Having problems with your Air Conditioners ?

I have a Janitrol Heat Pump Thermostat HPT-18-60 and need assistance connecting my new Honeywell RTH7500D thermostat I have a Goodman Heat Pump System Indoor Unit Model#AWB24-05C REV D Outdoor Unit Model#CPLE18-1 Here is the wiring of the old thermostat Y-Yellow Wire G-Green Wire R-Red Wire O-Orange Wire W2-White Wire E-Blue Wire C-Black Wire Where should each of these be connected to the new thermostats terminals?


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Janitrol Heat Pump Thermostat HPT-18-60 and need assistance connecting my new Honeywell RTH7500D thermostat I have a Goodman Heat Pump System Indoor Unit Model#AWB24-05C REV D Outdoor Unit Model#CPLE18-1 Here is the wiring of the old thermostat Y-Yellow Wire G-Green Wire R-Red Wire O-Orange Wire W2-White Wire E-Blue Wire C-Black Wire Where should each of these be connected to the new thermostats terminals?


... Air Conditioners

I have a Trane Heater/AC unit no heat pump with a thermostat model 802AS32DAA that has seven wires. I am going to a five wire heating/cooling thermostat. What do i do with the two extra wires? old thermostat red wire-RC slot (24 V from A/C) white wire-W1 (???) yellow wire-Y (A/C Compressor) green wire-G (A/C Fan) black wire-B (?????) Blue wire-Y2 (????) orange wire-W2 (24 V to Furnace new thermostat therminals G Rc Rh Y/O W/B Y1 Can you tell me what wires to connect to each


From Honeywell : "If your old thermostat had Six or more wires, the replacement you have is Wrong!" ... Air Conditioners

I installed a new Honeywell Programable thermostat, When I turned on the AC it turned on the Heater... I followed the wiring but some of it is not making sense... G=Green, Y=Yellow, R=Red, C=Blue, W2=White, Y2=Brown... The problem is that I have an Orange and Black Wire left over, Which one do I connect to W? and do I have the wiring right... my unit is a central Heat & Air, not a heat pump.


Hi, the problem is you have bought the wrong thermostat for the unit if it is not a heat-pump. A heat pump will have W-1, W-2 for heat strips, and Y-2 is for 2nd stage cooling. G is Green for Fan, R is Red for Power, Y is Yellow for cooling, and W wo ... Goodman Air Conditioners

I need help with my central heat and air unit, it has a heat pump. the model number is GQ3RA-036K. I am changing the theromstat out and the wires are connected to it. there are eight wire colors that are orange,light blue,black, red, yellow,brown,green, white. on the new thermostat are letters that are r,w,y,g,l,b,o,e,aux. Which ones go where?


Normal\015\012 0\015\012 \015\012 \015\012 \015\012 \015\012 \015\012 \015\012 MicrosoftInternetExplorer4\015\012 \015\012\015\012\015\012\015\012\015\012\015\012 /* Style Definitions */\015\012 table.MsoNormalTable\015\012\011{mso-style- ... Air Conditioners

Rheem Model RQNJ-A042JK Heat Pump Unit wired to a protech 520 Thermostat. Everything OK in auto mode. Fan will not run in on mode. All wiring connected except orange and black. Do not have original manuals for either unit. Installer went AOL and out of business without leaving me the manuals. Anyone have a solution. I know that Rheem is notorious for their wiring color tricks and I do not want to screw something up. Here is the wiring as it is now: Red - R Blue - B Yellow - Y White - E Jumper -


Connect the orange to the o terminal.\015\012Dave ... Air Conditioners

I replaced an old mercury T-stat (York with model number 2TH11704024) installed a new T-stat (RTH6350). The wires that I I have are O (orange), G (green), Y (yellow), T (gray but not used in new T-stat), R (red), L (black), C (blue but not used in new T-stat), W (white) and L (black). I connect all wires with their respective colors except that I connect the W in the AUX (jumped with the E). After I finalized all connections, the heat pump unit (York with model number ETFB024S06A) did not


Did you shut the power off to the air handler/furnace...... before you installed the new thermostat??? You may have shorted out the transformer or blown the transformer fuse...... If you try to put the Fan switch on the stat to Fan ON does the fan ... Air Conditioners

I am replacing a White Rogers 1F58-77 with a Honeywell RTH2300. When I removed the old stat the wire colors are white, red, orange, green, yellow, and blue. G- green wire Y- Yellow wire R- Red wire W- White wire O-Orange wire X1- Blue wire I hooked up all the wires except the blue. Instructions with the Honeywell unit said not to hook up the blue wire if there is an orange wire to hook up which I did. The problem, when I light off the A/C (heat pump) the compressor comes on but the


Yes you did correct. Tape of f blue wire. On your thermostat you should have el/gas turn top el and fan should work Russ ... Air Conditioners

Changing from a Trane Weathertron Heat Pump thermostat to a Honeywell TH5220D1003. The Trane unit had a white wire, green wire, red wire, orange wire, yellow wire, blue wire and a tan wire. Where do they go on my Honeywell TH5220D1003


... Honeywell Air Conditioners

I have an older Carrier Heat Pump which I am trying to update the thermostat control with a Hunter model 44550. The problem is that the wiring to the current thermostat is as follows, G= green wire, R= red wire, W2= blue wire, O= orange wire, Y= yellow wire, E= grey wire and C= white wire. If I am reading the schematic correct for the Hunter thermostate I am to wire as follows Green to G, Red to RC, Blue to W, Orange to O, Yellow to Y/Y1, C cap it as batteries are used. It does not tell me


JUMPER STAYS BETWEEN RC AND RH SO YOU HAVE INCOMING POWER FOR BOTH COOLING AND HEATING. THE WHITE WIRE YOU SAID C IS COMMON AND SHOULD BE USED IF POSSIBLE TO COMMON TERMINAL ON NEW STAT . IF THERE IS NO COMMON, THEN CAP IT BUT YOU'LL BE CHANGING BAT ... Carrier Air Conditioners

I have an amana rha36b2a heat pump and am trying to hook up a new thermostat. It's a pro 1 iaq t905 programable thermostat. I have hooked up the green yellow white and red (and ran a jumper wire from rh to rc). I also ran a jumper wire from W to Y. I ran the brown wire to C. The thermostat works great for heating but won't cool. When cool is chosen the heat comes on. Help! I know the O and B on the thermostat are the heat and cooling changeover valves but what should I do to connect them if that


... Air Conditioners

I have a carrier air/heating unit with pump. It has 8 wires. Brown,blue, white, yellow, green, black, orange,and red. I'm trying to install honeywell thermostat. The wires from my unit are suppose to go into these honeywell (RTH3100C) thermostat slots. hONEYWELL WIRE SLOTS E Aux Y G O L R B C The only thing i have to go on is the wire colors from my wall which were not labeled or coded in any way. I am not sure about the model# of our unit because it is so old that the model# has faded away the


Turn the power off to the air handler. Open the control cover. Write down what color wires go together at the wiring terminal. All 8 wires are probably not used.\015\012Post the findings here.\015\012In most cases,\015\012E= brown-e ... Carrier Air Conditioners

I am installing a new 3 1/2 ton heat pump the thermostat they sold me does not have the W-1 terminal for the white thermostat wire run from unit or the W-2 for the brown wire. One must go to Aux. Heat and the other the heat and although I am licensed and experienced I cant for the life of me remember which goes to which


Hi,W-1 goes to the heat and W-2 to the Aux. heat...so white on the heat and brown on the Aux.heatman101 ... Goodman CKL30AR30 Air Conditioner

Th6220d1002 Need to wire new thermostat Base board heat using red & white wire. AC American Standard Air Handler using red, white, green, blue. Both units have their own transformer Thanks


... Air Conditioners

Thermostat Connection ________________________________________ I just purchased a rheem rqpm series 4ton packaged heat pump and a honeywell pro th4210d thermostat. I had 15 kwatt heat strips installed in the heatpump as I live in norther florida where the temp might drop to 20 degrees occasionally. I am unclear as to how to connect the thermostat. The wires coming from the heatpump unit are red, yellow, blue, green, white, and brown. The thermostat terminals are as such: E Aux Y G O L R B


Jumper E to Aux, OR B + O, G--green, R----red(power), & C--------common. w2---------white, Y.....Yellow and finally the Brown-----------PRCrossed my fingers too & go for it. worst is a warning hum &/or sparking one one terminal whic ... Air Conditioners

At condense unit the diagram on the board has C,Y,O,W2,R on it.I just change the unit and the wires are confusing me. On the thermostat the wires being use are the R-red,W-Orange,Y-yellow,G-green,Y2-White.This is a heat pump unit.


Hi,\015\012\015\012Here is a tip that explans the wiring and the color designations...\015\012\015\012Thermostat Wiring a ... Air Conditioners

Need to change a broken blower motor in RUUD central air unit. Old central air blower motor (GE electric) was connected with brown and orange wire to 15 MHD capacitor. Another orange wire from central air unit connected to orange motor wire on capacitor. Black wire from motor (Hi Speed) connected to central air unit. Blue and red wires not connected. New motor is an AO Smith FD6000A. Has Black, brown/white, brown, blue,yellow,red, white and black wires. Need to connect to a 5 MHD capacitor. M


On the motor should be a diagram detailing the wires. brown white goes to either side of the capacitor and brown wire to other side of capacitor. hi speed goes to normally open contact on the indoor fan relay and the wire designated common on the mot ... Air Conditioners

Replacing old heat pump thermostat with not quite so old heat pump thermostat. New thermostat is Luxpro psmh45. Old thermostat had an AUX tab. New one(lux) does not. Where do I put white wire that went to Aux on old thermostat on new one?


Can you provide the manufacturer name and model number of the old and new thermostats? ... Air Conditioners

Trying to hook up Honeywell RTH6350 thermostat. When turned on cool out air blows out. We only have a green, red, yellow and white wire from the old unit. Are we missing some wires? we have a heat pump.


Your Thermostat should wire as Red to Rc/Rh (if Rc/Rh are not connected you need to put a jumper between them; White to W; Green to G; and Yellow to Y on your thermostat. These will be the only wire connections that you need ... Air Conditioners

Suburban sf30 rv unit.. I had a new board and limit switch installed. The service tech said it was working. I marked the wires when I removed the unit. I re installed the unit conecting the wires the same as when I removed the unit. I have 2 blue wires, 1yellow and 1 red coming from the furnace. There are 3 thermostat wires 1 grn, 1 wht and 1 red---The power source are 2 solid white wires and 2 blk and wht striped wires, there is power to the unit. I am at a loss as to why it will not work. T


... Dometic Rooftop RV Air Conditioner

Thermostat with 4 wires, red, green, white and blue; no yellow wire to connect to new thermostat


... Air Conditioners

I have a Tempstar model NFCP3600A1 (style # FCP3600A) ICP Heat Pump. Starting last week, the unit kept heating well over the set temperature. I swapped out the thermostat thinking it went bad, but it still continued heating and the "off" wouldn't work at the new thermostat either. Next, I checked for shorts in the thermostat wires and they seemed OK. I then replaced the TI 26FC-2 circuit board. Once the unit heated the house to the set temp, it continued running up to 75 degrees. "Off" and lowe


... Air Conditioners

I have a Trane XE1000 heat pump and a RiteTemp 6036 Thermostat. I have red,orange, black, white, yellow, green, blue & brown wires & need to know what to connect where?


... Air Conditioners

Thermostat wiring I have a Frigidaire Model R4GA FWA and Central A/C system. I am trying to replace the thermostat with a programable Hunter model. I do not have the original wiring diagram and the old thermostat is no help. The wiring colors I have is Green, Red, Brown, Yellow, White and Orange-(not used). The terminals on the new thermostat are RH, RC, Y/O, W/B, G, and Y1.


Your best bet and where i would start is to identify where the coulors are conected at the fernace. in the industry we use standard wireing coulors wher green is g for fan and red is rh=switched trans power for heating . rc=switched transformer pow ... Air Conditioners

Honeywell 7512A. Working fine. Turned off power yesterday notice no display so once power was restored I changed to new batteries. There should of been a display due to the batteries. New batteries were checked fully charged. Breakers were all reset. Batteries are in properly. Now I have no display. Polarity is correct. Wiring configurations is White to white. Orange to Yellow terminal. Green to green. Black to red terminal. Red to RC terminal. I have airconditioning and heating.


... Honeywell Air Conditioners

My dog chewed up the t-stat wiring on my outside a/c unit (compressor?). I purchased some t-stat wire at Home Depot and replaced the wiring. At the outside unit, I connected the new white wire with the brown from the unit, and the new red wire with the yellow from the unit. This part was still connected from the previous install, so I copied from how it was wired before. For the wiring to the house, this was disconnected completely by the dog, so I connected the new white wire to the white w


Hello,Yes there is a 3 amp blade fuse(same as in a car) in the blower unit,take off the door and it is plugged in to the(curcuit) board.Pull it out and slip a new one in.That will restore the control voltage.Your repair sounds correct.Some times ther ... Air Conditioners