Gas furnance would only operate for about 3-5 minutes then turn off. Replaced gas valve on furance for a Rudd comerical A/C 4 ton unit model UKKA-A048JK10E. Now the blower fan turns on but the igniator and gas does not come on as before. LED light (flashes 5 times) on board indicates flame roll out switch is open. Need manual to locate roll out switch, does it have a reset button or does it need to be replaced?


Answers :

The rollout switches will be located at the ends of the burner assembly and will have a manual reset. they must be manually reset to ensure that the problem has been corrected. Most units will go into a soft lockout for a time and eventually a hard lockout if the problem persists. Go to tempstar.com and go to their troubleshooting section for a gas furnace. the codes they give are pretty common for alot of furnaces and see if they help

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Gas furnance would only operate for about 3-5 minutes then turn off. Replaced gas valve on furance for a Rudd comerical A/C 4 ton unit model UKKA-A048JK10E. Now the blower fan turns on but the igniator and gas does not come on as before. LED light (flashes 5 times) on board indicates flame roll out switch is open. Need manual to locate roll out switch, does it have a reset button or does it need to be replaced?


The rollout switches will be located at the ends of the burner assembly and will have a manual reset. they must be manually reset to ensure that the problem has been corrected. Most units will go into a soft lockout for a time and eventually a hard l ... Ruud UAKA042 Air Conditioner

I have a Sta Rite Max E Therm pool heater and when I start the unit, the fan kicks on but the heater never does. After 45 seconds or so, I get a " Service Heater" light. The circuit board had leds for limit switch, pressure switch, air sensors, etc, but none are lit. The ignition contol module has a blinking red led which the manual says is a "ignition lockout" issue. What is an ignition lockout? Do I need to replace the HSI Ignitor? Or could it be something other than ignitor? Thanks


Hi,How many times that light is blinking?Is it 3 times sequence?Let me know,so that we could proceed.Thanks!! ... Air Conditioners

We have a residential Lochinvar Solution Boiler (model RBN090). Around 7 years old. For past 2 weeks pilot light keeps going out. 2 repairmen have come out. We have replaced the Gas regulator, the roll out switch, the thermocouple, and the pilot flame on the thermocouple. Pilot light continues to go out. No one has anwser. Pilot flame goes out sometimes when system is cold, other times after working for several hours and hot. Very random. But we have to relight serveral times per day a


... Air Conditioners

The light fixture needed to be repaired. It never worked when I bought the house. New light bulbs didn't worked. I replaced the two ceramic light switches that had corroded wiring and reconnected blue to black and white to white. I have a dual wall switch that controls the fan and light. Now the light only works when the fan is on. The light on my other identical fan works without the fan on. Is the wiring problem in the fan or switch. The switches are different.


If its a duel switch that controls lights, and the fan seperately. sounds like the power for the lights is going directly to the fan, and therefore making the lights work also. also check out switch, make sure power is only going to the lights, with ... Air Conditioners

The flame on my majestic gas fireplace will suddenly (and seemingly without cause) extinguish itself with no lingering smell of gas while the pilot light remains lit. At times, the flame will re-light with no intervention and, at other times, it will remain off for quite some time all the while with the electrical off/on switch being in the "on" position. Believing it is some type of an electrical issue, I replaced the off/on switch last night and the flame turned on immediately and rema


Hello\015\012Sounds like the thermocouple is bad.\015\012\015\012The thermocouple is a 1 to 2 inch metal tube located near the pilot lite with a very thin metal tube leading back to the gas valve which it is held into by a compressi ... Air Conditioners

I have a Casablanca Ceiling Fan (Model 652T) from 1980. It works well except that the pull chain switch has broken and needs to be replaced. The switch has a pull chain and 3 lead wires and is marked "Leviton 689, 3A-250V 6A-125V-T". The Leviton catalog shows a model 1689-50 2 circuit, 4 position single pole pull chain switch. Is that the correct one?? I need this switch to turn the fan on and off and the light on and off. Thank you, Eric Steele


The switch will work ,there are a lot of universal ones out there . but a fan speed switch can't work the lite also ... Air Conditioners

I have a dayton furnace with a honeywell vr8440p-2088 gas control. The ignition works fine but the problem is I am getting no gas it seems to light the pilot. I checked the orifices at the end of the pilot gas tube and could see light thru it so it was not blocked. Could this mean I would need to replace the gas valve completely? Any help appreciated [email protected]


Actually, after exhaustive troubleshooting and testing, all testing told me the gas valve was defective. I then replaced it. Problem was still there. I then took a shot for what it was worth and went down to purchase a new thermocouple to sense the p ... Honeywell Air Conditioners

My Airworks ceiling fan with remote stopped working. With Room light switch in 'on' position, remote no longer turns light on or controls fan speeds. Changed 9-volt battery but did not make a difference. In the compartment where 9-volt battery sits there is a small switch that has 4 tiny switches. Are these for any particular function of the ceiling fan? If it was only the bulb that needs replacement why should not the remote control the fan operation? Can you help or make suggestions to try?


... Air Conditioners

I have a Rheem RGDA-100A-AR gas furnace, and I believe the pilot light is out and needs to be re-lit, but I'm not sure where it is. Any ideas where it might be or what it might look like? And do I have to light it with a match? The instructions on the inside of the cover just say to "light it" while depressing the manual gas switch in the Pilot position.


Hello and thanks for inquiring. Take the front covers off the inside unit. This is where you will find the Gas Valve. Next locate the pilot assembly. This can be done by following the thermocouple from the gas valve to the end where you will see a li ... Air Conditioners

I have a Lennox pulse 21 furnace. It will not turn on when I turn it to cool or heat. I checked the main computer module and the LED light is off. I had reset the furnace by using the switch next to the furnace, and this will not turn on the light. Is there anything else I need to check before I call a service tech to look at the main module? The switch to turn on and off the furnace with the removal of the bottom door may be bad. Is there anyway to check this?


The switch you are talking about can be checked. Turn power off to unit. Disconnect wires on both terminals of this door switch. Next use a meter that will show Ohms or just connectivity to see if switch is closed when pressed all the way in. You cou ... Air Conditioners

Sometimes my Silhouette doesn't start and then I flip the emergency on off switch. It starts up, igniter lights, gas blows, lights up and then clicks off and cold air blows. After the 3rd time the cycle completes itself and we get heat. We replaced the safety temp switch and it worked great for about 3 months. and it's starting to happen again.


... Ruud Air Conditioners

Rheem-Gas Furnace I have a gas furnace that will not ignite. I have attempted many times to start/ignite it using the manual suggested sequence, and I have been unsucessful. In diagnosing the problem(s) the technicial manual flowchart suggests that I replace the vent pressure switch. How do I not know I need to replace the igniter. What tests can I do to ensure it is.If I let a proffessional trained technician perform the work, How much should I expect to spend?


It may be a little difficult to diagnose if you don't have a volt/ohm meter to check the switches with, but I will try to help what I can.\015\012\015\012The first thing to check is the pressure hose from the vent fan to the pressure swit ... Air Conditioners

I have an amana dual fuel heat pump with LP gas furnace. the furnace will not light. the ignitor heats up, acts like it's not getting LP to the burner and i don't get 24 volts to the pressure switch just above the gas valve, or to the gas valve itself. i cut the power to the unit, removed pintle to the gas valve to ck for gas to the valve and it's o.k.,. what do i need to check next, i don't know how to get codes out of self diagnostic system and don't know if these codes would effect the furnac


... Amana Air Conditioners

I am trying to find information on re-lighting my pilot light on my honeywell day and night furnace. I see switch for blower is off, pilot dial is on "pilot". Blowers not active and pilot light not lit. I think I just need to turn pilot dial to off to reset and leave for 5 minutes and turn back to "pilot" and re-light, before turning everything back on. I'm not sure where the gas is coming out of. Is it right above the dial. I have long matches to use. Please let me know. Thanks for you


Without knowing exactly who the manufacturer is and the model number of the furnace, most of us really don't want to reply to this question, for fear of you blowing yourself up. So, if you can provide that information, I'm sure one us can help you. ... Air Conditioners

I have a GMP100 gas furnace. I need the diagnostics table that provides the meaning of the status light states. I get flame for 20 seconds and then the gas is shut off and LED on control board blinks 3 times. The flame sensor looks clean. I wired the flame sensor lead to ground as a quick test but then the gas goes out in 6-7 seconds. Any thoughts?


Hi!!! you just answer your question.change your flame sensor cleaning it wont work..\015\012\015\012\015\012 ... Air Conditioners

A 2 month old Goodman GMH95 natural gas furnace has been working properly until tonight. Now it starts up properly, but after 30 seconds (and right when the cirulator fan kicks on) it shuts the gas valve stopping the flame. LED light flashes 8 times, which is not an option on the trouble shooting guide. Unit will retry every few minutes and cycles this way over and over. It appears the control module is not receiving the gas flame detection signal. What do we need to do?


Goodman's control boards are very sensitive as well as the connections to the gas valves. Check the wires and make sure they are snug and tight. With it being only 2 months old, I doubt the board is bad or the flame sensor(unless it is a used syste ... Air Conditioners

Air ease enhanced furnace has flashing red led light/ diagnostic code is pressure switch, roll out switch, or aux, limit switch open with inducer on.


... Air Conditioners

I have a old Bryant city gas heater combination air conditioner model no 80 v 393 u. Series SE C. serial no 44N 77879 about 1968 year and need wireing diagram .The safety limit switch is not working and there is no number to buy new replacement switch. Do you have the diagram or the number of the switch or where to buy it ??? Thanks [email protected]


Email me a photo of the part:[email protected] ... Bryant Air Conditioners

We just installed a brand new haier 40,000 btu gas upflow furnace. Followed all the instructions to a T. With the power and gas turned on, we turn the thermostat on. The inducer motor turns on. The LED light is solid green for about 30 seconds. Then it starts blinking twice, over and over again. The manual says that this is because the pressure switch does not close within 30 seconds of inducer energized. It does not tell us how to fix this problem. Please explain how to fix the proble


This means that the pressure is not building up so that the furnace can work properly. Please check the natural gas line for switches and turn them on. When you installed the furnace, the gas had to be turned off so maybe you forgot it that way. ... Haier Air Conditioners

I have spark, I have gas, the fan is working, but will not light. Am I supposed to be using a propane regulator for this heater, or just direct from propane to inlet on the unit..... the solonoid is opening to allow the gas flow, spark is working for a short time after turning the switch on, just not firing.... do you think I need a new igniter, if so, where can I purchase one..... I would like to get a owner's manual for this unit.... thanks


Look 4 the brand name on unit and google it and i bet u will find all the info u need ... Air Conditioners

I have a Goodman (AR24-1) unit, the heating is electric not gas. How do I test the blower motor with out removing it. I have a part number but not sure if it is the blower motor number or not. Part number 15212-50. (1.5 AMP 1/5 HP) 208/204 Volts) I have replaced the capacitor today but still did not start when I have the Fan switch turned on. I have checked the thermostat. Any way to check the motor? The switch board number is ( # Goodman B1370735) I can test it with my meter if needed.


... Goodman CKL24AR24 Air Conditioner

Rheem Criterion II gas furnace, model RGLH, 8 - 10 years old. Came back from vacation and furnace won't fire up. Went through start-up procedure. Brand new digital thermostat, maybe one month old, been working perfectly, replaced batteries in in anyway to no avail. On motherboard, two green lights (LEDs) comes on, but 'flame' LED (orange) won't come on.


... Air Conditioners

Gas heat does not always come on when it is switched on, when it does it works fine when it does not, the house is filled with a bad smell, I'm assuming unused gas. we have had the burners scrubbed with a wire brush before and no problems for 2 years. Can the burners just be replaced? Pilot light works fine. The furnace tries to come on, i can hear it clicking to ignite. Thanks Ronnie from Atlanta


You need to check gas vent ASAP. You should not be getting any odors from your furnace. Have a technician check your furnace. Could have hole in Heat exchanger. If so you and anyone else there are in danger. Please do not operate till it has been che ... Air Conditioners

I have a mitsubishi air conditioning unit model MUH-12v. The fan on the machine outside has stopped and of course inside the air is not cold. Could this be a problem with replacing the gas or could it be a technical problem with the outdoor unit. Also I have noticed when I switch on the unit on the inside with the remote control that instead of two green lights comimg on I only have one green light flashing. Does that mean anything?


Hi,Here is a tip about Mitsubishi Air Conditioners and how to get the manuals for all of the mitsubishi line. The manual include both troubleshooting and installation. ... Air Conditioners

I have a mobile home furnace Intertherm #1378. The pilot light is on, but the burner will not light. The thermostat clicks on and everything seems to be running properly, but there is no flame. Last year I had the motor replaced and the relay switch. What could be wrong? Is there a gas valve that is not opening properly.


First make sure that the gas valve is in the on position. There is a spring load diaphragm that will stick when not in use over time, When the t-stat clicks on for heat tap the valve with a hammer L ... Intertherm Air Conditioners