first hooked it up it wouldnt turn on so i check to find out which connections on the thermostat when open i changed my wire to make it correct now when it turns on it doesnt turn off. i only have 2 wire that were on the old thermostat and the new one shows spots for 3 wire do i need to run a 3rd wire to get the furnace to shut off after it reaches desired temp? right now i have to disconnect the thermostatto shut it off.?


Hello my name is Heath it will be my pleasure to assit you. If you did not turn the power off to the furnace before rerplacing the thermostat then you may have burned out the board in the furnace. But first if there is a RH/Rc terminal in the new the ... Honeywell Air Conditioners

Hi i have a white rodgers thermostat model 1f58w-58. And I need help! We tried to change the thermostat to a new one, but for some reason the ac would not turn on. So we put the old one (white rodgers) and put all the wires back how they were and it still won't turn on! is there a fuse or something?


... Air Conditioners

Goodman GSH130301AB heat pump with Braeburn 1200 multi-stage thermostat - both less than 1 year old and installed in new construction. Heat can be set at 60, fan on AUTO, with room temp at 70 and heat will kick on and stay on. When this happens, turning thermostat to OFF does nothing - system continues to blow heat - and I can only shut it off by flipping the breaker. This only happens now and then - typically works fine. All wiring appears to be correct though reversing valve for cooling is


The reversing valve wire needs to be on the o terminal.nothing will be on the b terminal on the thermostat ... Goodman Air Conditioners

I was installing a new thermostat and in the process lost power to the thermostat. I crossed the red and green wires and the fan didn't turn on. I check the outside compressor and inside air handler and found no 5 amp fuse. Does it have one or did i short out the transformer in the air handler and need to replace it?


You can ck the low side of the transformer to see if you are getting 24v with a mutimeter. If you are then look on the cicuit board for a fuse. It would look like a fuse you would find under thr hood of your car. flat with two probes. Purple or pin ... Air Conditioners

The blower in my Ruud gas furnace won't shut off. It just runs and runs. The thermostat is set to "off" and the fan switch is set to "auto". We haven't used the furnace or AC the past few months since we haven't needed it, so it's been in the off position. Then yesterday out of nowhere the blower randomly fired up and hasn't turned off since. It just runs and runs until I kill it at the breaker. The thermostat is about two years old so it's fairly new. I replaced its batteries and that didn't


I'm not sure what setup your unit has but the fan relay sound like it is bad. If your blower connects to a circuit board then the board could be bad. Different units use different ways to control the fan. Some use a relay like I mentioned. Some use t ... Ruud UAKA037 Air Conditioner

I have a Janitrol Heat Pump Thermostat HPT-18-60 and need assistance connecting my new Honeywell RTH7500D thermostat I have a Goodman Heat Pump System Indoor Unit Model#AWB24-05C REV D Outdoor Unit Model#CPLE18-1 Here is the wiring of the old thermostat Y-Yellow Wire G-Green Wire R-Red Wire O-Orange Wire W2-White Wire E-Blue Wire C-Black Wire Where should each of these be connected to the new thermostats terminals?


... Air Conditioners

My thermastate went out and i cant hook up the new one because it is not labled, and i need to know how i figure out what wires need to go to with letters (o/b, y, r, g, w). There is a plug with 10 wires ( there are colored ) that goes from the a/c unit to the thermostate, and seperate red and wite wires going to the thermostate. Also there was 12v power going to the other thermostat. The only thing the new thermostat has for hookups is o/b, y, r, g, w. can you help


Let me guess, you have a flat ribbon type harness coming from AC unit to thermostat, correct?Older Ac unit? What thermostat model came off, and what type are you trying to install? ... Dometic Rooftop RV Air Conditioner

I have a Carrier Gas Furnace Model # 395CAV024055ABJA, I works fine if you keep the temp low, like 68, so that it doesnt come on very often, but if you try turning it up and it needs to run for awhile, it wil start this cycle where the flame will kick on and off, the blower is continously running and only blowing cold air, I have tried new batteries in the thermostat on the wall, and have tried putting it on manual heat, no change, another thing is that once it starts this cycle, if you shut it


It sounds like it is going into overheat mode. Check the overheat sensor, make sure the flue is clean, make sure any filters are clean, also check the gas passage inthe heat exchanger, if there is a blockage from soot the system will overheat ... Carrier Air Conditioners

Purchased a dometic duotherm a/c for rv partially installed it, but conected all the correct wires and it will not turn on. All new unit with new thermostat and control box. the Thermostat requires 7.5v dc to function but the control box is not producing the voltage. None can be detected on the terminals of the thermostat. there are two wires for an solar/filter indicator that should have +12v and a -12v. neither have any voltage present. tried to return the whole system to the vendor bu


Check all grounds,all grounds,I stress this because the system may need ground elsewhere to operate.If the control box is what produces the 12 volts dc,and the 7.5 volts dc,and you have power to the box,then the box(converter)is bad.Is this unit 120v ... Dometic Rooftop RV Air Conditioner

Thermostat Labeling of wires to follow the new Thermostat routing missing. Wires all unlabeled. Cant afford to pay I need a schematic of how to identify wires coming out of wall and how to connect to new thermo.....


... Honeywell Ct31a Heating & Cooling House Thermostat Heat Pump Great Sale

First, my thermostat wouldn't shut off either my heat pump or my furnace (it runs both). Thought it was an issue with the thermostat...got a new one. Worked like a charm for 1 day. Now, there is a clicking noise coming from the heat pump - it did it at first when trying to turn it on....now, when it's warmer, it will turn on, then start to do it. Doesn't seem to be putting out hot air now. Any ideas? The thermostat came with a new box that sits inside the ceiling and it's been replaced, bu


Sounds like your unit may be tripping on a pressure switch due to low refrigerant or a dirty outdoor coil. You may be able to look through the cover with a flash light to see if the inside of the outdoor coil is stopped up. Otherwise, you will have ... Dometic Rooftop RV Air Conditioner

Wiring compressor Replaced defective fan motor on my a/c unit. Old motor had three wires: black, yellow, brown. New generic motor has black, white, brown, brown w/white stripe. This new motor came with a new two terminal capacitor. Old cap. had three terminals. The black and white wires from motor connect across the line voltage and the other two wires connect across the capacitor. After install and trying to run the unit, found that compressor turns on for about two seconds and shuts down, but


The two terminal cap is only for the new fan motor. Connect the compressor wire back where you found it, on the 3 terminal cap. It's the terminal marked, "herm". The "common" terminal on the 3 terminal cap must still be connected to one side of the ... Carrier 38CKC036 Air Conditioner

OK I am a dumb A--. I did not turn the power off to my Payne PG9MAA Condensing Gas Furnace. Also A/C. In my futile attempt at relocating the thermostat. I 1. did not turn off the unit 2. I did not have enough wire so I spliced in a new longer one. 3. Voila' there is absolutely nothing on the thermostat showing power. I used the voltage regulator and put the contacts one on red and the other I went in sequence to all the other wires and it read 11.00 or so volts.. If I changed the (lead) or


Depends if its a 12 volt or 24 volt system and if your meter is reading right also check meter then check red wire if its a 12 volt thats what you should have and 24 so on or you have a dead short good luck with that one just be calm a go thru all t ... Air Conditioners

My thermostat inside my house will not shut off, runs constantly now, on both a/c and heat cycles. Does the thermostat need to be replaced?I have central air and heat. Recently tried to shut off the heater one morning , had warmed up outside and was too warm in house. I could not get the heater to shut off even manually. finally tried turning on the a/c, it came on but it would not shut off later when it reached temperature set even when I manually tried to shut it off. My outside unit (a/c) is


Hello\015\012IF this is a programable stat.Take the batteries out and replace them.\015\012Then reprogram the stat.\015\012\015\012IF this is not programable have the wiring checked at the unit and the stat.May need to replac ... Air Conditioners

I just installed a P474-1100REC & P474-1100RF in place of a Honeywell Thermostat.I have a typical 4 wire 1 stage Cool 1 stage gas heat setup. The new thermostat is not working right. I noticed on the old thermostat there was a jumper wire from R to R1. Do I need a jumper wire set-up here as well? If I do where do I connect to? There is no R1. Please help


Does the new stat have a rc and an rh if so you will need a jumper between them ... Air Conditioners

Our fan for the intertherm p3ra-024k will not shut off. We have put new wiring from thermostat to unit. He pulled the green wire like the serviceman told him to when he serviced it and it still keeps running. The only way it will shut off if you shut the power off to it. Any Suggestions?


You have a problem with the wiring somewhere it could be in the thermostat. When the service man said pull the green wire off that was the power to the fan. The thermostat should wire up as red to the R terminal on the thermostat this is the 24 vol ... Intertherm P3RA-024K Air Conditioner

Ihave an Intermatic mechanical timer model T104 that runs pool filter equipment. Had problems with the old timer and replaced it with a new timer - wired it exactly like the old timer - one wire at time so I was sure not to mix any wires. Turned it on and everything worked - set the off tripper and waited about 25 mins for it to shut off and it worked great. Set the timer for the on and off and it came on ok but didn't shut off. Have re set it and in came on and I was watching it when it was


Hi,\015\012No there is no difference in the T104 and the T104M the m just stands for mechanism only...\015\012\015\012So it would seems vey unlike ly that both poles would fail... so it seems that the internal part that moves the co ... Air Conditioners

I installed a new Honeywell Programable thermostat, When I turned on the AC it turned on the Heater... I followed the wiring but some of it is not making sense... G=Green, Y=Yellow, R=Red, C=Blue, W2=White, Y2=Brown... The problem is that I have an Orange and Black Wire left over, Which one do I connect to W? and do I have the wiring right... my unit is a central Heat & Air, not a heat pump.


Hi, the problem is you have bought the wrong thermostat for the unit if it is not a heat-pump. A heat pump will have W-1, W-2 for heat strips, and Y-2 is for 2nd stage cooling. G is Green for Fan, R is Red for Power, Y is Yellow for cooling, and W wo ... Goodman Air Conditioners

I HAVE A CARRIER 7DAY PROGRAMMABLE THERMOSTATS, NICOR INSTALLED IT . IT HAS 4 WIRES GOING TO THE BLOWER white,blue/yellow,green and red.there is a spot for the blue wire but it was put in the yellow spot. do i need to change it to the right spot or leave it as is


... Carrier TSTATHCP Programmable Thermostat Air Conditioner

Model FC24B3XN1H. Modulating Echelon 60k btu. Fan runs constantly but no heat. Was installed 9/09. When turn thermostat off, fan still runs, have to shut off at furnace. It has never been a hot heat, installer said that is normal?? Used air couple days this week, was fine. We then turned furn off at thermostat as it was not needed. Turned heat on late yesterday afternoon & problem started. Left furn power off for about 15 minutes, but would not reset. Easy solve?? Is it supposed to be a 'cool' h


Hi,The fan running constant and the unit not firing is usually an indication that the high limit reset has tripped. And yes... these furnaces will run a cooler air... that is one way they get better efficiency...Also the ... Coleman Air Conditioners

I just moved into a new place and it has the RTH230B thermostat installed. I turned on the furnace, set the thermostat to "Heat" then the fan to "Auto" and used the up and down arrows to set the temp to 72 degrees. The temperature seemed fine for the first hour or so. However, the heat and fan stays on full power and continued to heat at full power well into 80 degrees on the thermostat screen. I could only shut it off by turning off the actual furnace switch. I first tried reducing the temper


From what you learned from your neighbor, I would say no. Certainly, sounds like a manufacturing defect to me. ... Air Conditioners

I need to find a wiring schematic for a honeywell CT31 Thermostat. I'm trying to run a solar colector through a goldline GL30 controler. my unit needs to open for the run of the fan and close on temperature rise to shut down, however I've tried several different wiring schemes to no avail. thanks for your help


... Honeywell Air Conditioners

Reset button for Ruud Achiever 14 heat pump/AC compressor? My Ac/heat thermostat was blowing fan on and would not turn off. I switched it off at the circuit box, and bought a new thermostat RTH221, wired it and it would not blow cool air when on cool nor warm air when on heat. Called the 800 number for Honeywell and tech said I had wired it correctly, to check outside and see if the compressor was running. It was not. This Ruud unit is only 8years old so I'm wondering if a reset button has


... Air Conditioners

I have an intertherm rpbmb030k combo a/c and heat. Had frion put in the unit over the summer and a new digital thermostat. Unit has worked great until we needed heat. Unit works great on aux. heat but keeps switching to to defrost mode when standard heat is on. Switched out the defrost board on the unit to no avail and an a/c guy checked to ensure the new thermostat was wired correctly.


Hi, if the unit had a leak in it, was the leak located and repaired? Did he check the pressures in the unit now? If it switches to the aux mode ( Heat Strips ) is normally caused when your primary unit, compressor and freon are low on charge. I would ... Intertherm P3RA-060K Air Conditioner

I've replaced my very old (mercury) Honeywell thermostat with a new one (round, Model: YCT87K1011), but I can't get it to control the temperature. If I connect the two wires one way, the furnace comes on but won't shut off. If I reverse the wires, the furnace doesn't come on at all. I've actually tried two of these replacement thermostats with the same results. Any suggestions? John


Hey John, man that ole T87 has been around for a hundred years and I have installed many of them, but I cant remember the letters on the wiring. Seems to me that it is R-W-Y, any way you will use the R and W. I have a t87 at home still in the box an ... Honeywell Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific