Having problems with your Air Conditioners ?

Hello.. I am looking for the bottom squirrel Cage for my Edgestar AP14,000HS Portable Air Conditioner.. I have called Edgestar all I get is voicemail. I have e-mailed Edgestar and have not received any replies.. I have paid about $500.00 for this air conditioner not quite 2 years ago. I can't find anyone able to help repair it..


Answers :

If you take off the back filter panel, you can look down into the innerds of the unit and you will see the squirrel cage.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Hello.. I am looking for the bottom squirrel Cage for my Edgestar AP14,000HS Portable Air Conditioner.. I have called Edgestar all I get is voicemail. I have e-mailed Edgestar and have not received any replies.. I have paid about $500.00 for this air conditioner not quite 2 years ago. I can't find anyone able to help repair it..


If you take off the back filter panel, you can look down into the innerds of the unit and you will see the squirrel cage. ... EdgeStar AP14000HS Portable Air Conditioner

I have a Danby DPAC10030 air conditioner. It was working fine until yesterday, when we moved it to another room. Now it blows cold air for 5 minutes and then the air turns hot. The a/c motor continues to run even though the air is no longer blowing cold air. The current ambient temperature is 25 degrees C and I have the a/c set to cool to 17 degrees C. The timer has been turned off (0:00 on and 0:00 off). I noticed that the hoses (exhaust) feel quite hot. Not sure if that it normal within


Clean you filter and clean the area under the intake duck it will solve your problem ... Air Conditioners

Have a Fedders A6Q10F2B-S air conditioner serial #BU158972056X that I used from May thru September, I believe it was the 4th summer or possibly the 5th. Last August 2010 it quit cooling. Keyboard funtions seem to operate as mornal and fan runs continuous like always but I never hear the compressor kick in and it doesn't cool at any temperature setting. Any ideas? I'm an electronic tech for avionics and communications and a handy guy. If it is something I can handle, I'll try to repair it


Hello Jimscs, \015\012\015\012I understand that you are having a problem with you window air conditioner. You state that the unit is not cooling any longer and can not hear the compressor kick on.\015\012\015\012I ... Fedders A6Q10F2B Q Chassis Room Air Conditioner

Rooftop rv air conditioner doesn't work - what can I check myself without taking the rv to a repair place? will any air conditioner repair place do repairs or do I need to use an rv place?


I'm assuming when you say 'doesn't work' you mean 'nothing comes on,' i.e. the fan or the compressor.\015\012\015\012If that's the case I would check for the AC breaker to see if it's tripped. Usually a 'tripped' breaker will look half o ... Dometic Rooftop RV Air Conditioner

My son has a Goodman Manufacturer Corp Heat Pump/air conditioner. Forced air I believe. The air conditioner quit. A repairman indicated that in order to replace the air conditioner the furnace will have to be replaced also. The air conditioner unit outside is Model No. CPE30-1-AB. Any thoughts?


I don't see any reason to change the furnace unless it's an air handler and not a furnace with a coil on top or bottom. And then, the only reason to change the inside unit when you change the outside unit is because it's a R-22 system and your going ... Goodman CKL30AR30 Air Conditioner

Bryant air conditioner - outside unit will not run - before it quit running, air temperature in house rose from 65 degrees to 75 degrees. Inside fan continued to blow - air smelled like a car air conditioner that ran out of Freon. Bought Freon - need to know where to add it. The heat pump model # BF-163S bi directional but also coming from unit is another line that runs same direction with same type of valves. Air conditioner model # 697CN030 - B


... Air Conditioners

Air conditioner my air conditioner is leaking water from the bottom can you tell me what's wrong and if I can repair it and if it's worth repairing


... Simplicity 9,500 BTU 3-in-1 Portable Air Conditioner SPAC9507

Installing an 24,000btu air conditioner. The original wiring at that outlet has an double pole 20amp circuit breaker. The old air conditioner that was their was plug into an outlet box that sat on the face of the wall that had 30 and 250 on it. I had purchased an outlet that had 20 and 250 on it. The instruction for the wiring of the new air conditioner said 208/230 volts; 0 to 12amps; 20amp time delay fuse or circuit breaker. So tell me if I am doing the right thing with that 20amp and 250 volt


Yes your ok if they say the unit doesn't need to be changed in the incomimg power from 208 up to 230 volts or vice-versa,normally they classify motors as120/208/ 230 /460 volts, instead of 120/240/480 volts,but all line voltage varies in this voltage ... ACE -Air 24,000BTU Heat Pump A/C Free DVD Install it yourself Air Conditioner

I have an daewoo wall air conditioner unit that is out of freon or refrigerant,how can i repair the air conditioner and get some cool air outta of the unit


Hi,\012Here is a tip that I wrote about how to add refrigerant to a air conditioner orcooling systemHow to add Freon to a Air Conditioner or Refrigeration Sys ... Daewoo DWA-146R Air Conditioner

Sometimes, our furnace will start blowing cold air when it should be blowing hot...I know it is normal that it blows hot air and then will blow cool air as it cools to shut down. This is not what I am talking about. I am talking about while the furnace is blowing hot air to heat, it will quit blowing the hot air and start blowing cold and it it like the air conditioner kicks in. It will then continue running cold air...I usually have to shut the furnance off and when it kicks back on it will


Do you have an automatic change over thermostat? this would switch it from heating to cooling. ... Air Conditioners

Okay I got a reply for help on my fedder air conditioner, but for some reason I never found the owners manual where I was sent to so Thank You for your help and now I will send the Model #out so maybe somebody can take me to get a manual for this air conditioner. A6D24E7A.


OK, now with the model number you provided, I can determine that it's an older model and the manual is no longer available online. The part number for the manual should be #CRC23230258N013\015\012\015\012This supplier states to email the ... Fedders Appliance Air Conditioner Wall

I have a wall mounted Kenmore 21,000 BTU/hr air conditioner model 106.8752192. The compressor and cooling portion of the air conditoner works fine. However, the blower motor bearing appears to be going bad. The noise at ''LO'' speed with the compressor off is gradually getting worse. Is it repairable? What is the estimated repair cost?


Sure it is repairable, in fact it's a relatively simple process if you are familiar with electronic devices and handy with tools.\015\012\015\012You will need to simply replace the blower motor and capacitor.\015\012\015\012Mo ... Air Conditioners

I have a gas furnace that was to have a 10acc air conditioner unit installed with it. Instead of the 10acc unit a 10hpr48 heat pump unit was installed, The house is 4 years old and the reversing valve has failed. The unit is not wired as a heat pump but as an ac unit with only three wires. A independent air conditioner repair company has said this installation is inproper.Is this unit installed to code and would lennox guarante a unit installed in this manner?


It should definitly be warrantied. their is nothing wrong with your set up however id have the contrator pull a new wire and go dual fuel withh outdoor sensor and get the full benifit of dual fuel. you should use the hp above 40 ... Air Conditioners

I have an Edgestar Portable Air Conditioner AP12000HS. The Air Conditioner works wonderful, however I can't get it to heat, I put the Mode Button on red which is supossed to put the heater on, it will run for a few minutes and then shut off and it does not take the chill out of the room I have the unit in, is there some kind if thermostat internally which can be set? The way it runs now does not do me any good as a heater.


The unit has a built in thermostat in the front control panel, this is what maintains the set temperature, it is very likely that this control is defective, all the controls for the unit are contained in the CCU (central control unit) ... Air Conditioners

Hello, i have a haier HSU-09HG04 Split Air conditioner system. It is a fantastic air conditioner. I am needing to move it to another location. While unscrewing I noticed that gas began to escape from the join. I w643d 352e t6 2n6w h6w t6 t4rn 6ff the gas so that I can unscrew both pipes? I hope that you are able to assist. I look forward to your reply? Many thanks Greg


You cant "turn off the gas" in an AC system.\015\012\015\012It is a recirculating loop of refrigerant. It is not a gas that's piped in from an outside source.\015\012\015\012If you were able to re tighten the nut and prevent a ... Air Conditioners

Edgestar 12,000 portale air conditioner and heater


There are 3 possibilities beginning with the most likely problem\015\012\015\0121) If your heater heats up for a few minutes and then quits, chances are there is a blockage in the air flow, check for dust and grime blocking the air intake ... EdgeStar Portable Air Conditioner Heater

Window air conditioner repair


When you smell something like that it only means your unit is leaking.the freon/refrigerant is what you smell.so i suggest compare a brand new one with the labor cost for repairs in your area. ... Air Conditioners

Hi guys, i have a portable air conditioner 9000btu 'ariagel ag90' window) that works great for the first 5 minutes, until gradually the unit makes more and more noise until it shudders quite violently , returns to its normal noise and blows out hot air for 5 minutes. This hot air seems enough to cancel out the cooling it does. then after a while it cools gradually I've read alot about this air con problem, but nothing regarding the gradual noise and shudder. The slide out filter at the back s


This is due to the compressor going into thermal overload, It can be cause by really dirty coils preventing air flow,A restriction in the cap tubes or orafice, Or an over or under charge in the system.The noise is due to the compressor building up to ... Air Conditioners

Danby DB98-26786A window air conditioner will start up and blow cold air..frost forms on the tubes..after a few minutes the frost disappears and the compressor shuts off .. the fan still blows; but no cold air ..the compressor doesn't start again unless it is turned off for quite awhile


Hi,Here is a tip about troubleshooting your air conditioner...\012There are many things that can cause your air conditioner not to cool... ... Danby Air Conditioners

Gree air conditioner GSW24-22L/A(0)


... Air Conditioners

I have a whirpol air conditioner ACC 108 PS 0 do


Thanks for your question!\015\012I'm sorry that you haven't received an answer yet.\015\012The response rate on FixYa FREE questions is usually over 80%, but sometimes questions go un-answered when:1. the question is unclear, incomp ... Whirlpool ACC108PS Air Conditioner

Leak repair Samsung window air conditioner


You will have to repair the hole pull avaccum and refill with refrigerant ... Air Conditioners

I have a Goodman Air Conditioner Model CK49-1B. The fan in the unit does not turn on when the thermostate is set for cooling; the fan in the furnace works and blows warm air. Checking outside I discover that the dog chewed three wires that are coming from the unit. The repair person told me that the dog shortout the CONTACTOR and had to be replaced it, he also replaced 12 inches of wires damaged by the dog.. He did the job in less than one hour and charged me $225.00. Did he over charge me? Late


Take a look on amazon for same parts, and compare the prices: Amazon com goodman air conditioner parts. I hope this was helpful. Cheers ... Goodman CLQ36AR49 Air Conditioner

The fan for my air conditioner will not turn. When we cut the system on it makes a humming sound and the light go dim for just a moment and this goes on repeatedly. No heat or air. We have a dual system. One outside and the other is in the attic. Can you help. I am on a fixed income at this time and no money for a repair man.


If the humming noise is coming from the attic it would indicate that the blower motor on the air handler is trying to start but the rotor is locked.If the humming noise is coming from the outside unit and the fan runs but the compressor d ... Air Conditioners

I have a two year old central goodman air conditioner. The air out of the regrister is about 70 degrees I called repair and the man said that the freon and readings were ok. He thinks it might be in the evapoator coil. I also took off the side panel of the coil and measure the temp on the coil itself. One side was 57 degrees and the other side was 67 degree. What do you think the problm might be?


Hi, the repairman did check the freon pressures? You should have a T D of 18 to 25 degrees F. at the supply and return air vents for it to be right. This is a 3 ton unit. Yes, if it were low, you would have ice forming on the evaporator coil. He shou ... Goodman CLQ36AR49 Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific