Having problems with your Air Conditioners ?

CARRIER HEATER AIR CONDITIONER MODEL 58PAV070-12 IS FLASHING A CODE THREE SHORT FLASHES AND THEN THREE LONG FLASHES. THERE IS 220 POWER TO THE OUTSIDE UNIT AND IT WILL START IF I PUSH THE SOLONOID AND MAKE THE CONTACTS TOUCH. THERE IS NO 24 VOLT SIGNAL TO ACTIVATE THE SOLONOID. IN AT THE FURNACE THERE IS NO 24 VOLTS ON THE CIRCUIT BOARD AT THE CONNECTION GOING TO THE OUTSIDE UNIT. THERE IS 26.5 VOLTS COMING FROM THE TRANSFORMER. WHAT TO DO NEXT?


Answers :

This means a high temp limit switch or flame roll\015\012 out switch has triped, check your air filter and clean or replace, than\015\012 watch unit when it runs and make sure the inducer motor is not slowing \015\012down or stopping.

The flame roll out, is the small safety switch\015\012 mounted above the main burners, if the flue pipe gets damaged or the \015\012inducer motor does not run at full speed the flames will try to come out\015\012 of the front of the furnace. This switch will shut down the gas.\015\012
5d1d14f.jpg

Have you checked your air filter to see if it is \015\012clean? your furnace is overheating a dirty filter can cause this. First open all vents and see if it runs longer\015\012 if not, than try this, turn your fan switch from auto to on. Than\015\012 turn on the heat and see if it runs longer.\015\012
Also, we can't rule a faulty circuit board (ie: bad \015\012connection at board).\015\012
\015\012Hope helps.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

CARRIER HEATER AIR CONDITIONER MODEL 58PAV070-12 IS FLASHING A CODE THREE SHORT FLASHES AND THEN THREE LONG FLASHES. THERE IS 220 POWER TO THE OUTSIDE UNIT AND IT WILL START IF I PUSH THE SOLONOID AND MAKE THE CONTACTS TOUCH. THERE IS NO 24 VOLT SIGNAL TO ACTIVATE THE SOLONOID. IN AT THE FURNACE THERE IS NO 24 VOLTS ON THE CIRCUIT BOARD AT THE CONNECTION GOING TO THE OUTSIDE UNIT. THERE IS 26.5 VOLTS COMING FROM THE TRANSFORMER. WHAT TO DO NEXT?


This means a high temp limit switch or flame roll\015\012 out switch has triped, check your air filter and clean or replace, than\015\012 watch unit when it runs and make sure the inducer motor is not slowing \015\012down or stopping.The ... Air Conditioners

I have a Carries Mod# 24ABR348G510 Condenser unit. The system start with a normal cycle for about Three min, I've timed this to be this way every time the system is started. After the Three minutes the contacts starts to chaters. The 24 volt control voltage is up and down the scale and the condenser unit thin stalls and shuts down? I have Twelve of these units to keep maintained. The head is to be OK and the system is clean and the Thermostat checks out to be OK.


Hi,Did you already check the exhaust or the motor unit, the possible that has problem on there was the electric contactor, this was the switch the make the main motor to power, if this one was faulty it will have a problem just like the o ... Air Conditioners

Intertherm gas furnace 80 % mod# MMHA-070ABHR-05 will not open gas valve and light <changed gas valve <control board<ignitor all three limits and still not working I have been in the hvac buisness for 10 years but cant solve this one ,the board is flashing a 3 code < i have called a fellow tech who had the same problem on the exact same model last year and he spent 10 hrs trying to repair this unit but was unsuccesfull also<i can make this furnace burn by wiring 24 volts direct t


... Intertherm Air Conditioners

Amana heat pump was working fine. Inside blower still working, outside condenser has 230 at contacts and 24 volts at time delay. unit will run if contacts pushed in by hand. high and low pressure switches are made. not sure about time delay, defrost board or defrost relay. i can by pass all the controls and it operates in cool mode for now. what five devices is most likely to be defective?


Time delay bad Tom ... Air Conditioners

I have a Goodman Air Conditioner Model CK49-1B. The fan in the unit does not turn on when the thermostate is set for cooling; the fan in the furnace works and blows warm air. Checking outside I discover that the dog chewed three wires that are coming from the unit. The repair person told me that the dog shortout the CONTACTOR and had to be replaced it, he also replaced 12 inches of wires damaged by the dog.. He did the job in less than one hour and charged me $225.00. Did he over charge me? Late


Take a look on amazon for same parts, and compare the prices: Amazon com goodman air conditioner parts. I hope this was helpful. Cheers ... Goodman CLQ36AR49 Air Conditioner

I have an APAC ducted reverse cycle air conditioner Sundowner 11 which keeps shuddering intermitently at the outside unit. I have had a service technician look at it and he has replaced three contacters in the unit and checked the thermostat. He does not what the fault is. He has also by passed the pressure switches to see if this sorts out the problem. But this did not work. he has also checked the board in the unit as well.


Listen to see if the contactors make a clicking noise when the fan starts to studder. If not, then it's not the signal to the contactors. If a clicking sound of the contactors can be heard, then the problem is the contactor coil dropping in and out ... Air Conditioners

I have an AR32-1 with an emergency heat switch on the thermostat. The heat pump runs and runs and runs and blows cold air when it's freezing outside. If I turn on the 'emergency heat', nothing happens. We do have three 220V breakers in the panel box. One is labeled 'heat pump', the other two are labeled 'furnace'. What could be wrong that the 'emergency heat' does not work?


... Goodman Air Conditioners

Ac unit clicks outside but nothing engages fan or compressor on unit furnace still runs for heat setting and fan still blows but ac will not engage just hear a clicking was running for three days this season but hasn't ran since


Have you check the outside breaker? If its ok then you got a problem in your electrical system inside the unit probably the contactor is not engaging this is where the 24 volts from the thermostat calls for the 240 volts to run the condenser fan and ... Carrier 38CKC048 Air Conditioner

OK I am a dumb A--. I did not turn the power off to my Payne PG9MAA Condensing Gas Furnace. Also A/C. In my futile attempt at relocating the thermostat. I 1. did not turn off the unit 2. I did not have enough wire so I spliced in a new longer one. 3. Voila' there is absolutely nothing on the thermostat showing power. I used the voltage regulator and put the contacts one on red and the other I went in sequence to all the other wires and it read 11.00 or so volts.. If I changed the (lead) or


Depends if its a 12 volt or 24 volt system and if your meter is reading right also check meter then check red wire if its a 12 volt thats what you should have and 24 so on or you have a dead short good luck with that one just be calm a go thru all t ... Air Conditioners

I am living in a home with a carrier furnace. The furnace is in the back part of the house in a store room. It has two- 2 1/2 inch plastic pipes. One that suppplies air to the furnace and the other is venting air out. Both picpes go though an outside wall. Also above the furnace in the ceiling of the room is an air supply vent bringing in outside air through an outside wall. Is there a purpose for having this second vent in the ceiling as it brings in so much cold air into the room & into the ho


As long as the fresh air intake pipe to the furnace is not plugged up the second vent is not needed some homes when they are new are air tight and need a fresh air circulation system ... Carrier Air Conditioners

Gas Furnace will not start when outside temperature rises to 50F


The anticipator basically prolongs or reduces the time from shut down to start up, so your furnace or air conditioner isn't cycling too much , off and on. It also will anticipate that the setting you have the thermostat set at is near, and will shut ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

Bryant furnace model 340mav. Furnace filter got extrey dirty due to updates in home. Started to freeze up. Caught it pretty early. Turned off unit. Thawed it out. Turned wl unit to off. Woke up in am. Furnace blower motor running. Code flashing red on furnace. Three quick red. Three longer red. Blower will not shut off unless I turn off manual switch


... Air Conditioners

The A/C unit control is powered from the 24 volt supply in a Ruud high efficiency furnace. The furnace fires up when the house thermostat is set for heating but there is no power in the line to the A/C unit when the thermostat is set to cool. The 24 volt transformer is delivering, and the fuse has not blown. Can you advise?


You will have to trace wiring. See where power starts and stops. Check to see if there are any fusible links in the wiring, or if there are any relays for A/C to wiring. ... Air Conditioners

I have a bryant out door unit heat pump 661cj030-a. I recently lost the 27vac transformer in the indoor unit. Replaced it and ran fine for 4 weeks. I lost the 27vac again but wasnt tranformer this time. Outside unti was holding the 27 volts down. I disconnected all outputs to logic bd on outside unit only leaving wires connected from inside unit. 27 volts held up. I started putting outputs back on. lost the 27volts when i connected defrost thermostat to logic bd. I ohmed out thermostat and it sh


... Air Conditioners

I want to find the transformer for the 36 volt inside unit. Is it in the inside unit or outside unit .I have no power to the inside unit however the outside unit has power,and the inside unit appears to be 36 volt


It's a 24v transformer. Your indoor unit houses the transformer for the outdoor unit. The outdoor has a low voltage (24v) supply running to it to push in the contactor for the outdoor unit to run. If your air handler inside has no power then it will ... Comfort-Aire HMC36AT-1 Air Conditioner

I am using my furnace for the first time this season. When turning my furnace on with the auto ignition, the gas come on the three pilots for about 10 - 20 secs with the flames, of course, then it goes off. Is this normal. I cant feel any heat coming from any of the vent in the rooms. When the flames on the three pilots comes on are they suppose to stay on, or do they suppose to intermitantly come on and off. What could be the problem


Hello,the flames should stay on. Check the blower?fan to see if that is running.It should come on 30-90sec after the burners light. ... Air Conditioners

I have a DuoTherm BriskAIr 13.5K BTU. The Dometic thermostat also controls my HydroFlame 8531-IV furnace. This morning, the furnace would not come on. I checked the wiring and there is no voltage at the thermostat blue wire on the furnace. If I jump 12 volts to the thermostat blue wire, the furnace works normally. Replaced thermostat; no change. I hear something clicking in the air conditioner unit when I switch the thermostat to furnace mode. I assume the A/C has a relay to control the thermost


If you look at control box at roof unit, they usually use a separate set of wires for furnace. See what colors they are attached to at harness to thermostat. Some just follow other harness, and come out at thermostat. (bypass control box) Once you've ... Dometic Rooftop RV Air Conditioner

My 1996 Motorhome Dometic 4 button Comfort Control suddenly does not recognize that the furnace is present. After wiring in a manual thermostat the Comfort Control suddenly recognizes the furnace. I take out the manual thermostat. I clean all the external contacts and then it continues to recognize the furnace thourgh about 15 test over 6 weeks. Pause 2 weeks and suddenly it does not recognize the furnace. What is going on. Could it be a sticky relay in the suburban Furnace?


... Dometic Air Conditioners

Have a Payne pg8uaa furnace. Furnace only works when I run a jumper between R and W. Replace wiring to furnace. I suspect that the outside blower motor is the problem. When furnace is running the blower motor has a humming sound but does not blow air. At this point, I would like to know how you would diagnose a Tjernlund HSUL-J blower motor. Should the motor itself be replaced or should the fan prover be replaced?


You would have to test the motor as well as the capacitor on the motor capacitor goes for alot less then the motor though.here is the pdf manual on your blower h ... Air Conditioners

I have a three year old Goodman Furnac /AC unit Model nuber CAPF030B2C. When I turn on the AC it blows a 3 Amp blade fuse in the furnace. If I just turn the furnace on or the fan only on it does not blow. What should I check for?


I would first look at all the wires and make sure the insulation has not rubbed off somewhere and causing a short, after that it means one component is failing and requires special tools and testing that should be done bu expert who has those tools a ... Air Conditioners

Mitsubishi Mr Slim: Hi, I read your response to a question from someone who had a Mr Slim that was leaking inside their house. I have the same problem. In your response you said to locate the drainage pipe and blow into it to clear it. Could you elaborate? I have three Mr Slim units in my house but only one is leaking. The outside condenser has six hoses or pipes leading into it, I assume three are air and three are for drainage. Is there any way of figuring out which is which? and once I


There should be a clear or white pipe comming out of the back of the wall hung unit. ... Air Conditioners

I have a split system air conditioner. the inside fan turns on fine but the out door will not. i pushed the contactor in (located at the outdoor fan)that seems to turn on the fan. i measured the voltage with multimeter across the contact 24 volt side and got low voltage reading. then i disconnected the wires to the 24 volt side of the contactor and measured the wires, the wires read 24-27 volts. i dont know why when i connect it the readings are low. i even got a new contactor and still the same


Contactor working means fan might be bad can you feel any resistance from fan or bad capacitor. ... LG LSC091PMA Split System Air Conditioner

Leaking Mitsubishi Mr Slim: I read a response to a question from someone who had a Mr Slim that was leaking inside their house. I have the same problem. In the posted response the person was told that their drainage pipe was probably blocked and they should locate the drainage pipe and blow into it to clear it. Could anyone elaborate? I have three Mr Slim units in my house but only one is leaking. The outside condenser has six hoses or pipes leading into it, I assume three are air and three are


Hello my name is Heath it will be my pleasure to assist you. The drain line shouldn't be hooked to the condenser. It will run from the bottom of the unit either to a drain in the house or to a pump that will pump the water to a drain. If you pull the ... Air Conditioners

Central air seems to be working fine except for the outside unit fan stays on all the time. The line to the outside compressor also drips condensation from the furnace all along the basement to the outside wall.


Alot of humidity in the basement will cause the dripping need dehumidifier ... Air Conditioners

My ac unit does not have power to the thermostat. There is 200 volts going into the transformer and 24 volts going out. There is 24 volts on the back side of a terminal with thermostat wire running to the thermostat and the outside AC unit. However, no power on the front side of this terminal and therefor no power to the thermostat.


Please exercise due caution in checking voltages in live circuits!24 volts sourced by the transformer, through the thermostat, then through the contactor (turns on power to compressor/fan) and returns to the transformer, If the thermostat ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific