Having problems with your Air Conditioners ?

I have a Royal Sovereign Portable AC/Heater ARP-5012xh and cannot find any info regarding my problem. Here's the deal: When in "heat" mode, the unit will turn off and on several times before finally turning off for several minutes before turning back on (and off...). I did manage to get it to stay on for a few minutes, but no air was coming out of the front vent although there was airflow from both of the rear vent hoses. I checked the drain - empty. I checked the vent hoses - clear of obstr


Answers :

Make sure there is no obstruction anywhere on either coil,and the fan is turning,and turning the right way,I believe the fan turns in the opposite direction for heat.If this does not work,freon would be needed,even for the heat.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Royal Sovereign Portable AC/Heater ARP-5012xh and cannot find any info regarding my problem. Here's the deal: When in "heat" mode, the unit will turn off and on several times before finally turning off for several minutes before turning back on (and off...). I did manage to get it to stay on for a few minutes, but no air was coming out of the front vent although there was airflow from both of the rear vent hoses. I checked the drain - empty. I checked the vent hoses - clear of obstr


Make sure there is no obstruction anywhere on either coil,and the fan is turning,and turning the right way,I believe the fan turns in the opposite direction for heat.If this does not work,freon would be needed,even for the heat. ... Air Conditioners

I have the toyotomi TAD-T38J portable air conditioner. It shuts off after 2 minutes after I turn it on with the remote. I have turned the timer off and it still does the same thing. I have tried turning it on with the emergency on/off switch on the front panel of the unit, and it still shuts off after 2 minutes. The screen light around the emergency on/off switch on the front flashes in blue when this happens. (Not the small led light). I have checked the water tank, and it is empty, and I have


That means you have some fairly major hardware failure inside the machine. The control board is my suspicion for sure, it definitely sounds like that is having electrical failure.. Have you called back the Toyotomi service person / people after you ... Toyotomi TADT38J Air Conditioner

My unit is 4 years old. I always turn it off when I leave for work in the am and turn it back on when I get home in the pm. Last night I turned it on at 7:30pm. When I went to the front of the house about 45 minutes later, I noticed the unit outside was trying to turn on but would immediately turn off. I checked the breakers in the garage, turned them off and back on but still had the same problem. The fan inside the house is running but unit outside will not kick on. I looked for a magic


It could be a few things.. It could be the capacitor - which the most economical to replace first..\015\012\015\012If you are not really very mechanically inclined - get a trained pro to come out.. It is very dag ... Air Conditioners

A/c in front did not show read out on the thermostat this am. I thought it had been turned off. I checked the switch, turned it off and then back on and the numbers etc. came up but then it went blank again. It did not work until 4:05 pm and then it came on for less than 1/2 minute and then stopped. The back a/c is working today but they seem to coordinate their on and off times. Do they have some sort of conection?


Depending on the brand of digital tstat usually when the display A/C it usually means that you lost control power to the tstat if the tstat has batteries in it pull the batteries out and display goes blank then there is no control voltage depending o ... Air Conditioners

My air condition inside unit seems to be freezing up and the air stops blowing through the vents after I turn it off it sounds like ice melting. after a few hours I can turn it back on ,it will blow throuh the vents again there is a fan on yhe front of the inside unit it is making noise. is that a exhaust vent not the one that blows air through the vents. how can I fix this myself


When does it make the noise, when on AC or heat?? 2 things if the fan is on the ac unit itself that's not the one that blows air thorugh your vents, if its the one inside the furnace that is the one that blows air through your vents, but remember th ... Goodman CKL60AR60 Air Conditioner

Vulcan comfort control turns on ok, runs for a few minutes & then turns off before reaching set temp. it then continues to turn back on for a few minutes before turning off again. the air does not seem to warm either from the vents. set temp of 18 C is not reached over a full day.


... Air Conditioners

I have a Sharp Portable air conditioner Model CV-10NH. It will start up and cool and in just a few minutes, it's as if some one thru the switch. It just shuts off and all three lights on front start flashing green one yellow one and red one. The only way I can get it to turn back on is to turn power of and let sit for a few minutes, or kick the reset on the plug end. but it just runs again for a few minutes and shuts down again.


... Air Conditioners

Honeywell F50F 1065 electronic air cleaner. Replaced power supplies in two units, installation went well. One unit works as it should. Second unit turns on for just under a minute and then goes off. After two or three minutes unit can be turned on again but only for a minute or so and the problem continues. All wiring and switches seem to check out fine. Any thoughts or pointers you can give me?


... Honeywell Air Conditioners

I have a Raypak RP 2100 R405 pool heater. When I turn the rocker switch on the front panel to ?on? I get nothing or no lights on the front control panel and nothing happens to the heater. I checked and there is power going from the transformer via the blue wire to the PC board but no power being distributed to anywhere else. Is it the PC board and if so how can I check to verify this is problem? The board is expensive and no one will accept a return of this item it if this isn't the problem. C


\012When you turn the power ON of the unit.It will show "Water pump" in the display".\012If its not showing "water pump"\012Then  3 things has to be checked>\0121)Check ON/OFF switch right side of heater.\0122)Check 120/240 volts for tr ... Air Conditioners

Weather King 8PJ10NDR01 When I turn the heater switch to ON position the furnace runs what sounds like an internal fan. Second, the igniter glows and when it reaches it's hottest stage the fan thrusts air through the air ducts / vents and the burners light for about 30 seconds to a minute blowing cool air. After a period of about 30 seconds to a minute the burner turns off. After the igniter and burners repeat this about 2 times the heater shuts down by it's self, even when the temp gauge has no


The gas valve is not sensing flame, and the unit shuts down on safety.\015\012\015\012Chances are the flame sensor is bad, its a common problem.\015\012\015\012If its a thermocouple you can buy one for 10 bucks, If its a newer ... Weather King 12AJA4801AH Air Conditioner

I have a Sharp CV10NH Portable Air Conditioner with the same problem as posted by gtkermit on Jun 08, 2010: works fine for a few minutes then compressor turns off and fan continues for a few minutes then compressor kicks in again and cools for a few minutes (cycles about every 5 minutes perhaps.) I have followed all suggestions on page 30 of the manual (as well as the different options for venting, etc.) ms-shop suggested that the thermostat needs to be replaced. How do i do this? Thank you!


Hello,The problem could be the thermostat, and any of the following compressor cycling for every few minutes\015\012could be over load for the compressor, dirty condenser coils need \015\012cleaning, To check \015\012the compressor\015\01 ... Sharp CV10NH Air Conditioner

I have the Royal Sovereigh ARP-1400BLS, 1400ww. T/he ac turned on the first day I installed it and then after turning it off once, it would not come back on. I played w it for days making sure to leave it off for three minutes between each turn on. I floowed the direction for Power Plug Check: press the RESET button Insert the power plug in the electrical outlet Press the TESt button. If the circuit bresker is working you'll hear a clik (which I did usually hear) Press the RESET button


... Royal Sovereign Air Conditioners

I have a goodman gsc13 ac unit about 4 year old. When the temp gets around 90 or above outside the fan on the unit starts but the compressor does not. I had service check it out but that day they were here it was in the 80's and it worked fine. I replace the thermostat to make sure that wasn't the problem. Interesting if I turn the unit off at the thermostat and wait 15 minutes and turn it back on it will run fine. But the next time it tries to turn on automaitcally it will just be the fan o


The hum you hear is the 24v transformer which is powered form the air handler inside have you tried a hard start kit or had cap checked ... Air Conditioners

LG LP0711WNR blows cold air for a few minutes, then starts blowing warm air. It will start blowing cold air again if I wait several minutes. Or if I turn it off and wait a few minutes it will blow c


... LG LP0711WNR Portable Air Conditioner

Ruud Silhouette II furnace: comes on and runs for as long as it wants, then turns off. Sometimes turns off at pre-set temp, other times just when it wants. May turn on again, behave well for several cycles, or for 20 minutes. When I get too cold, I go out, downstairs, and thump it near the fan. Starts right up, runs for as long as it chooses. Nearly least energy-efficient kind, v. frustrating. Had trouble-shooter out a few years ago, couldn't find anything. An intermittent short?


Hi ruby. Begin by installing a new thermostat. Preferably one that allows you to program weekday and weekend temps. separately. Joe ... Ruud UBHC Air Conditioner

I have a electrolux split system ese21hra is the model.It runs for 2 minutes and shuts down.The auto light starts flashing and the remote is non responsive ihave replaced the remote batteries and turned the unit off at the mains to try to reset it but to no avail.I have to turn it on with manual cool button behind the front panel.I does not turn on or off with the remote Regards Daniel Clifford


Indoor room sensor and coil sensor defective. Replace it. ... Electrolux E23CS75SS Air Conditioner

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


If both fans runs (inside and outside), check if the compresor runs , if does probably the unit is low in freon and needs to be recharged after the freon leak has been fixed (remember this is a seal system and it shouldn't leak), but if the compresso ... Ruud UBHC Air Conditioner

2007 Monaco with 2 rooftop dometic model 630035-331 units. Turn on front unit, fan starts immediately but compessor does not. Rear unit works fine but doesn't start for approximately 2 minutes after turning on which is normal . This same unit had a start cap switch replaced 2 years ago when it failed in same manner. Could this be saame problem again?


... Dometic Rooftop RV Air Conditioner

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


Nope, nope, sounds like a stuck contactor in the electrical compartment of the condenser, but there are actually several things that could cause it. ... Air Conditioners

I have a DeLonghi CF210 and I'm getting the "E3 Fault" code on the main screen. It will not power up in Air Conditioning mode, but the fan mode will run. I saw where someone suggested it is a voltage problem, and have tried it in several outlets to no avail. This problem happened to me about a week ago and I turned it off for a while (10-20 minutes), then turned it back on and it worked again for a week before giving me the E3 Fault error today. I do not have the financial resources to sen


Remote controller comms error. Check wired correctly, if so check dipswitch in RC. Set to Sg for 1 unit, or Gr for group then reset power ... DeLonghi CF210 Portable Air Conditioner

The fan knob on the climate control panel only operates on the high range and will not even turn the a/c on in low or medium. when in high range the a/c unit overall seems to be performing like normal except sometimes the air flow from the vents decreases and increases from the vent that is below the im assuming blower in the floor board on the passenger side. ive checked all the fuses under the hood and on the inside, and even replaced the optional climate control panel yesterday.


Had the identical problem in my Grand Cherokee... you need a new relay switch... mine was located under the dash on the passenger side and was ceramic -- when they go bad they only allow the climate control system to work on high speed. ... Air Conditioners

Wall A/C only SPORADICALLY blowing cold air. Turn it off and back on, you can feel it's cold, but only if you're 5 inches from it. After a couple of minutes, fan is only blowing warm air again. Vacuumed front of A/C, still doing the same thing. Filter is clean. It is over 100 degrees outside with very low humidity the last few days.(Los Angeles) ; since it's a wall a/c, of course 1/2 of it is outside in the heat. As I noted, if you put your hand right up against the front, you can feel cool air


If it blows be not with force like it used to it can be fan motor capacitor not boosting fan speed. but if speed is not the issuse. remove and clean both coils water hose ... Air Conditioners

1999 beetle AC... Ac works maybe 1 in 10 times for about 10 minutes then stops. Checked 134a level (good)... When AC is turned on, aux fan turns on, clutch engages on compressor and 134a pressure drops slightly, but not to normal operating range. When the few times it works, 134a pressure drops to normal range.


System is short cycling. A sign of low refrigerant. Post the numbers you get from the gauges for me if you would. Two readings. One at idle and the second at around 1200 rpm.Thanks -Ned ... Air Conditioners

Got this new air conditioner installed last week and turned it on yesterday...it ran for about one hour...but after about 30 minutes it was going of and on every few minutes...and not the breaker (power) is on I checked that and it never when off.


If you turn the temp. dial up the unit wont kick on as often,turn the temp dial down and it will run longer .it is working right. ... LG Heat cool Window Air Conditioner

I thought i smelled the ordor of burnt wire coming from somewhere in the house, which I could not figure out where it was coming from. I tried to regulate the therostat and found the a/c would not come on. So i turned off the unit for a few minutes to turned it back on and all i could hear was a loud humming sound of the motor, but no air were coming out of the vents. The outside fan is moving. I wonder what could be the problem.


Sounds like a siezed up blower motor inside your furnace if you were running your air conditioner with out the blower motor it will turn everything into a block of ice at your indoor coil you need to let this thaw out \015\012i would ... Air Conditioners