Having problems with your Air Conditioners ?

I have a 1993 Model SRHF48U01A (The 0 might be a O (zero) When the thermostat calls for cooling, the inside unit (fan) starts up and continues to run but the outside unit wants to start (it comes on for a second and then trips the breaker that is located behind the outside unit. I can turn the breakers off that are inside the house and let them stay off for a short time and then reset the outside breaker and then turn the inside breakers on and the unit starts and continues to run until the te


Answers :

Well the trouble is surely at the compressor side. Dont know what kind of repair man you invited. He should have atleast diagnosed the problem. Following can be the causes
\015\012
\015\0121. Capacitor is slightly faulty (As you said). If the capacitor is fully defective, the compressor cannot start in any way possible. Also your compressor model maybe the one which runs without capacitor.
\015\012
\015\0122. Compressor is near the end of its service life. highly probable as the AC is nearly 17 years old. The motor in the compressor maybe getting stuck due to any reason.
\015\012
\015\0123. The unit is over charged with refrigerant gas, but i dont think you have charged it recently or did you?.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a 1993 Model SRHF48U01A (The 0 might be a O (zero) When the thermostat calls for cooling, the inside unit (fan) starts up and continues to run but the outside unit wants to start (it comes on for a second and then trips the breaker that is located behind the outside unit. I can turn the breakers off that are inside the house and let them stay off for a short time and then reset the outside breaker and then turn the inside breakers on and the unit starts and continues to run until the te


Well the trouble is surely at the compressor side. Dont know what kind of repair man you invited. He should have atleast diagnosed the problem. Following can be the causes\015\012\015\0121. Capacitor is slightly faulty (As you said). If t ... Amana Air Conditioners

I have a Goodman Heat Pump System. When I turn the thermostat up to call for heat the outside unit starts and the inside unit(Air Handler) starts. However the inside unit only runs for about one minute then shuts off while the outside unit continues to run normally? Any ideas?


... Goodman CLQ36AR49 Air Conditioner

Central Airconditioner Heat Pump Weather King Brand outside unit continues to run even when thermostat is disconnected from terminal block base. Have to flip ckt bkr off to turn unit off. Recently it even started up on its own without turning on the fan and started to ice the inside cooling fins. Thermostat is new and was doing same thing with old thermostat.


It sounds like you might have a short in the wiring that goes from the furnace (inside part) to the condenser (outside part). Follow these lines by hand and check to see the wire isn't damaged and shorting out. ... Air Conditioners

I wired the unitfrom the outside breaker box,on the inside unit i have a switch that cut the power to the unit and turns it on.when i turn that switch to on my unit started making noise like it trying to run so i turn my thermostat to on my heat acts like its coming on and then my transformer blows.this happen twice


It may be wiring is wrong.Make sure the ground goes to ground, and the other 2 , 110 volts each, go to correct contactor poles. ... Ruud UBHC Air Conditioner

My breaker trips when the outside unit tries to turn on. The inside furnace runs. I cut the inside unit off and the breaker doesn't trip. I manually turn on the outside unit by depressing the cont


Hello, there is a short to ground somewhere, check all the wiring from the inside un it to the outside unit and make sure nothing is touching metal. ... Goodman Air Conditioners

My A/C outside will not run, inside a fan is blowing air (a little cooler than the 82 degrees it is in here, but not cold). Unlike all the other posts I've read, my unit outside is not making any noise. I makes a click when I turn it on at the termostat 1 time and then nothing. All this started yesterday sometime, after the remains of TS Fay left us. Help. I tried the breaker thing and resetting the 240v box thing outside at the unit. Help.


I am not an a/c expert but mine did this one time and it was the transformer I think it is called pull the panel off and look for wires burnt at connections also. BE sure you cut power off before doing this ... Carrier 38CKC042 Air Conditioner

My air stops running inside before it get to the temp. Its set for but the outside unit keeps running and after a minute or two the air will start blowing inside again but the outside unit never turns off until it gets to the desired temp but because it stops and starts so often inside it takes a long time for it to reach the desired temp. Inside


You have a possible thermal overload problem in your furnace blower motor dirt will cause this problem when it doesnt allow air across the windings of the blower motor if not dirt the motors going bad and getting hot use a shop vac and eliminate dirt ... Goodman CKL36AR36 Air Conditioner

I have a goodman cpk j42 -1b ac unit on the outside and a central heat and air unit inside. the ac unit come on and runs fine but when it hit the temp the thermastat clicks and the fan outside goes of but the one inside stays running and will not turn off unless i hit the breaker. is it he fan relay at the outside ac unit?


Hello BWOOD Check the thermostat FAN button is in AUTO position not ON position.That might be it .The relay is in the blower unit but they RARELY become frozen/welded stuck on. ... Air Conditioners

Sometimes, when the inside blower shuts down, the outside compressor and fan motor continue to run for some time. Other times, when the inside fan motor is running, the outside fan and compressor motors are not ... if I press the outside reset button, it starts up When both inside fan motor and outside fan and compressor motors are running, it works fine ... warm air blows out of registers. Other than that problem, both units work great!


Sounds like you have a dirty condenser. You are going to need to disconnect the power at the outside unit on the wall by pulling the fuse block out. Take a good look at the louvered covers that are attached to the outside of the unit. Remove the scr ... Ruud UAKA060 Air Conditioner

The fan on the Ruud furnice unit runs all the time but the Ruud ac unit is not kicking on . I know nothing about any of this but would like some Ideas what I might check. I went outside and could not find any kind of breaker on the outside unit. I do have a breaker inside and I turned it off and waited then turned it back on ..no change...


Some Ruuds have a red rubber cap reset button on the bottom of the unit or inside. Usually the fan quits and trips the switch. Or look at the metal run cap with 3 leads on it, if it looks bulged(concave on top) and not flat and sunk in, replace tha ... Ruud Central System Air Conditioner

My unit is 4 years old. I always turn it off when I leave for work in the am and turn it back on when I get home in the pm. Last night I turned it on at 7:30pm. When I went to the front of the house about 45 minutes later, I noticed the unit outside was trying to turn on but would immediately turn off. I checked the breakers in the garage, turned them off and back on but still had the same problem. The fan inside the house is running but unit outside will not kick on. I looked for a magic


It could be a few things.. It could be the capacitor - which the most economical to replace first..\015\012\015\012If you are not really very mechanically inclined - get a trained pro to come out.. It is very dag ... Air Conditioners

A/C outside unit will not run. Inside works, breakers are on and did not trip. No noise coming from outside unit, except for low buz when 1st turned on. After 10 seconds, nothing. Goodman # CPLJ36 - 1B. No idea how old. Have tried turning breaker switches off and on. Has been 24 hours, just tried again . . . nothing happens but that short buzzing sound, a low beep, and then silence.


Sounds like your contactor/relay on compressor defective, by the way it sounds the buzz is from the magnetic coil on the contactor but its not pulling the contacts in to start the compressor ... Air Conditioners

I have a Goodman Split Air Conditioner and the outside condenser fan was not working. relay tested ok breaker wasnt tripped, then discovered 1 leg of the 220 line was out. Replaced the breaker, cleaned the unit turned it on, cooled the house 2 degrees then it stopped working. Turned the stat off ,pulled the 220 block waited 10 minutes, turned it back on and it is currently running. Can the relay and/or start-run cap behave in this kind of intermitent way ?


Run cap may be badthumbs up ... Air Conditioners

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


Nope, nope, sounds like a stuck contactor in the electrical compartment of the condenser, but there are actually several things that could cause it. ... Air Conditioners

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


If both fans runs (inside and outside), check if the compresor runs , if does probably the unit is low in freon and needs to be recharged after the freon leak has been fixed (remember this is a seal system and it shouldn't leak), but if the compresso ... Ruud UBHC Air Conditioner

My unit is running but not blowing cool air. I went outside and the condenor fan was not moving. Took a stick and shoved a blade and the fan started moving but the air is still not cool inside. I did notice the air coming through the unit outside after fan was blowing was cooler than my 2nd a/c unit that was working fine. I wondered if the entire unit was frozen. I turned off unit at thermostat and figured I would see what happens tomorrow


Sometimes on new units it is common for the fan to not start until you give it a push. Did you happen to hear if the compressor was operating? If the unit was froze-up the Insulated Suction line would also be iced over as well. If it wasn`t it is mor ... Carrier 38CKC024 Air Conditioner

Outside unit is running however it is not cooling.I cut off the circuit breaker wait 20 or so minutes and turn it back on and the unit works perfect for a while (no set amount of time ranges from hours to days) any ideas?It is a new unit and did the same thing when it was turned on for the first time.Worked 2 weeks before starting again.Unit is a little low on freon.It is a Goodman 3.5 ton ac only(gas furnace)


Sounds like there is a Freon leak and has been since it was installed and is going off on because of low charge, you will need to call a competent A/C repairer, more then likely the leak will be in the air handler, should cost under a $100 to fix. Go ... Goodman CKL42AR42 Air Conditioner

The outside unit keeps tripping the breaker. It will run for a few seconds, loud rumble, then stops, and does this for about five minutes before tripping the breaker. I just bought the house. The unit is about 8 yrs old. I pulled off the cover and the inside near the compressor is full of dirt. We had a bad storm with lighting the night the unit started acting up. Should I replace the capacitor or is my compressor bad?


There is a process to go thru for checking the unit to see which part is causing the problem. first thing, listen to the compressor when it first tries to start. if the compressor does nothing and the breaker trips then you will have to check the com ... Ruud UBHC Air Conditioner

My LG LSN182HE will not turn on using remote or the one button. I check fuses and breaker and they are fine. Power is coming into the inside unit but nothing happens when I push the power button. I turned it on AC mode and it started running. When I went back into the room later the unit was off.


You should check the condition of capacitor, there may be a small transformer inside the unit, check it for 24vac. If your problem still exists then you can contact with LG technical support at ... LG LS-K2430HL Heat Cool Mini Split Air Conditioner

NOT COOLING I AM HAVING A PROBLEM WITH THE UNIT. I HAVE WARM AIR BLOWING INSIDE, BUT WHEN I GO OUTSIDE TO CHECK THE UNIT THE FAN ON THE UNIT IS NOT RUNNING. I CHECKED THE BREAKER TO SEE IF IT WAS TRIPPED, BUT IT WAS FINE. I WENT BACK TO THE UNIT AND GOT REAL CLOSE TO IT. I CAN HEAR A LOW HUM NOISE AS IF POWER IS GOING TO IT, BUT THE FAN ON THE UNIT IS NOT TURNING. I PLACED MY HAND ON THE TOP CENTER OF THE UNIT, AND IT WAS REAL WARM. I DON'T KNOW WHAT THE PROBLEM IS. NEED HELP


A/c unit refrigerant charge is possibly low due to leakage, call a a/c engineer ! ... Air Conditioners

Throwing breaker When it is very, very hot, my Duotherm unit throws the breaker. Have replaced breaker, cleaned coils inside and outside. Have waited as long as 30 min and then turned back on; may run 5-10 minutes, then does it again. Have had AC repairman look at it and his only idea was to clean the coils.


Throwing the MAIN BREAKER should not happen. Calculate the distance to your main box. Tell me the wire gauge or breaker amperage. Whatever you do, do not get a larger breaker! If its a breaker on this unit Its probably doa with current leak possibly. ... Dometic Rooftop RV Air Conditioner

My 38CKCK24330 Unit stopped running, it will try and turn on every 10 or 15 mins you can here it outside buzz, I looked outside at the unit and the fan is not running. The system has power, the breaker switches are working, the furnace turns on fromt he attic. What do I need to trouble shoot, someone told me to check the switch on the unit by pressing it in to see if the fan will turn on once the button is pressed in. I did this but the fan did not turn on. Any help would be appreciated it, I


Hi angelagaddy,With the fan not running and you are hearing a buzzing noise outside this is more likely that the fan motor needs to be replaced or the capacitor ... Air Conditioners

My heat pump will not come on in HEAT or A/C. I thought I might have a simple defrost control board problem, but still no go after replacing the board and the defrost relay. I checked the pressure switch and it is not tripped. I've checked all the circuit breakers and they, too, are all set. I've checked the outside unit using the "test" switch inside on the start relay and the unit will come on, but won't stay running on it's own. When I select HEAT, I wait the necessary five minutes for the un


Hi; Need more info. How old is the equipment,look on the outside unit data plate it will give the built date usually in the top right corner. Also heat pumps can run with a faulty defrost board. I would check for control voltage at the secondary side ... Ruud UBHC Air Conditioner

Both inside and outside units start and run for about 10 minutes then both turn off for 30-40 mins or so. therm is set for 72. it is averaging 77 right now. it just does not run long enough to cool off the house


Check the thermostat accuracy try to set at65 and check the run time and the temperatureif it runs more than usual and the temperature decrease means that the thermostat is defective ... Air Conditioners

I have a RUDD AC 5 ton and the inside unit is running and blowing but the air is not cooling and the outside unit is not turning on. I checked all the breakers and tried pressing the reset button on the bottom. Is there a trick to pressing that button....nothing seems to be happening...do I need to hold it down for a certain amount of time? Thanks! It is getting hot in here....


Is the contacror pulled in? If not check the low voltage to see why it isn't, if it is, check for voltage out the other side with a meter. ... Ruud UBHC Air Conditioner