Having problems with your Air Conditioners ?

Blows cold air when heat is on. I just cleaned the filter and reset the button on the surge protector. Digital display and blower both work fine, but makes no hot air when the heat is on


Answers :

AMP TEST THE HEAT ELEMENTS , SEEM LIKE A BAD ELEMENTS

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Blows cold air when heat is on. I just cleaned the filter and reset the button on the surge protector. Digital display and blower both work fine, but makes no hot air when the heat is on


AMP TEST THE HEAT ELEMENTS , SEEM LIKE A BAD ELEMENTS ... Amana PTC153B50AM Split System Air Conditioner

At 30,000 miles my then 8 or 9 month old chevy 2500hd 4wd pickup truck air conditioning started blowing hot air on the driver side (the passenger side was still cold). I turned the truck off and back on and it began blowing normally for a few days and then it would do it again. A year or so later the heat on the driver side went out totally (passenger side worked properly). So now the driver side blows cold air constantly. A few months after that the blower quit working all together. Now at 185,


What year truck is this? This is actually a very very common problem on those chevy trucks. Most times it is the door blend actuator that has failed. and the default for this failure is driver side blowing hot. There are a million posts out there on ... Air Conditioners

I have an old RUUD central AC unit that started blowing hot air. I set the thermostat to off and set the temp gage higher than air temp to turn the unit off and save money, but inside blower unit runs constantly. I'm trying to save money to have it serviced, but noticed my electric bill was higher that last month when the ac was working. The bill was about 4 times higher than the winter when ac is off and the gas heat kicks in. Can the blower running constantly cause this power usage and what is


HelloOkay did you check your thermostat to see if you have the fan switch on auto? The switch must be on auto or the fan will continue to run. If the thermostat fan switch is on auto then there is a malfunction in the thermostat probably ... Air Conditioners

Heating Hi we can't get our system to work on heating, we just brought this house and moved in yesterday, put it on heating and its making a noise but no hot air


... Sanyo Split System Air Conditioner

ENGLAND, UK. DOMESTIC HOUSE CENTRAL HEATING Baxi Bermuda. i recently fitted a thermestate valve on one of my radiators (the only one that didn't have one, but it was so hot) it works fine but since I have turned it all back on i had air in the system, that makes a loud whirling sound in the boiler. We have an old back-boiler system (behind the fireplace). I have bled the radiators many times since... We have a tank in the loft which feeds the system and a hot water tank in one of the bedrooms


The air in the system has been introduced when the TRV (Thermostatic Radiator Valve) was fitted, and offering suggestions to solve the overall air leakage problem is difficult without examining the system layout. Difficult to clear air pockets are of ... Air Conditioners

My Goodman air handler RELAY, ELECTRONIC BLOWER TIME DELAY makes a clicking noise 4 or 5 five cycles (about 10+ Sec delay ) before the squirrel cage fan will come/stay on. I have reset the unit by switch it off for 5 minutes then back on and it worked for a week but now it makes the outside compressor go on and off the same number of cycles before it comes on. Do I need a new board or can the capacitor cause this problem? Help it's hot in Phoenix!


When this happens turn off power and feel motor if hot capicitor i dont think this board cost much but if it does you can get a fan sequenseing stack switch to repace the board with ... Air Conditioners

My carver 4000 fanmaster does not heat up properly on the electric, the blower works fine but no hot air!! Phil


... Air Conditioners

I have a weather king model 90RJ - first time I've had hot air heat..When I turn on the heat, the blower turns on right away ( blowing cold air) - I understand that the ducts have to cleared of the cold air - but shouldn't the blower turn off until the air is warmed to temp thanks Bob


When the furnace first comes on there is a induced draft motor that should come on first but that forces air up the exhaust or flue,not into supply air on ductwork. It is not unusual for cold air to be blown out when burner first turns blower motor o ... Weather King 10AJA3001AH Air Conditioner

I have 2 kickboard heaters in the baseboards under the cupboards in the kitchen (Smith SS7's). They are run off the hot water central heating circuit. The fan in each unit is supposed to click on to blow hot air from the heat exchanger when the temperature falls. Both units have stopped working - when one stopped the other worked intermittently for a few weeks but now this does not come on either. I have bled both units and if I keep doing this then eventually hot water reaches both but the flo


Does your heating system have zone control valves? if so make sure they are opening with kitchen t-stat. sounds like the boiler pump is not able to flow water to the units. might be a zone control problem. ... Air Conditioners

I have a vitodens 100-w combi boiler and tried to turn the heating on just to give it a working as was advised. However, I have no heat coming to my radiators. The boilers seems to be working as my hot water is fine and no fault displays are being displayed. Have turned it off at the mains and restarted it, but has done no good. Any ideas?


Here's the deal: If your Vitodens 100 has outdoor temperature sensing capability, either built in or via external aftermarket control such as Tekmar or other, and the temperature outside is above warm weather shut down (WWSD), then the boiler will no ... Air Conditioners

Goodman model E3EB-020H central heat and air blower was replaced 8 months ago the air works fine but when switched over to heat the core comes on but the blower doesn't and I have an exposed yellow wire with no idea where it supposed to be attached to.


Yellow wire where? in thermostat or blower contactor? Write clearly. ... Air Conditioners

Crazy Heat I have a Dometic Duo-Therm Ducted air conditioner with a analog stat. Some times in order to make the heat work I have to: set the stat to cool and set it to the lowest temp setting. Then I set the stat to heat and a desired temp.The heat works fine as long as I leave it on heat. If I just set the stat to heat it does not do anything. This is a nine year old unit. This does not happen all the time. It seem it is getting worse. It happens more often now. Dometic said to replace the sta


I think that I would change out the thermostat only due to the symptoms you are describing. Think the control board may be fine however, the thermostat sounds as if the internal componants are going out. Good luck on your repairs\015\012 ... Dometic Rooftop RV Air Conditioner

The heat pump is not working properly. i think the problem is in the switch mechanism. when the heat is on and the thermostat is turned up it blows cold air. sometimes the compressor turns on and off. if you turn the other switch to the off position, then turn the thermostat up then turn it back to heat. it will blow hot air. if you then turn the thermostat down, wait till it turns off, then turn it back up, it will blow room temp air and sometimes the compressor will turn on.


Hi,\012The problem may be the switch, but it sounds more likely that the contactor in the outdoor unit is bad and is not making all of the time...then the compressor will not always run...\012To figure it out you will need to catch it at ... Air Conditioners

Intermittent heat I have a Carrier (Payne) unit (FA4ANF030) with intermittent heat output. The air works as does the fan when in heat mode, but usually no heat. Sometimes it will suddenly begin to put out heat normally and will function fine...until it doesn't. The thermostat was old, so I replaced it first. Seems to make no difference at all since it works exactly as before.


Check wiring of heater, it may have loosed connection or corroded connection. ... Air Conditioners

My carrier A/C YHB243D this window unit was working find. But about one week ago only blows out cold air and sometimes only hot air but now it blows only regular air, and doesn't work nither the cool or heat air. what could be wrong with it?_a) could be- the thermostate that goest at it front with its condenser unit? b) could be the whole temperature switch ? or what else can be its problem, please help! and tell me where I can get the replacement part


... Carrier Air Conditioners

Hi guys, i have a portable air conditioner 9000btu 'ariagel ag90' window) that works great for the first 5 minutes, until gradually the unit makes more and more noise until it shudders quite violently , returns to its normal noise and blows out hot air for 5 minutes. This hot air seems enough to cancel out the cooling it does. then after a while it cools gradually I've read alot about this air con problem, but nothing regarding the gradual noise and shudder. The slide out filter at the back s


This is due to the compressor going into thermal overload, It can be cause by really dirty coils preventing air flow,A restriction in the cap tubes or orafice, Or an over or under charge in the system.The noise is due to the compressor building up to ... Air Conditioners

My Mistral MSS25 dosn't blow hot air and makes a whistle noise when it's trying to heat up and when you turn it off? Any idea what the problem would be? It does heat the air but only to about


... Air Conditioners

I have a new Rheem heat pump. The cooling works fine but won't blow hot air in HEAT setting. I have reset the breakers for heat pump and air handler, changed filters and pulled batteries and reset the Braeburn 3000 thermostat. Still blows cold.... Any other suggestions?


If this is indeed a heat pump you rthermostat should also have a emergency heat setting does it work on that setting... a heat pump on heat wuns the outside unit and has a recersing valve that changes the refigerant flow ..is the outside runnigndurin ... Air Conditioners

I have an air conditioner Appliance AAC 1100 A-PTC that wos working for two days and now its not cooling or heating:-( Both outer and inner parts of the machine seems to be running but it wont heat or cool the room. When i try to turn it on there is a red symbol that lights up on the display (defrosting) this light goes off every 5 minutes or so,then the machine starts to blow air (not heated or cooled) for aprox 20 seconds then the red light comes on again and this procedure starts over again.


... Air Conditioners

My air conditioner will not turn on. (See below for a more detailed description.) I recently bought a used Kenmore Room Air Conditioner Model 580. 76129. It worked well for about a month (running almost continuously, usually on either energy saver or cool). About a week ago, I walked out of my room when the air conditioner was on, and it was off when I walked back in about an hour later. (The display was unlit, and it was not making noise.) The power button still does not work. The outlet


If you have a GFCI plug on A/C unit it may need to be reset at the plug. ... Kenmore 76129 Air Conditioner

The heat work blower works but the air conditioning blower will not work


... Intertherm P3RA-048K Air Conditioner

I have an inwall Friedrich Heating and a/c unit. The blower for the heat comes on but blows cold air. The a/c side blower does not work at all. Both happened about the same time. Related? Why not heat and no fan.


HI\015\012most boards have a small 3 or 5 amp fuse on the board it looks just like a car fuse. do not put in wrong size fuse it can allow damage to the board. ... Air Conditioners

I turn the thermostat down at night. When I get up in the morning I turn it back up. The heat kicks on for a minute or two then the unit starts blowing colder air. If I turn the thermostat to the OFF position, wait until I hear all blowers stop, then turn it back to the ON position, it will start blowing HOT air again. Some times I have to perform this cycle 3 times to get it to keep blowing hot air. Any ideas as to what is shutting the furnace off? Thanks, Wayne


Theremostat switch problem. Replace it. ... Air Conditioners

A/C was working fine a few hours ago, but now is blowing hot air on the cool setting. Blower comes on and stays on, but hot air is blowing. Unit is in a residential home. Whirlpool Air Handler model WAHM236A00-1P. 36,000 BTUH


... Air Conditioners

My heat unit will not blow hot air unless we go outside and hit a button on the back bottom of the unit. Once we do that it will blow hot air for that cycle. when it is time for it to come on it is cold air again and the unit outside is not working.


If it does not have a furnace or heating elements for heating, then it is a heat pump, which is rare for a central AC system, but makes sense of the fact that it blows warm air when you reset the pressure switch, which may indicates freon pressure ch ... Ruud Central System Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific