I purchased a ductless amcoraire mini split system. I believe the models are AWSO91HX (inside unit) and AOSO91HX (outside unit). I am getting a F1 error (indoor outdoor communication failure). Please advise me and my licensed installer on how to correct the problem or who I can contact for a house call repair.


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I purchased a ductless amcoraire mini split system. I believe the models are AWSO91HX (inside unit) and AOSO91HX (outside unit). I am getting a F1 error (indoor outdoor communication failure). Please advise me and my licensed installer on how to correct the problem or who I can contact for a house call repair.


... Air Conditioners

I had a new sears heating unit installed by sears contractors yesterday. Before I purchased the boiler, I was told by sears salesman that I had a maintenance plan that included 24/7 repairs. 6 hours after it was installed, the unit started linking and is still inlinking. Upon calling sears repair, I was told that repair dept. is only opened monday thru friday, 8am to 5 pm. and would have to wait until monday. I was told by a sears answering service that the salesman had lied about 24/7 coverage,


Yes as with all big companies problems with comunications are a pain to say the least. Anyway it sounds like someone left a loose fitting. If you can locate the place where it is leaking there is probably a fitting loose there which you can tighten u ... Air Conditioners

I Installed a spit unit that I removed from my office. The brand is McQuary. The inside Evaporator unit is a model# WM20C/25C. The outside condenser unit is Model MDCX18-18. Somehow I connected the 240V wiring incorrectly and the outside unit doesnot start. Please provide me with the correct wiring installation


Is there a chance that the outside unit gets the line connection (from your breaker), and sends it to the inside unit? In that case, you'd wire the L1 to one leg of the 240, the L2 to the other, and the white would go to the neutral. Obviously you ... Air Conditioners

My frigidaire air conditioners spit dirt all over the floor. My window unit and my through the wall unit in a sleeve both do the same thing. I called Frigidaire two years ago and they told me there were no reported problems. I keep the filters clean and don't know what is causing this. My rugs and furniture are full of dirt particles when I use these units. I have had air conditioners for many, many years and have never experienced a problem like this. Please advise me if this is a problem with


1. Turn units off\0122. Remove Filter\0123. Spray a foaming cleaner on the coils (Dow Bathroom Cleaner)\0124. Use a spray bottle filled with plain water\0125. Replace Filter and Grill ... Frigidaire FAC124 wall/Window Air Conditioner

I have a split unit and the one wall unit does not work at all. I called an air conditioner contractor and he replaced the circut board and blower motor. When he turned the unit on it blew the new parts. Now he is telling me that it cannot be repaired. Can you please help ?


Hi,I have no idea, how they replaced the circuit board and blower motor without running the diagnostics or inspecting different components. It would be really hard without looking at the AC that what's wrong with it. It could be a problem ... Samsung AS18A6RB Air Conditioner

Replacement Repairs My air conditioning unit is slightly less than three years old. It quit working so I called the business that installed it. He found that there was a blockage in the necking device on the evaporator coil increasing liquid pressure 40 PSI. I feel that, in as much as this is within a sealed unit, it is a manufacturing problem, not one due to my environment or my doing. It is a very expensive part to replace and I feel that there is some responsibility on your part for this prob


Most units have a 5 yr parts warranty but you would be resposable for labor. ... Weather King Air Conditioners

I have a rinnai gas heater ultima inbuilt (i think it is called a high efficiency 30 model) which is almost 6 years old the local plumber says the timer is faulty & a new control panel is neede however he can not locate a unit, can you please let me know where i can get one as the unit has hardly been used since installation & otherwise is in perfect condition thanks Ray


You can try www.sdsmarket.com/rinnai-parts-lists-s/750.htm. Thank you. ... Rinnai Air Conditioners

The PKH3 FAK unit begins making an intermittent buzzing noise when it has been operating for about 10 mins. when the unit is turned off using the remote control, it continues making the noise for 10 mins or so. can you advise please? I have just bought the apartment where this air conditioner is installed. Thanks


As per your statement, it's understood, your unit is under gas leak. Hope there won't be cooling. Am I right?. Thanks. ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have a Baxi combi boiler 105e and a Honeywell ST6100C programmer/controler, and i wish to add a Seimens wireless digital room thermostat RDH10RF/Set. the RCR10/433 unit needs to be wired to the boiler/controler above so that the thermostat switches the boiler on and of when demand for heat is called for by the room thermostat unit RDH10RF. can you please advise on how to connect the wiring or if it is possible to get a wiring diagram many thanks Paul


... Honeywell Air Conditioners

Air conditioning unit not running but fan keeps running even though thermostat is turned to off, auto, and temp set to highest position 90degrees. 3 amp fuse keeps blowing on the circuit board in the blower compartment. I replaced it 3 times then installed a new thermostat. no change. I can usually figure it out if I got a little input or direction. Any help would be deeply appreciated. I would much rather have a trained expert easily repair my hvac unit but I can only call the professionals in


If the fuse is blowing then this is generally indicative of a short in the low voltage wiring, isolate the wires on the thermostat and the unit ends, use an ohmmeter to verify that there is no path for continuity with no wires touching, if there is t ... Air Conditioners

Please advise, a comfortmaker A/C unit was installed in my home in February 2009. I was told that feeze on could not be installed until it get about 70 degree ... what will happen if I use the AC without having it check and service right now?


The unit will not work without refrigerant. You could damage the system. It was probably too cold to install refrigerant in February, but should be ok now...anytime. ... Air Conditioners

We have a 1997 Coleman popup camper. The air is just a little cool and it keeps leaking on the inside. I called a repair place and was told it was most likely low in freon and that it could not be added due to it being a sealed unit. Does anyone know if this is correct or how to fix the problem. The AC is a roof top unit


The drain is blocked and needs a clean out ,look for a drain hole with a pipe to the outside .as for the gas recharge then yes it can be filled by a specialist and not a chancer ,you have to cut a pipe on the motor and solder a connection on the end ... Air Conditioners

I have a Goodman split unit installed. The inside furnace works fine. When the system is turned on the outside unit makes a slight "popping" sound like the current is getting there but the fan will not start. I have replaced the capacitor but it is still doing the same thing. Please advise. Thank You, Dan Clevenger. [email protected]


Hi,\015\012 Change the circuit board of the system... no other option.. and also check the electric contactor switch... Have any other queries, please let me know..\015\012Thank you..... ... Goodman Air Conditioners

Unit will not start up and displays fault code F1, which according to installation manual is "Indoor and outdoor communication failure". How do I fix this?


Hi, The unit was not installed properly.You should allow a professional technician to installed the unit for you.You can go to the website below to see the installation guide. http://www.shophmac.com/pr ... Amcor Aire AMS241HX Split System Air Conditioner

We purchased a model TCH7090ERL a few weeks ago. The heater has worked very well until day before yesterday. Now, the heater does not function properly. We can select the "mode", but the unit will not turn on properly. I have misplaced the instruction manual, so cannot look up information. There is a red circle light illuminated in the display. Please advise how to correct the problem. Thanks!


... DeLonghi Air Conditioners

My heatpump has quit working I have checked voltage to out door unit it is fine. I have checked low voltage to make sure it is calling it is showing 24 volts from blue to yellow. I have check the uf on the capacitor it is good. I am getting correct voltage into contactor. please help


If all the voltages are correct you might have a bad contactor. Check the low vltage wires that controle the contactor and see if you have >24 volts. There also might be a low pressure not letting it come on. ... Ruud UBHC Air Conditioner

Our new Ruud air conditioner/heating unit freezes up repeatedly in hot weather. It was bought 11/10/08. How long do we have to get it swapped out? Please email: [email protected] P.S. The installer does not WANT to replace it, as he has tried a repair of one sort or the other all summer long.


There is a possibilty that 1 of 2 things could be wrong 1 if only the outside unit was replaced it may be incompatable to the inside unit (size in tonnage) you can't place a 3 ton unit on a 2 ton furnance or vice versa. If both were replaced togethe ... Air Conditioners

I have a split unit interherm and have had allmost everything in the world done to it just had capsator replaced two weeks ago and every scence then it has not been cooling off fast enough like was before it sounds like to me the fans have slowed down and the main thing is it keeps coming on every ten minutes all the time have spent a lot of money in it the last two years by having these so called part time ac repair men please help


It sounds to me like you have the wrong size capacitor installed if you are talking about the outside condenser fan motor running slower than normal, it might have just enough to kick on, but not enough to keep running, which could cause your system ... Air Conditioners

Hi, I have a WARMAIRE wood burner and i am looking for a manual that shows how it is assembled and installed. I need to to remove it to repair it. Are you able to please assist. Its an older unit and i would gues its at least 10 to 15 years old. regards, Louie


... Air Conditioners

Inside unit The control transformer blowed up when when water got on it from thawing out the coil after it froze over due to being low on coolant. I call a repair company and they installed the wired transformer backwards Where would i get a wiring diagram for a Intertherm heat pump Model#: E1EH-105HA SERIAL#: E1E9505-06625


How do you know it was installed backwards? ... Air Conditioners

Third control board has been installed on a goodman 3 ton central air unit in the attic...the only that happens is when the thermostat calls for cooling...the inducer fan comes on and then the blower motor stays running but the condenser does not come on......There is always 6 flashes on the control board.....which says roll out switch....please help me on this one....Calvin from Memphis


Temporarily jump out roll out switch. ... Goodman CKL42AR42 Air Conditioner

I purchased a Friedrich PDH15KS BTU Cooling, 17,000 BTU Heating, 9.3 EER PTAC Air Conditioner With Heat Pump and 5.0 KW Backup Electric Heat....in October of 2007...it was installed in November and ran perfectly until the last 2 weeks or so...it has metallic "rattling" ..we think when the back up heat is on?? but we are not certain... it was placed in a new addition ...contracters did not give us paper work about waranty or repair??? please advise ...my location is Balwin City, Kansas ...thanks


... Friedrich Air Conditioners

Goodman unit ck-36 1b replaced capacitor installed a amrad's 200 turbo ac worked for 1 week now ac is not working again please advise


Was the turbo 200 set to the correct microfarad rating? ... Air Conditioners

I have a gas furnace that was to have a 10acc air conditioner unit installed with it. Instead of the 10acc unit a 10hpr48 heat pump unit was installed, The house is 4 years old and the reversing valve has failed. The unit is not wired as a heat pump but as an ac unit with only three wires. A independent air conditioner repair company has said this installation is inproper.Is this unit installed to code and would lennox guarante a unit installed in this manner?


It should definitly be warrantied. their is nothing wrong with your set up however id have the contrator pull a new wire and go dual fuel withh outdoor sensor and get the full benifit of dual fuel. you should use the hp above 40 ... Air Conditioners

Have AMCORAIRE mini-split purchased in 11/08 and installed in new guest cottage on 7/17/09 by local AC tech. in Cocoa, FL. Unit worked fine for approx. 7 months then stopped working with error code F!. Called AC Tech who installed unit and he called Pridiom tech support and spoke to Alan while trouble shooting unit. They determined that trouble was in circuit boards and suggested replacing boards, which were back ordered or buy new outside unit. The unit is a 12,000btu mini- split with heat


Try this link. They will be able to help you with your concerns.\015\012\015\012\015\012The FixYa Team ... AmcorAire UCHW-H12AF2 Split System Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1137 seconds