Having problems with your Air Conditioners ?

Fedders Model No. A7U12W2A-A, 12000btu airconditioner. The unit has been cooling satisfactorily for two to three years. Today the unit was cooling and suddenly there were a couple of reasonably loud knocks and the compressor stopped cooling. The fan continues to run. In about five minutes the cooling comes back on. The compressor runs for abut four minutes and shuts down. Earlier today we had a power dip without losing all power.


Answers :

Hi, the power dip when translated means low current actually affected the relay starter which is situated beside the compressor. Now the relay starter works and stop intermittently which is why the Compressor cools whenever it works and does not cool whenever it does not work.
You need to change the relay starter immediately.

Take care

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Fedders Model No. A7U12W2A-A, 12000btu airconditioner. The unit has been cooling satisfactorily for two to three years. Today the unit was cooling and suddenly there were a couple of reasonably loud knocks and the compressor stopped cooling. The fan continues to run. In about five minutes the cooling comes back on. The compressor runs for abut four minutes and shuts down. Earlier today we had a power dip without losing all power.


Hi, the power dip when translated means low current actually affected the relay starter which is situated beside the compressor. Now the relay starter works and stop intermittently which is why the Compressor cools whenever it works and does not cool ... Fedders Air Conditioners

You can set the temp for the unit to come on and it comes on and runs and cools for a few minutes then the compressor cuts off then the fan a little later. After a few minutes it comes back on and does the same thing. It never cools down to the set temp. The coils are wet but not frosting.


Is the AC set on an energy saving mode. Together with this program if the thermostat is defective the same symtoms can appear. So please check on the thermostat and replace.\012Since the compressor is cutting off the cooling does not take place ... Whirlpool ACC184PS Thru-Wall/Window Air Conditioner

I have a Nationwede YL-2300 portable air conditioner. The compressor runs, the fans run, but it is not cooling. After a few minutes the compressor cuts out and then restarts again after another minute or two, which is what it should do, but it still doesn't blow cool air. There is no hot air coming from the compressor unit. Any ideas about what is wrong with it?


... Air Conditioners

I have a Sanyo Split System the indoor unit is a KHS0921 and the outdoor unit is a CH0921. When i first turn the indoor unit ON the fan will run for a few minutes and then go off. The outdoor unit never comes ON when there is a cll for cooling. The only way to get the fan to come ON again is to turn the breaker OFF and then back ON. The Operation loght will come ON when the fan is running but it will start flashing when the fan goes OFF. What should i look for?


... Sanyo Split System Air Conditioner

Breaker breaks When my Dometic roof a/c compressor comes on during a regular cycle, it sometimes pops the breaker. I replaced the breaker but think there must be some sort of timer in the unit that allows some time to go by before the compressor comes back on. If I reset the breaker and turn the unit back on immediately, it pops again. If I wait about 5 minutes it will run ok. The amps are ok. Help.


This unit may have an internal overload mounted on top of the compressor. You would have to get to the\015\012compressor to find out and it maybe faulty. That may\015\012explain why the compressor comes on later on, this\015\012over ... Dometic Rooftop RV Air Conditioner

After a cooling cycle, when the thermostat call for more cooling, it take up to 5 minutes after the air handler starts for the compressor motor to restart. The top fan operates on the outside unit, but since the house is not circulating cold air, only the room tep air the house heats up about 3 degrees before the compressor comes back on and cool air begins to come from the ducts. Yes. I know there is a safety feature to protect the compressor, but can the cycle be shortened?


No, this cycle cannot be shortened due to the simple fact that this feature is in place to protect your system. Even if it could be, I wouldn't recommend it.Mat ... Coleman Air Conditioners

Installed new compressor on Carrier 3 ton a/c unit. Compressor comes in, but only runs for about 2-3 minutes and then trips out. Have installed new compitcor. Have 24 volts coming in. Will not take freon charge. Liquid line coming back to compressor behind dryer is extremely hot. Do you think the dryer may be stopped up causing unit not to take charge?


Hello,The trpping off may be as a result of dirty condenser. please clean the condenser to stop this problem.The dryer may be stop up causing unit to take a charge.Thanks ... Carrier 38CKC036 Air Conditioner

I have a Coleman Central Air/Heat System. This year, the outside compressor (or whatever it is called) is shutting off within minutes of the air conditioner coming on. This is resulting in the home never cooling down. I can reset the system by shutting the air off inside the home for a few minutes and the outside compressor comes back on, but again, only for a minute or two, and the unit only blows what seems to be room temperature air.


Do you know the devices model. It would help in locateing the manual. also I beleave you have the manual?\015\012\015\012As micromaster already said, check for sleep timer.\015\012\015\012has the system worked fine before has ... Air Conditioners

HAVE A COLEMAN MODEL DRHSO601CB --- THE UNIT WILL RUN FINE FOR SEVERAL HOURS WITH GOOD COOLING AND THEN PERIODICALLY THE TROUBLE LIGHT WILL COME ON THE THERMOSTAT AND THE UNIT HAS SHUT DOWN. TO RESTART - YOU MOVE THE THERMOSTAT TO OFF WAIT 5 MINUTES OR SO AND PUT IT BACK ON COOL -- IT WILL RESTART ALMOST EVERY TIME AND RUN FOR SEVERAL HOURS. IN THE PAST IN THE PAST I REPLACED THE DEFROST CONTROL BOARD BUT WHEN I DID THAT THIS TIME IT STILL SHUTS DOWN - WHAT OTHER PROBLEMS ARE YOU AWARE OF ON TH


You may have a low pressure or high pressure switch tripping out the board as well. You might try cleaning both the indoor (evaporator) coil and the outdoor (condensing) coil. Be sure to turn off the power source before servicing this. ... Coleman Air Conditioners

Not a GE unit. I charged unit with refrigerant and powered up unit. After running for @ a minute it shut off, having no power light at all. I found a set of wires reversed that were going to the outdoor unit. after fixing the wires i can't get the unit to come back on. The breaker is not popped and I assume there is some kind of fuse or overload that I have to manually reset or replace. It is a chinese (i think) made unit Air Control


Since most of these units, come precharged for line sets up to 125' in some models, the fact that you charged it, concerns me. Second you made no mention of the king valve, did you open it.\015\012 Then your diagnosis speaks to overvcharge, an ... GE Quiet-Aire Ductless Mini Split System Air Conditioner

Cooling well it starts just fine cools for about two minutes then the compressor shuts off unexpectedly? i thought it might be the thermostat? i bypassed the thermostat completely but no luck? i can here the compressor come on when the unit is switched on and it does appear to cool down before the compressor shuts off and the fan keeps running.


Check if the condensar ( outside fan unit) is getting enough free ventilation. IF there is no free air flow you will mostlikely be triping the unit due to short cycling. Ie the unit is pulling its own discherge air causing the compressor to trip due ... Haier HPAC9M Air Conditioner

1996 coleman rooftop unit,fan runs,no power to compressor, has inside relay board, no power past compressor relay unless bypass then compressor comes on and cools


... Coleman Air Conditioner Shroud Rv Roof Top Ac Rvp Mach 3 A/c

My ac comes on in my RV and runs for a about 15 minutes and then the fan shuts off and finally the compressor shuts off. this happens before reaching the cooling temp. When it comes back on the fan does not come on at all and you can just hear the compressor hum


The Fan topside , Is the one working? The one that blows on the condensor? If not, your compressor can be trying to start against high head pressure. Ck the other fan, not the one that blows inside, the other one.It cools down the condensor and ... Air Conditioners

Hi, I have an 8,000 BTU unit. The unit is about 5 years old. It was running fine, no problems at all. Then whan I went to turn it back on after a few days-nothing. No noise, no air, nothing. It just did not turn back on. Before this happeend it cooled, it reponded to degree changes all was fine. The green light button on the test and retest comes on, but there is not a sound from the unit itself. Its like you would hit a power button that was not plugged in (but it is). This problem occur


After changing or cleaning your Filter, you need to reset the A/C. Follow the procedures below:\015\012\015\012Disconnect the power plug from the power supply.\015\012Clean the air filter.\015\012 ... Sharp AF-S80FX Air Conditioner

I have a Mistral Inverter Reverse Cycle Split System Air Conditioner. MSS.3INV. The trouble we are having is the cooling will work for half an hour or so and the compressor will turn off leaving only the fan going and the comporessor and timer light flashing. This hapens before the desired cooling temp is reached. You can switch the main power off to the unit and back on again after a few minutes have past and the unit will operate again in cooling mode and then just do the same thing. The gas


Hello,What this problem indicate is that the thermostat of the air condition has been gone bad.When ever an refrigerator does such it simply mean that thermostat need to be replace by some time it could be on the time progra ... Sanyo 24KS32A Cool Mini Split Air Conditioner

I have a window air conditioner. When it runs for several hours it will trip the breaker. I have had the unit for 5 years. I bought it used and even though it has always shaken when the air compressor comes on it has cooled fine. Recently, however, my landlord changed the circuit breaker (had an electrician come out to do this and supposedly everything is working find). However when I pluuged the unit back into the plug for this circuit, the unit would not even operate for 10 mintues withou


It's probably fine even though it jiggles and makes noise. I would ask the landlord to change the circuit breaker again and ask the electrician what the amps were for the breaker he took out and the one he put in. \015\012\015\012Hopefull ... Whirlpool Air Conditioners

My Duo-Therm RV roof-top a/c unit continues to come on and off when the system is turned off. No air blows, just the compressor runs for about a minute then shuts off. About 5 minutes later, it comes back on and does the same thing. Again, let me stress, the system is in the OFF mode.


Hi,The liquid line solenoid valve is bad and is allowing just a bit of refrigerant through it after it shuts off and the compressor pumps down....this causes the pressure to rise a gain and then the compressor comes on to pump down again. ... Air Conditioners

I have a unit that is cutting off and on every 5 minutes, what could cause this? It is running 55 suction and 235 head pressure and working and cooling but every 5 minutes it cuts off and comes back on in another 5 by itself.....acts like a sensor or something is reading faulty but there is no info on this unit...its just a little mini split.


If this is a R-22 unit the unit is cycling on the low pressure switch. They are usually set to open at 60 psig. Pressure below 55 psig the indoor coil will freeze up so they set the pressure switch to open at 60 psig + - 3 or 4 psig. You either need ... Air Conditioners

Duotherm ac Installed new duotherm ac on rv. In cool mode on call for cooling everything comes on properly. 10 minutes later fan stops while compressor continues to run. 10 minutes later fan starts back.


... Coleman Dometic Duotherm Rv Air Conditioner Universal Roof Gasket Seal 14 X 14

Unit will cool for about 10 minutes and then compressor shuts off an unit blows warm air for about 10 minutes and compressor will start again blowing cool air and then compressor will shut down again and unit will blow warm air ... etc. the unit is running off a generator to cool down a 10x14 enclosed trailer and does not do the job of cooling


... Haier CPN10XCJ Air Conditioner

My inside and outside unit turn on fine, out side fan and compressor running good,inside blowing cool air, about four minutes after that, out side unit shutoff, no humming, nothing.


... Ruud Air Conditioners

I noticed some straining noise coming from my a/c unit today. The fan on top of the condenser runs fine but as soon as the compressor tries to kick on the fan stops for a split second and you get a kind of surging noise from the condenser unit. Then the fans kicks back on, the the process repeats itself every couple of minutes. Meanwhile no cold air is being produced inside the house. Any ideas?


You amy ahave a bvad capacitor on the outside unit. It starts the fan and the compressor. You can change this yourself. Open the outside panel and you will see a silver canister with terminals out the top. Replace this and I think your problem will g ... Goodman CKL24AR24 Air Conditioner

The compressor in my central air unit does not kick on. Sometimes it will sometimes it won't. I really notice when it doesn't because of the scorching heat from outside. Basically when the air is off all night, which I don't run at night because it is to cool, but in the morning when the thermostat is set for it to come back on the compressor won't kick on for a couple of hours after if at all. Please help me figure this out. I'm pretty handy a do it yourself projects.


Sounds like you may be low on charge and going off on internal thermal over load.Just a guess though. ... Air Conditioners

On my 1999 camper trailer when I turn on the dc powered lights while the airconditioning is running the compressor will kick off. If you wait 3 minutes it will come back on and continue to work fine until you turn the light back on.


Welcome to FixYa\015\012\015\012Not enough cooling complaints are due to air flow issues, and not lack of “Freon.RV air conditioner- come from the factory- are hermetically sealed.The first basic area is the air ... Dometic Rooftop RV Air Conditioner

I have a frigidaire window unit model fra256st2, when I first turn it on the unit blows ice cold air for 1 to 2 minutes then the compressor kicks off. I have to wait 5 minutes then switch it from cool to fan only then back to cool again in order for the cOmpressor to Kick on for another 1-2 minutes.


... Frigidaire Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1540 seconds