GOODMAN AIR HANDLER MODEL CA*F4961*6A*+MBE2000**-1 HAS HEAVY CONDENSATION IN THE TOP OF THE UNIT WHERE THE ELECTRICAL /CIRCUIT BOARD IS LOCATED.THE UNIT IS LESS THAN ONE WEEK OLD. THE COMPANY THAT INSTALLED IT HAS CHANGED THE DIP SWITCH SETTINGS AND TODAY PUT IN LARGER COLD AIR RETURN DUCTS.STILL IS THE SAME.ALSO THE COILS UNDERNEATH HAVE HEAVY CONDENSATION ON THE BOTTOM OF THEM.WHY CANT THEY FIX THIS ONE WEEK OLD UNIT.THE OUTSIDE MODEL# IS SSZ140601A*THE HOUSE IS 2480 SQ FT. THE OUTSIDE UNIT IS


Answers :

This is not even a repair issue.If it is hot out and it's on quite a bit,there will be much condensation.However,condensation on a circuit board is never good.Since it is only 1 week old and you can see this serious of a potential problem,especially the possibility of fire because of the circuit board,I would consider a different a/c unit.If they have to rig it to try to prevent failure,I would not even consider that ethical.Is this unit you're having the problem with a window unit?I would contact them,look for a better designed unit,and have them re-install...BETTER BE FREE,VERY LOW COST IF ANY.If they refuse,get as bad as they do such as ,I will talk to my lawyer about who would be at fault if this catches fire,stuff like that.I hate do that kind of stuff,but I am the type of person where I give back what I get from a store.If they still refuse and you bought it with a credit card,call them.They are willing to do much more for consumers than most people realize.That's all I have to suggest.Good luck and please let me know how you make out.
You may check you manual if that design is matched with the diagram on it. If you feel that the settings were heavy just like the condensation on the bottom, you may refer to goodman and I believe you have a free service technician that can work to since it is only 1 week old. I am sure if you avail the 30-day money back guarantee on that company. But just to make things better on your part, if they cant fix this unit, you may refer to local handler who is an expert to this product. You may also ask other people if they have encountered this same problem...

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

GOODMAN AIR HANDLER MODEL CA*F4961*6A*+MBE2000**-1 HAS HEAVY CONDENSATION IN THE TOP OF THE UNIT WHERE THE ELECTRICAL /CIRCUIT BOARD IS LOCATED.THE UNIT IS LESS THAN ONE WEEK OLD. THE COMPANY THAT INSTALLED IT HAS CHANGED THE DIP SWITCH SETTINGS AND TODAY PUT IN LARGER COLD AIR RETURN DUCTS.STILL IS THE SAME.ALSO THE COILS UNDERNEATH HAVE HEAVY CONDENSATION ON THE BOTTOM OF THEM.WHY CANT THEY FIX THIS ONE WEEK OLD UNIT.THE OUTSIDE MODEL# IS SSZ140601A*THE HOUSE IS 2480 SQ FT. THE OUTSIDE UNIT IS


This is not even a repair issue.If it is hot out and it's on quite a bit,there will be much condensation.However,condensation on a circuit board is never good.Since it is only 1 week old and you can see this serious of a potential problem,especially ... Goodman Air Conditioners

My outside a/c condensing unit's fan runs, but inside vent air is not cold. compresser may not be running. inside vent air was cold last week. Janitrol ckj361ab is model # of outside unit.


Start the unit and go outside to see if the insulated pipe is sweating or cold, hot air should be discharging from top of outside unit. Since the breaker is not tripping, my best guess is the compressor is not operating. You might have to replace the ... Air Conditioners

Hello, my HVAC is constantly freezing, even after freon is added. I was told that I have a leak in the coils and need to chance the air handler - the outside unit is about 10 years old - air handler about 18 years old. I would like to get only the air handler for my R22 outside condensing unit. My question is if in the future can I use this same 3.5 ton air handler with a new 410 condensing unit once my outside unit needs to be replaced. In other words can a Goodman air handler be used firs


I'm new at this and I can't tell how old the post is but I'll contribute anyway.You probably have fixed the problem by now. I wonder what part of the system is freezing up. I don't have a lot of experience but I know you can get frost where there ... Goodman CKL42AR42 Air Conditioner

We installed a 4 ton downflow coleman air handler with evap coil Model number 1854s2m we did not change out the outside unit. the outside unit is a 13 year old 3 1/2 ton intertherm condenser the system is only generating a 10 degree delta T. My question is, this coil came with a factory TXV I am trying to find out is this a 10 seer or 13 seer coil is it compatable with the outside unit.


You have a missmatched system, for it to work try removing the orfice on the high side txv it is not allowing the evaperator coil to fill with refrigerant properly coleman and intertherm dont like each other since they control a large market in the ... Air Conditioners

Our ac is not blowing any air the vents are cool to the touch but no air. The fan is running and the outside unit is running. We took our old filter out and havent' put a new one in--it's been a week


Dirty indoor coil? ... Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

Outside unit will not turn on. Inside fan works fine. This intertherm unit is an upright, 6yrs old. Model number unkown. Fan will turn. No hum coming from unit. inside condenser sits on furnace model # E2EB-015Hb. Freon charging is outside on the lines coming from outside unit.


Hi! You may want to start on having the power supply checked. Good cause why the unit won't power up. Have the compressor checked too just to be sure. ... Intertherm Air Conditioners

We have a Rheem air conditioner that is 9 years old Model number RAKA 037-JAZ and have been having some issue with it. Last summer the condenser wasn't coming on so we have a friend who is a HVAC guy and he came over and cleaned it all out and then it worked great. At the beginning of this summer we started having the same issue, so we cleaned it out and it worked for a couple of weeks and then started to have problems again. One day, it ran all day and the temp stayed high when we went to look


It sounds like he got you a Hard Start Kit/Capacitor, that might explain\015\012the five minute delay. When the fan is not operating the compressor will\015\012make a loud noise..\015\012\015\012Check to make sure insulated su ... Air Conditioners

I have a central air conditioning unit in the apartment where I live. It is a split unit - somewhere outside is my outdoor unit (and everybody elses too). Anyway I seem to get way too much humidity in my apartment. The air conditioner I suspect is 15 or 20 years old or more. The label on the indoor part is almost unreadable. Carrier is the maker. The model might be 40AC02450052. There are also other numbers 40AC901190 ? or 40709010 ? Can anyone identify what I have? I would like to know how old


The humidity problem is from the condesation drain. It is more than likely to be clogged up keeping water in the condensation pan causing the humidity problem. This can be cured by a wet vac put onto the outside drain for the inside condensation pa ... Carrier 38CKC030 Air Conditioner

I have a colman evcon split unit, I had a guy replace the thermostat (old electronic, new mercury) and everthing worked fine. One week later out side unit stopped and was frosted over on the outside. I can push the contactors on the outside unit and got power. I traced wiring down to transformer. I replaced the transformer with one with a circutbraker built in. When i turn the brakers on the transformer curcuit breaker trips...I followed the wiring on the transformer to the best of my ability, h


Hi, you do have a dead short in the control side of the system. Good that you bought a transformer with the breaker. Most people don't and will smoke several of them. Anyway, it is a split system. If it was iced up, it must be a heat-pump, not gas fi ... Air Conditioners

I have two Amcor AmcorAire UCHW-H09AF2 Split System Air Conditioner units -- 2 years old. One works fine, but the other does not blow heated air (Heat Mode). It is cold outside, but the good unit is blowing heated air at the same time the bad one does not. All other settings are the same. All suggested service numbers, as well as the company number in user guide are disconnected. Thanks


... Amcor Aire UCHW-H09AF2 Split System Air Conditioner

What outside temperature can you not charge an air conditioner unit?when is it to cool outside to put r-22 in a condenser unit? sometimes i hear from techs that it to cool in outside temp. to charge a unit with freon,but no one has told me the range of temp.to which you can or cant service charge a unit.does anyone know the official answer?


If you need to charge a unit whe it is to cold. if you know how to un plug out dooor motor take wire off that well let head perssure go up . or you can cover up condenser that will work to good luck. ... Air Conditioners

My carrier A/C YHB243D this window unit was working find. But about one week ago only blows out cold air and sometimes only hot air but now it blows only regular air, and doesn't work nither the cool or heat air. what could be wrong with it?_a) could be- the thermostate that goest at it front with its condenser unit? b) could be the whole temperature switch ? or what else can be its problem, please help! and tell me where I can get the replacement part


... Carrier Air Conditioners

I have a Goodman Furnace model#GDS80703AXBC.The unit is one year old and ran fine until the gas got shut off accidently outside at the meter.Unit was cycling with no gas for 2 days.we turned the gas back on and the unit is showing one light blinking for over cycle trys.The unit did eventually start up but it does not fire up after each time the thermostat is calling for heat.The unit has been running like this for about 10 days now.I have replaced the Diagnostic computer, glow igniter,flame sens


The only part not replaced so far is the gas valve. Because the gas valve is getting power does not mean it is opening.You could also have gotten trash(corrosion/scale) in the valve orifice and or the burner orifices.Is there a drip ... Goodman Air Conditioners

I have a mitsubishi air conditioning unit model MUH-12v. The fan on the machine outside has stopped and of course inside the air is not cold. Could this be a problem with replacing the gas or could it be a technical problem with the outdoor unit. Also I have noticed when I switch on the unit on the inside with the remote control that instead of two green lights comimg on I only have one green light flashing. Does that mean anything?


Hi,Here is a tip about Mitsubishi Air Conditioners and how to get the manuals for all of the mitsubishi line. The manual include both troubleshooting and installation. ... Air Conditioners

I have a ten year old carrier heat pump unit. I recently replaced the indoor tstat. the outside contact and the transformer. Had a tech put freon in the unit also. I have to problems one is the airflow is minimal coming out of the vents it has new air filter and I cleaned the inside and outside unit coils. And the second problem is the ac with not get cold.


Two things are the most likely culprit. First check ytour inside coil with the unit running for 10 minutes or more and see if the coil is sweating there should be water running off of it. Also after one hour is there ice forming on it. These problems ... Air Conditioners

Carrier 38CK036330 Hi,  I totally know nothing about air conditioning. It's getting so hot in LA and we really need help since our house has a 18-month old child. We have a Carrier 38CK036330 central unit, and it's not cooling the house as we'd like it to. It's already about 13 years old and we are looking for a new one to replace it. The question is we cannot find this model anymore, or do we have to replace it with the same model?? What model or brand would you suggest for a 1350 square feet h


The model numbers change.You have a 3 ton system.The make and model that you replace it with is not nearly as important as a quality install.Do your homework on picking a contractor that you can trust.Have them do a load calculation to make sure a 3t ... Carrier 38CKC060 Air Conditioner

Have Coleman-Evcon heat pump system. Model DRHS0421CB. Condensing unit has intermittent no run condition. I replaced the contactor, as it was a few years old. I eliminated the thermostat from the equation by twisting together the RYO wires at the thermostat sub panel. This makes the air handler run and MOST of the time also makes the condensing unit come on as well. When it does run together, it cools great. Suction and discharge pressures are normal. The float switch is ok and no water prese


Elimate the items not needed to test the unit.\015\012Disconnect the defrost power board and set air handler to run.\015\012Disconnect the thermostat and hold contactor switch in closeing connections to the compressor and condensor fan. ... Air Conditioners

I do not know what ton condenser unit i have.It is a Concept High Effiency the model number is SB3OSA-4D Can you tell me what it is? I had the furnace and ac replaced about 6 years ago and was told the condenser was fine . Well now it's gone out and i found this one but I understand it's about 15 years old and i'm trying to see if they will match up. The unit i have is a Bryant 3 ton.


Unit you are describing is a 2 1/2 Ton ... Air Conditioners

I have a Goodman Air Conditioner Model CK49-1B. The fan in the unit does not turn on when the thermostate is set for cooling; the fan in the furnace works and blows warm air. Checking outside I discover that the dog chewed three wires that are coming from the unit. The repair person told me that the dog shortout the CONTACTOR and had to be replaced it, he also replaced 12 inches of wires damaged by the dog.. He did the job in less than one hour and charged me $225.00. Did he over charge me? Late


Take a look on amazon for same parts, and compare the prices: Amazon com goodman air conditioner parts. I hope this was helpful. Cheers ... Goodman CLQ36AR49 Air Conditioner

My colmen central air unit is not working properly. The Outside unit is not working. The problem initally arouse in June, but it "self corrected" after having the A/C unit turned off. Since that time the unit has run perfectly untill now. I did look for a reset button, but was unable to find one. The system (at most) is only 4 years old.


If nothing is running outside at times you probably have a weak contactor coil that is not pulling the contactor in all the time. If the outside fan comes on but not the compressor, the compressor is over heating and ... Coleman Air Conditioners

Good day! I am running my Carrier A/C Model 38EYG and it is running fine...the outside unit is running fine and the air coming out of the ceiling vents is cool. However, the inside unit (the one in the closet) is very hot. When I walked by the closet it felt like I was walking by an oven. I checked the temperature with my handy temp gauge and it was reading 120 degrees near the top of the unit...is this normal??


No its not normal. Check and make sure there is no flame inside the furnace. If not , turn the pilot light off it is a gas furnace and see if this makes a difference. good day to you too. ... Air Conditioners

The fan in the condenser unit appears fine its a CM42-1CE, 20 years old, The pipes between the inside unit and outside unit do not get cold? The air temp is room temperature .


Have you checked ... Goodman CLQ36AR49 Air Conditioner

My central air conditioning unit model edd2x30ba2 outside unit is on and turning, but the inside unit will not come on it has a lot of condensation on it. is there a reset switch and where is it located?


Turn off power remove cover feel indoor motor if hot bad or bad relay ... Kenmore 72055 Air Conditioner

I have a suncutter outside air unit and the fan barren has broken and i need a new fan for this unit I have the model # can you tell me where to locate one


Generally speaking the fan motor will have to be removed and taken to an appliance repair supply house. The unit model number will need to be written down and taken with you, but it is best to compare the motors when purchasing. ... Air Conditioners