Having problems with your Air Conditioners ?

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


... Air Conditioners

I have a Haier HPRBO7XC7 portable air conditioner that isn't working properly. When I turn the air conditioning mode on, the cooling unit seems to turn on, but then stops after about a minute or so, and the fan just keeps running. The unit is only about a year old. I purchased it last summer, it worked fine and then when I pulled it out the other day, it had this problem. Any suggestions?


... Haier Air Conditioners

I have an Edgestar Portable Air Conditioner AP12000HS. The Air Conditioner works wonderful, however I can't get it to heat, I put the Mode Button on red which is supossed to put the heater on, it will run for a few minutes and then shut off and it does not take the chill out of the room I have the unit in, is there some kind if thermostat internally which can be set? The way it runs now does not do me any good as a heater.


The unit has a built in thermostat in the front control panel, this is what maintains the set temperature, it is very likely that this control is defective, all the controls for the unit are contained in the CCU (central control unit) ... Air Conditioners

Hello i have a toyotomi air condition TIN 288 (R-22).At heat mode when the pump start working it stops after 1 minute and the operation led (green)and heat mode led(orange)flashing.Could you help me because i have lost the manual?Thank you


... Toyotomi TIN/TIG-329D Air Conditioner

I have a DeLonghi CF210 and I'm getting the "E3 Fault" code on the main screen. It will not power up in Air Conditioning mode, but the fan mode will run. I saw where someone suggested it is a voltage problem, and have tried it in several outlets to no avail. This problem happened to me about a week ago and I turned it off for a while (10-20 minutes), then turned it back on and it worked again for a week before giving me the E3 Fault error today. I do not have the financial resources to sen


Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power ... DeLonghi CF210 Portable Air Conditioner

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

I purchased the ARP 2412 Portable Air Conditioner unit, and I find myself very unsatisfied, cause no matter what function mode I select to cool the area, after only 30 minutes aprox, it turns off... (in all COOL, AUTO, DRY... etc.) I understand this function allows the saving of energy, but I understood it was an automatic function, and I would like to know if there's a way to make it work NON STOP... as it should. THANX, I would really appreciate your response.


... Royal Sovereign ARP2412 Air Conditioner

Hi I have an LG S 24AWN / N 56 split system type room air conditioner which when turned on in cooling mode runs for about a minute then stops working with the error code CH 5 flashing. Has anyone got any clues on this one please. Cheers Roy1


Have you cleaned the filter? Check the condensate drainpipe is not blocked by blowing into it from the outside. ... LG LSC183VMA Split System Air Conditioner

I have a Mistral Inverter Reverse Cycle Split System Air Conditioner. MSS.3INV. The trouble we are having is the cooling will work for half an hour or so and the compressor will turn off leaving only the fan going and the comporessor and timer light flashing. This hapens before the desired cooling temp is reached. You can switch the main power off to the unit and back on again after a few minutes have past and the unit will operate again in cooling mode and then just do the same thing. The gas


Hello,What this problem indicate is that the thermostat of the air condition has been gone bad.When ever an refrigerator does such it simply mean that thermostat need to be replace by some time it could be on the time progra ... Sanyo 24KS32A Cool Mini Split Air Conditioner

My goodman unit is Blowing cold air when in Heat mode, I called the heating & cooling man and he came out and in ten minutes he got the heat working but he just disconected one of the Black wires from the Reversing Valve from the defrost board.


... Air Conditioners

Hi i recently purchased a used convair portable supacool 9 air conditioner the first time i switched it on it appeared to work ok but the next time i turned it on it is working on normal fan mode but when i turn it to air conditioner mode it is doing exactly the same as on normal fan mode the compressor does not appear to be working and is not making the extra noise that it was the first time i have tryed all the switchs including the thermostat but there is only a very simple to use set up any


... Convair Portable Air Conditioner

Air conditioner does not work on cool mode. Dry mode works but compressor turns off and leaves the room with no air circulation. What can we do to get the cool mode to work again?


... Goldstar R1203 Air Conditioner

Lg Neo plasma inverter split model s18ahn isn't heating or cooling properly. When in heating mode air con will go into defrost/preheat mode for 5 minutes and then air con will blow out air for 5 seconds and then go back into defrost/preheat mode. When in cooling mode indoor fan will pump out air but will not get cold. In both heating and cooling modes the outdoor unit will not start up and the outdoor fan will not spin. I have just replaced the main pcb board and that hasnt made a difference. Bo


... Air Conditioners

My air conditioner stops cooling. Occasionally, it will just function on fan mode even though I confirm that it is on cool mode. Warm air comes out even on the absolute coldest setting. I have to turn it off and use the manual reset button on the plug to get it to work properly. The problem started after the unit iced up one night and it hasn't worked right since. Is there any way to fix this or am I gonna have to get a new AC?


If after reset the A/C cools then the fault seems related to the thermostat or the cut off pressure switch or load cut off.\012However is there is no cooling at all the compressor and the gas pressure- check for leak if gas is absent.- must be ... LG ZW6500R Air Conditioner

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan


The LG>LW5200ER AC is not listed as a heat providing unit. Click on link and this will give you the spec's\015\012\015\012 \015\012\015\012 ... LG LW5200ER Air Conditioner

The PAC-260 runs for a few minutes, then I hear the compressor stop and it spews hot air. Pressing the reset button fixes the issue only to have it be reset again after a few minutes. Air filter is fine, the tubes are setup properly (ie. it is a straight run up and into the window). What am I missing, the reset button is supposed to be used when I figure out what is wrong, but I know it works (sort of) because when it works it still is very cold.


I had exactly the same problem. After some diagnosis I discovered that the water pump was not engaging so I checked the float switch, it was fine. \012\012A press of the red reset button turned the compressor back on for a few minutes but the ... DeLonghi Pinguino PAC-260 Air Conditioner

Cold air not coming out. I JUST bought this the other day and it worked the first day just fine but now it will work fine for about 10 minutes and then the cold air will stop coming out. Air will continue to come out but not cold air. It is summer in New York so help please. PLEASE. Thanks in advance. This is a Haier ESA306 window unit.


Need to return this one where you got it. Sounds like compreesor or control problem. Do check outlet voltage to make sure it is not a low voltage problem first. Voltage should not drop below 10% of name plate voltage required. Voltage should be check ... Haier ESA306 Air Conditioner

Window air conditioner keeps switching to fan mode. Which means on hot days it is blowing warm air. It sporadically switches to air conditioner mode. Room is hot because the cool air only blows for about 10 minutes. Help!


... Air Conditioners

Hi guys, i have a portable air conditioner 9000btu 'ariagel ag90' window) that works great for the first 5 minutes, until gradually the unit makes more and more noise until it shudders quite violently , returns to its normal noise and blows out hot air for 5 minutes. This hot air seems enough to cancel out the cooling it does. then after a while it cools gradually I've read alot about this air con problem, but nothing regarding the gradual noise and shudder. The slide out filter at the back s


This is due to the compressor going into thermal overload, It can be cause by really dirty coils preventing air flow,A restriction in the cap tubes or orafice, Or an over or under charge in the system.The noise is due to the compressor building up to ... Air Conditioners

My air conditioner delivers cold air only in spurts. It then goes into fan mode for a few minutes, then to cold air in a few more minutes. It is over 100 degrees outside and the inside of the house is 85 or so. I have the temperature set at 74 degrees. Why does the cold air not pump out consistantly?


Hi,The\012 unit is probably low on freon and so it is running too cold....this \012trips the freeze stat and shuts down the compressor till it warms up The unit will \012need to be recharged or replaced...\012Here is a t ... Fedders AED24E7F Wall/Window Air Conditioner

Amana air command 80 SSE started makeing humming sound id shut it off and wait a few minutes and it would work again been doing this for about a week and now its not working what so ever it was blowing cold air but when humming it wasnt blowing anything at all i checked to see if the fans were binding up but their spining freely any ideas i see a sensor light but i dont know how that works either. please help im melting thanks


Sounds as if the motor is heating up and shorting.Call a pro to find out for sure. ... Air Conditioners

I have a Noma/ DeLonghi portable air conditioner. 3 Modes-fan-dehumidify-air conditioner.When I try the Dehumidify or air conditioner mode the mchine strains to start up and then blows a fuse. Fan still works fine.Tia


Compressor is not starting, it could be a bad or shorted run capacitor, start capacitor and relay, low voltage, loose or disconnected wire or a shorted compressor. ... Air Conditioners

We have a Fujitsu ASY-40UIM3 air conditioner here in Spain. We had to move the outdoor unit yesterday and since then we cannot get it to work. We are looking for error codes to help locate where the problem lies. The red light on start up goes off and we have a flashing green light (timer maybe?) that continues to flash at regular intervals. This outside unit was moved by a qualified engineer and the air-con worked perfectly up until the move. We cannot get heat or cold air.


There are two things that can cause this.\015\0121. Is the high voltage line energized. Is the power coming to the unit, make sure the disconnect is not tripped or manually shut off or pulled out and reversed. Check that the circuit breaker ... Air Conditioners

My air conditioner has started leaking and has very poor air flow. It worked fine in winter but when I switched it to cool water is coming out of it. Sometimes the fan will work (no cold air) for about 20 minutes before it starts to leak, other times it leaks straight away. Any help appreciated.


This sounds like an air restriction inside the evaporator probably caused by a dirty filter or dirty evaporator coil. ... Air Conditioners

We own this air conditioner and it is one year old. It is working find, however, when running in the air conditioning mode it omits a musty oder. Where I am allergic to mold , I am concerned especially since I keep getting a headache and stuffiness when it's running. We have run it for hours in the fan mode in the hope to alleviate any moisture in the unit, but the smell is still there. The unit also has a charcoal filter, but I don't know where I can buy them. Any suggestions you can prov


The problem is common. It is not a mold spore situation, rather it is a moisture laden problem of parts and dust that create an oder when allowed to warm and stay moist. A spray bottle with 1/2 clorine bleach and 1/2 water sprayed onto the inner com ... Amcor AF9000E Portable Air Conditioner