Good after noon i have a Starway Split Wall Mount Reverse Cycle Air Con. the problem i have is when i need to warm my house the air coming from the system is cold. even with the temp setting on the sun icon and set to 28 degrees it's still blowing cool air. kind regards Kerry Grace


Answers :

Hello,it is due to a bad thermostat,so sll you need to do is just to get a new thermostat and replace it with the bad one,after this is done you will then enjoy your air conditioner as normal,
wish you good luck,

take care.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Good after noon i have a Starway Split Wall Mount Reverse Cycle Air Con. the problem i have is when i need to warm my house the air coming from the system is cold. even with the temp setting on the sun icon and set to 28 degrees it's still blowing cool air. kind regards Kerry Grace


Hello,Examine the condenser. The condenser pushes the air and expels the warm \015\012air from the air condition to the house.\015\012Also check the fan heater on your system to see if it is functioning, because if it is not, it will circ ... Air Conditioners

Good after noon i have a Starway Split Wall Mount Reverse Cycle Air Con. the problem i have is when i need to warm my house the air coming from the system is cold. even with the temp setting on the sun icon and set to 28 degrees it's still blowing cool air. kind regards Kerry Grace


Hello,it is due to a bad thermostat,so sll you need to do is just to get a new thermostat and replace it with the bad one,after this is done you will then enjoy your air conditioner as normal,wish you good luck,take care. ... Air Conditioners

Bought this last year, and upon setting it up this year, it won't cool below 73, even though i have set temp at 60. i have tried turning it off at night, opening all the windows to let in 60 degree night air, then closing up house in the morning and setting temp to 60, but temp slowly rises throughout the day to 73 to 81, never getting any cooler - help!


Did you use it at all last year? My first impression is that it's just too small to use for your whole house... If this isn't the case, it may have lost some of it's refrigerant charge since last year, or may need the temp sensors service ... NewAir ACP-1000E Portable Air Conditioner

We are unsure of how to set our air conditioner on heating. I have it set on the 'sun' diagram and set temp to degrees however continues to blow out cool air. No manual available as was already installed when we purchased the house.


Get the make and model of your unit and check . The fixya service manuals and you can down load service manuals. Also go to product web site with model number and download manual, Rus ... Air Conditioners

Air conditioner I have a Honeywell air conditioner unit. For the last several days it has failed to cool down to the temp I set except at night. When I came in this evening it was 87 degrees in the house. I went to the main unit in the garage and flipped the fuse buttons to off and then back on. Then I dd the same at the main fuse box for the house. (Dont ask me why I thought this would help). Now I can't get the unit to turn on at all. Any ideas?


Yes, first turn your thermostat to the off position. Try to reset both fuse boxes again. If the ac comes back on problem solved, if not fuses and or breakers may need to be replaced.\015\012\015\012Let me know if this helps and we can go futher into ... Haier Energy Star ESA3183 Air Conditioner

Room temp 78 degrees with unit setting at 68 degrees. The unit is running (i.e. compressor) but unit not pumping out cold air. To be specific the unit is pushing out cool air just not cold with such a difference in room temp and temp setting. Any suggestions other than having an HVAC service contractor out.


Sounds like it could be low on freon I believe these units have about 1.5 pounds of freon in them and are critical in not undercharging or overcharging them if it is a freon 410 ac unit the pressures should be about 135 and both lines cold if is l ... LG LAN240HSV2-LAU240HSV2 24000 BTU 20 SEER Art Cool Ductless Heat Pump Air Conditioner

I have an electric furnace and heat pump that will at times blow only cold air during the heating season. I have checked the filter and don't believe that to be a problem. I usually have the temperature set to 74 degrees. When the outdoor temp. is extremely cold the axillary heat indicator will be on and still no heat. I can turn the heat pump off by switching to emergency heat and will get some heat from that but not as warm as I think it should be and even that will at times only blow cool


You are losing operation to your heat strips.\015\012\015\012In heat pumps, there is a secondary heat source. Usually electric heat strips. (Sometimes a gas furnace, this is known as a "dual fuel" system)\015\012\015\012The he ... Carrier Air Conditioners

In heat mode thermostat set for 68 and room temp on thermostat reads 68, but unit contines to run. The air coming through vents is cool air. Unit never shuts off, runs constantly. This is the case when outside temp is 30 degrees or 45 degrees.


Could be under sized unit or fan relay on unit. ... Goodman PHKJ024-1 Air Conditioner

Amcor 10,000BTU set at 64 degrees - - temperature of air coming out of unit is 72 degrees. In one and half hour set at 64 degrees the room temp only went from 90 degrees to 84 degrees. Recommendations? Recharge?


I am not sure, i have a similiar unit that is brand new, seems like a faulty mechanism from the maker, it starts cold for about 2-3 minutes and then shuts down condenser and blows hot air repeating this cycle. I don't believe it ias a recharge, just ... Amcor PLM-14000E Portable Air Conditioner

I have a Danby DPAC10030 air conditioner. It was working fine until yesterday, when we moved it to another room. Now it blows cold air for 5 minutes and then the air turns hot. The a/c motor continues to run even though the air is no longer blowing cold air. The current ambient temperature is 25 degrees C and I have the a/c set to cool to 17 degrees C. The timer has been turned off (0:00 on and 0:00 off). I noticed that the hoses (exhaust) feel quite hot. Not sure if that it normal within


Clean you filter and clean the area under the intake duck it will solve your problem ... Air Conditioners

I have a 18000btu LG mini split heat pump installed about 1 year ago in vacation home. In heat mode the unit cycles on and off when room temp is within 2-3 degrees of set point. Cycle on time varies between 35 to 60 seconds (sometimes more). The off time is 2-3 minutes. During this time, I check inside temp with accurate digital themometer mounted at the air intake of the unit and the temp does not change, assume because unit does not run long enough. When I put temp set point more than 3 d


Hello.I think they are on to something with shortcycling on temp sensor.I think it should be sampling the return air instead of (inside coils ?).A 2*f dead band use to be built in (factory installed) to thermostats to prevent on/off, but ... LG LS-L1210CL Mini Split Air Conditioner

I have a royal sovereign arp 1000es and when the room temp gets to 76 the machine thumps and stops blowing cold air. then when the temp rises again its starts to blow cold air, it does this even with the temp set at 72


... Air Conditioners

Our a/c-heat pump unit was replaced for our home. This unit throws hot air in the summer and cold air during the winter. We have called service techs numerous times and no one seems to find the issue. Currently we set the temp@ 76 degrees a/c and it says it's 85 degrees inside and blowing hot air. Please give me any suggestions??? Thanks


The issue is with the thermostat wiring. Depending on the heatpump, the Y1 wire is used to start the compressor, usually in the heating mode and the O wire operates the reversing valve, to bring on cooling. The crossed wire could be at the thermost ... Whirlwind FH-778 Air Conditioner

Hi. I have a Sanyo rcs-tm80bg heating and cooling system I my house BUT when the outside temp is very cold, say 2 degrees or less, it doesn't want to throw out hot air. The fan speed does what it wants no matter what speed I use. So, today I set for 24 degrees on high speed and I get a dribble of cold air. My room is freezing! Please help.


... Air Conditioners

I have a maytag nmpeb08f2a portable ac, just started it up for the season. cleaned the filters and coils by wiping down . I also emptied bottom resevior. Im not getting cold air when on cool setting, tried lowering temp all the way. when i turn it on it will be cold for a short time, doesnt fell cold like befor, the temp will go down maybe 1 degree then, no more cool air. can i add refrigerant to this unit?


Frank, refrigerant is what it needs, but it should be done by a pro. Unless you have experience with this sort of thing, it's not a DIY project, ... Maytag Portable Air Conditioner M6P09S2A

I have an Amana Air Command 90 Gas Furnace. It works and the heat will kick in when I set the thermostat to temps like 74, 75, 76 degrees. However, the unit will then shut off and the temp in the house drops and I'll wake up to it being 63, 64, 65 degrees, etc. Thoughts?


Ok try this. Take a small diameter wire about 6 inches long. Go down to the furnace and remove the bottom panel. locate where the thermostat wires go into your unit and with a small screw driver place the jumper wire the 6" one and place it on red ... Amana Air Conditioners

Our upstairs Central AC unit will not cool below 80 degrees. Everything is blowing fine. It is 89 degrees outside today. The air coming in thru the ducts is 80 degrees. The downstairs unit blows 70 degrees even if thermostat is set for 78. The unit is 6 years old. We cleaned the coils. No change. What should we check next? Thank you!


You will need a thermometer, you can use a meat therm.take a temp reading of the air going into the return and then coming out of the supply at the unit, it should be at least 15 to 20 degrees cooler in the supply, if not it may be low on refrigeran ... Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

I have a Dometic 15,000 btu, ducted air conditioner in my 30 ft fifth wheel. It seems like the unit has never cooled very efficiently. Dealer has checked out. I noticed yesterday, outside air over 100 degrees, that the air conditioner would put out good flow of cool air, but once in a while compressor would stop running even though not close to thermo setting. Fan would continue running. Any suggestions?


Not sure what the pressure sensor should ohm at but i would suspect a faulty sensor if everything else checks out. Its very common for these sensors to exhibit issues when they get hot. Also you may have a filter in the system that may be restricte ... Dometic Rooftop RV Air Conditioner

Hi, I have an Armstrong A/C that blows cool air when the outside temperature is around 75 even up to 77. When it goes hotter then it blows just air. Is there a setting that needs to be changed in order to get cool air when outside temp is greater than 80 ? or I should get a technician to check the A/C Thanks


It could be that the unit needs to be cleaned, it could\015\012be that the compressor is tripping on an internal overload because the internal part of the compressor\015\012is surrounded by high ambint air. It does not sound like a freon ... Air Conditioners

My 8 yr old Amana heat pump, model RHE48A2D with Honeywell progammable thermostat in heat mode has the blower running constantly. When there is a 6 to 8 degree differnce between room temp and thermostat setting compressor runs as it should, the closer it gets to thermostat setting, it will run about 30 seconds, blower continues to run until getting just cool air, about 5 minutes, compressor kicks back on for 30 sec., continues to do this, thermostat shows it has reached set temperature,


Hi, It sounds to me like what you are describing is, that when it is 6 to 8 or so degree difference then the stat says, unit operates as it is supposed to but then before it satisfies the t-stat, it shuts the compressor down long enough to start cool ... Air Conditioners

I have a new motorhome and the air conditioner only reduces the inside air temperature by 2 degrees on a hot day. e.g. outside air temp 26 degrees inside temp 29 degrees. After 2 hours of a/c running with door and windows shut inside air temp is 27 degrees. Dealer says the air conditioner is ok as air coming out of ducts is 3 degrees as required. I believe a larger a/c is required.


Can you tell me what size/make of motorhome you have? Certainly doesn"t sound right to me, and I've been working on them for over 15yrs. Whether it's a 13,500 BTU or 15,000 BTU, it should be plenty as long as motorhome has any insulation at all. I a ... Dometic Rooftop RV Air Conditioner

My upmc-030jaz runs continuously, it will be warm air for 20 mins then cold air for 2 hours, thermostat stays at the same temperature....or even declines a few degrees, but when reaches desired temp it will not shut off...techs have been here 5 times and keep replacing compressors...getting rather expensive....HELP! =(


... Ruud UPMC036 Air Conditioner

Fasdfas My Armstrong 80 furnace will work fine for about 10-20 minutes then turns off before reaching desired temperature. I sometimes have been toggling the thermostat set temperature to get the furnace to kick-on. Furnace does blow hot air. Example: My new thermostat reads 62 but is set for 70 degrees. When furnace kicks on, it only stays on for about 10-20 minutes and increases room temp to 65. I already cleaned the flame sensor which didn't seem to make a difference.


... Air Conditioners

We have a split system LG air con. Our local people cannot help us. The problem we have is that the unit seems to give off an offensive, unhealthy musky smell when not in use & also the temp when set at a certain degrees (eg. 23) within a few hours of use the temp drops to 19 deg or lower without lowering the controls.


There are two problems in your a/c. 1. Smell. 2. over freezing. The solution is 1.service the unit completely. 2. replace the room thermostat sensor. Sometimes, the room sensor may be working alright after servicing the unit. All the best. ... LG Air Conditioners