Having problems with your Air Conditioners ?

Ecu-Maxx Marine Air-Con. Compressor Load Fault Code (CLF) appears. Air Condition turns on but then after 2 minutes, I get the CLF code. Manuarl says it is Compressor Load Fault. How do I fix this?


Answers :

Clean the filter on the water pump. It may be clogged. Even if there is just a little bit of gunk in there it can cause this error.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Ecu-Maxx Marine Air-Con. Compressor Load Fault Code (CLF) appears. Air Condition turns on but then after 2 minutes, I get the CLF code. Manuarl says it is Compressor Load Fault. How do I fix this?


Clean the filter on the water pump. It may be clogged. Even if there is just a little bit of gunk in there it can cause this error. ... Air Conditioners

Cools for few minutes then stop cooling....Hi my unit GE (APH10AA) Air Conditioner, only cools for 10 minutes and then stops then is the fan that runs forever , with out getting to cool again,plus the back of the unit ,the vent takes out lots of VERY HOT AIR, my room will get so hot ,what I can do to fix it? please help


... GE APH10AA Air Conditioner

Hi, I have a 1.5 ton Coleman Central AC for almost 9 years now. The AC stopped cooling one day. The fan is still working, and I can still hear the compressor "compressing" but no cool air. Does that mean that it is not a compressor failure? A technician tried to put refrigerant into it, but it won't absorb. He still wasn't able to fix it. I just wanted to know if I should spend more money to get more technicians to try to fix this, or if this is a classic compressor failure problem, then


Hello,the problem of the AC system is a little thing that can be fix up in a little time the fan is OK and the compressor is also in good condition base on experience and also collection of date from your statement however, w ... Air Conditioners

My maytag M7D24E7A's compressor runs for 15 minutes and shuts off and doesn't come back on until we restart the air conditioner. How do we fix it so we don't have to restart the air conditioner every 15 minutes?


... Maytag M7D24E7A Air Conditioner

The PAC-260 runs for a few minutes, then I hear the compressor stop and it spews hot air. Pressing the reset button fixes the issue only to have it be reset again after a few minutes. Air filter is fine, the tubes are setup properly (ie. it is a straight run up and into the window). What am I missing, the reset button is supposed to be used when I figure out what is wrong, but I know it works (sort of) because when it works it still is very cold.


I had exactly the same problem. After some diagnosis I discovered that the water pump was not engaging so I checked the float switch, it was fine. \012\012A press of the red reset button turned the compressor back on for a few minutes but the ... DeLonghi Pinguino PAC-260 Air Conditioner

My 8 yr old Amana heat pump, model RHE48A2D with Honeywell progammable thermostat in heat mode has the blower running constantly. When there is a 6 to 8 degree differnce between room temp and thermostat setting compressor runs as it should, the closer it gets to thermostat setting, it will run about 30 seconds, blower continues to run until getting just cool air, about 5 minutes, compressor kicks back on for 30 sec., continues to do this, thermostat shows it has reached set temperature,


Hi, It sounds to me like what you are describing is, that when it is 6 to 8 or so degree difference then the stat says, unit operates as it is supposed to but then before it satisfies the t-stat, it shuts the compressor down long enough to start cool ... Air Conditioners

My m6po9s2a only blows fan air when i put on cool,the compressor clicks but does not blow cold air what soever it has a three minute cycle .every three minutes it clicks but does not get cold


It sounds like the compresor is trying to start but it can't ( it could be burned out or stuck) But before replacing the compresor put a booster in parallel with the capacitor ( is no more than $30) it will help the compresor to start ,if doesn't , i ... Maytag Portable Air Conditioner M6P09S2A

My unit's compressor will intermittantly stop working. The thermostat seems to keep the intake unit working but since it can't get the temperature down it never shuts off. We have been removing the batteries and letting the thermostat reset for 20 minutes. (thermostat Honeywell RTH23110B). After the reset the compressor will work again but will fault within a day. I am pretty sure that the compressor and fan are functional as if I press the contactor down it begans functioning. I also, to he


If the air handler coil is clogh , the air won't go through and the compresor will shut off on overload because of high head pressure, also this will happend if the condenser coil (outside) is blocked or if the fan dosn't work .Also if the outdoor un ... Air Conditioners

In my mitshubishi rosa coaster i got a air conditinor problem.it has a emergency red indicator at the AC switch.when i switch on AC it works for few minutes and the red indicator occurs and the AC compressor doesn't untill it gets start off for few minutes. after that the same thing happens.so would you plz heip me for that


... Mitsubishi Air Conditioners

My coleman 13,500 roof a/c year 2000 does not blow as cold as used to. I have cleaned the top condenser coils, with no help. It also at times will seem to pull a heavy load when I assume the compressor kicks in, very heavy that the generator bogs way down, then runs free, i believe the compressor is shutting down as cooling worsens, it was 85 outside and the coach continued to get warmer. The AC unit has shut down completely before, not sure why I waited 30 minutes and it restarted.


If the compressor started and stoped means \015\0121 thermostat need settings \015\0122 compressor over heated due to low suction pressure need to check and repair the leak then charge the freon ... Coleman Mach III Air Conditioner

Hi i have a friedrich model rm18j30-3 ac. the problem i am having is the fan does not turn on when i switch to hi/med/or low ac the compressor kicks on and the front of the ac get cold but no air blows out. and when i put it on fan only nothing happens.....is this a cheap fix? and can i fix it my self?


The switch is out of order. if yopu know, go to the junk yard get a used one put in, the part which you get must be same as yours. ... Friedrich Air Conditioners

I had a water leak. The fresh water runs right behind the compressor so it got hit. I was getting low AC voltage errors. Replaced the board and now get HP during air and CLF during heat. System was flushed and new circulation pump installed. Still happening. This is an ECU MAXX on a Rinker boat.


So you say you have the same problem, meaning it is still leaking water? Can you explain a little better where the leak is originating?ThanksTim ... Air Conditioners

Hello there. I have Friedrich wallmaster a.c ws16b30-a for about five years, a month ago it started not to cool enough, then i called service, the service guy cleaned the coil and recharged compresor with freon after finding that it was only 30% on freon. It worked good for about two weeks and now problem started again. Now compressor works for about a minute or two and than shuts-off releasin wery hot air on the back of unit and compressor itself gets very hot. Can somone tell me what kind of s


Hi,As it is already 5 years old, there could be many problems. Yes, freon is the main fault. Other than this, i would doubt freon leak. These AC's are more prone to freon air. I have no idea whether the repairman checked it for freon air. ... Friedrich WallMaster WS07A10D Air Conditioner

My Frigidaire FAC127S1A powers on but no air is coming out. It seems the fan isn't coming on and after a few minutes I get a burning smell. I've only had it two years and it was professionally installed so getting it out and putting it back in will be costly. Is there any way to fix this problem and will my warranty still cover it?


... Frigidaire FAC127S1A Air Conditioner

I have a DeLonghi CF210 and I'm getting the "E3 Fault" code on the main screen. It will not power up in Air Conditioning mode, but the fan mode will run. I saw where someone suggested it is a voltage problem, and have tried it in several outlets to no avail. This problem happened to me about a week ago and I turned it off for a while (10-20 minutes), then turned it back on and it worked again for a week before giving me the E3 Fault error today. I do not have the financial resources to sen


Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power ... DeLonghi CF210 Portable Air Conditioner

Our Mitsubishi FDC506HES ducted air conditioner keeps shutting off on hot and cold after about 10 minutes and flashes and the comes up with the error code E3.It will heat for those 10 monutes before it shuts down but it will not really cool at all. Please help. We cant afford to get someone to fix it. We just paid a guy to come and look at it $120 and still he said he didnt know and would have to contact Mitsubishi and get back to us. $120 for that. That was a good portion of our weekly budget G


Try to reset the error by disconnecting the circuit breaker for 10sec. and "on" again then operate the unit. But if wont work may there some parts that are defective that trigger the error E3. Replacement of pars is needed for this problem. ... Mitsubishi Air Conditioners

Window air conditioner cools (very icy cool air) for a minute or two then switches to fan. Will then stay on fan for about 10 minutes and then once again get "very cold", but only for a minute or two


Before I even read that far into your post, I was thinking "thermostat" replace it...It seems to be failing badly. If you take it into logical perspective...normally the unit gets turned on, then takes a bit to get cold, then once it reaches its pr ... Amana AH123E35AXAA 11,600 / 11,200 BTU Window Air Conditioner with 10,300 / 10,000 BTU Heat Pump,

I own an armstrong air unit after about 30 minutes the unit seems to get hot and the fan quits the compressor is still running I changed the motor on the fan and it still does the same thing I have also changed the braker and put in new wiring from the disconnect box to the unit. Please Help, Thanks Jimmy Watson


Chech the fans rotation , the fan is suppose to blow air out the top, also if you changed the fan out ,check for the blade on right, its suppose to scoop the air from the inside and blows it out the top,, also replace the capicator...sounds to me lik ... Air Conditioners

My 11 year old Friedrich WallMaster grinds for less than a minute trying to get the compressor to generate cold air. then it gives up. fan works fine. is it worth repairing or should i replace it?


Yes you need a capacitor or a hard start capacitor or a burnt wire somewhere by it or compressor ... Friedrich WallMaster WS07A10D Air Conditioner

I have a 5 TON Ruud split unit air conditioner.The Compressor was replaced last year.Now the unit works well for about 15 minutes and then stops cooling. Thermostat says,"In Recovery". What can I do to fix the problem?


May be due to improper refrigerant pressure; I would have it checked.\015\012\015\012'Recovery' is normally provided to allow high- and low-side pressures to return to a safe range before the unit is allowed to cycle again and yours is doing it ... Ruud Central System Air Conditioner

My Rudd Achiever 10 ran on air setting flawlessly this summer. Now that I am using heat, I have a problem. I get heat into the house; however, the outside unit keeps shutting down after a few minutes of service and I keep having to walk outside to the unit to press the reset button. Can I troublehoot and fix this on my own?


The reset button usually is related to refrigerant pressures, and should be checked by an epa certified technician. ... Ruud UBHC Air Conditioner

Not a GE unit. I charged unit with refrigerant and powered up unit. After running for @ a minute it shut off, having no power light at all. I found a set of wires reversed that were going to the outdoor unit. after fixing the wires i can't get the unit to come back on. The breaker is not popped and I assume there is some kind of fuse or overload that I have to manually reset or replace. It is a chinese (i think) made unit Air Control


Since most of these units, come precharged for line sets up to 125' in some models, the fact that you charged it, concerns me. Second you made no mention of the king valve, did you open it.\015\012 Then your diagnosis speaks to overvcharge, an ... GE Quiet-Aire Ductless Mini Split System Air Conditioner

I noticed some straining noise coming from my a/c unit today. The fan on top of the condenser runs fine but as soon as the compressor tries to kick on the fan stops for a split second and you get a kind of surging noise from the condenser unit. Then the fans kicks back on, the the process repeats itself every couple of minutes. Meanwhile no cold air is being produced inside the house. Any ideas?


You amy ahave a bvad capacitor on the outside unit. It starts the fan and the compressor. You can change this yourself. Open the outside panel and you will see a silver canister with terminals out the top. Replace this and I think your problem will g ... Goodman CKL24AR24 Air Conditioner

My goodman compressor fan isn't turning since breakers thrown in box. mfg CR34K6PFV220 could this be a silonoid or perhaps something blown in the unit I can fix??I can't seem to get the case off. I do have air blowing in vents, Hot Though!!!Thanks Lisa


Turn tsat off and try to turn fan blade with a screwdriver through the shroud on top if does not turn freely motor locked up. there is a capacitor in the electrical section usually round with three sets of wire terminals on top if top is is dome sha ... Ruud UBHC Air Conditioner

Bonaire heater not working I get fault code 07 when I reset it. reset icon comes up after a few minutes, cold air in blowing in


... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.2017 seconds