Hi, just replaced the capacitor thinking that would solve the problem but it appears it did not. The motor outside would kick on the unit inside would kick on but the blower motor inside works sometimes and wont other times. Basically, the unit will work just fine all day then we notice the house is getting warm, check the inside unit and everything is running fine but the blower motor is not circulating the air. I have a goodman a30-10 unit. I read where some people said the relay could be bad


Answers :

Turn off the power to the air handler(indoor unit). Remove the access panel. From the motor,trace the wires back to the fan relay. One wire will probably trace back to the incoming power terminal. The other is the fan relay. It could be intermittent thermostat signal to the relay or a bad relay.
To verify if the fan motor is good,you can remove the one wire from the relay and re-attach it to the other side of the incoming power terminal. If it runs OK there,replace the relay. If it does not run,replace the blower motor.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Hi, just replaced the capacitor thinking that would solve the problem but it appears it did not. The motor outside would kick on the unit inside would kick on but the blower motor inside works sometimes and wont other times. Basically, the unit will work just fine all day then we notice the house is getting warm, check the inside unit and everything is running fine but the blower motor is not circulating the air. I have a goodman a30-10 unit. I read where some people said the relay could be bad


Turn off the power to the air handler(indoor unit). Remove the access panel. From the motor,trace the wires back to the fan relay. One wire will probably trace back to the incoming power terminal. The other is the fan relay. It could be intermittent ... Air Conditioners

Sometimes, when the inside blower shuts down, the outside compressor and fan motor continue to run for some time. Other times, when the inside fan motor is running, the outside fan and compressor motors are not ... if I press the outside reset button, it starts up When both inside fan motor and outside fan and compressor motors are running, it works fine ... warm air blows out of registers. Other than that problem, both units work great!


Sounds like you have a dirty condenser. You are going to need to disconnect the power at the outside unit on the wall by pulling the fuse block out. Take a good look at the louvered covers that are attached to the outside of the unit. Remove the scr ... Ruud UAKA060 Air Conditioner

AC Condenser motor will stop at 1pm but inside unit is still running but no AC. If I turn the AC unit breaker unit off and then an hour later turn it back on. The unit runs fine all day until 1pm. Had a tech out and he checked the system and it's fine. He said I may have a thermostat problem and he would need to see the manual. My theromastat is programable (Carrier, 4 zone, Comfort II) with 3 remote temp sensors. How do I troubleshoot this?


I am having the same problem. The unit out side is off and I can have the thermostat off and it keeps blowing in the house. The weird thing is it turns it self on and off inside every 15 sec or so.. How can I stop this or why is it doing it? ... Carrier 38CKC060 Air Conditioner

Blower fan in the inside unit tries to turn on but wont. It can be turned manually and air conditioner comes on and runs fine. The " squirrel " cage spins completely freely and is not sticky or jammed. Is the motor bad or is it a run capacitor. Model number of inside unit is a49-15


\011Sound more like the cap, but if the motor is raging hot, it could be the motor, another thing it could is improper voltage although less likely. But Goodmans/ do have this weird fan relay issue were they just bite it some times. I wo ... Goodman Air Conditioners

I have a ruud model no. ubhc-17j11nfd and i am having a problem with my heat. when the heat does come on, the thermostat says it is on auxilary heat. the blower in the inside unit does not run. i changed the capacitor and now i get a really loud humming noise. the motor still does not spin. but when i spin the motor by hand then it seems to work fine.(the humming goes away) this happens every time when the heat goes off then back on. the only way to solve this is to keep the fan on constantly.


... Ruud UBHC Air Conditioner

Have a package unit that is tripping the circuit breaker early in the morning, around 5 a.m. each day for the past few days. The blower fan motor was recently replaced, but it seems to work fine, all day in fact, after resetting the breaker. (After letting rest for a bit before resetting the breaker.) Why would it only trip in the morning? It cuts off and on fine all other times, but only in the morning does it trip.


... Goodman GPC1342H21A Air Conditioner

I have a Goodman A/C unit, Inside unit P/N A42-15, my problem is inside blower won't turn on when in A/C outside unit turns on and the copper pipe going to inside unit gets cold, but no blower to circulate air, can some times get blower tot turn on by reseting inside units circuit breakers, also heater works fine.


What about the blower time delay relay: http://americanhvacparts.com/Merchant2/merchant.mvc?Screen ... Air Conditioners

I have a Inter therm Model# FEHB015HA central heat & air unit that I had problems with in the summer as the out side unit would not come on but the blower would kick on but nothing on the outside unit(No cold air).Ok I fixed that as it was the the transformer that switched it down to 24 volt to go to the outside.Now I have noticed that when the heat is on it will not kick the outside unit on?It has been very cold here in Georgia but right now as I type it is 50 degree's and the outside unit is s


Hi, if this is not a gas fired split system, it is a heat-pump with aux heat strips. The outdoor unit must be on to warm you're home by way of the reversing valve. The strips in the indoor unit are for emergency and auxiliary heat only. ... Air Conditioners

AMCOR 24,000 BTU split system. Worked fine two years, then today it had no power. Checked circuit breaker, it had popped. Reset CB and went to inside unit - would not turn on or off with remote or hard button. Checked wiring with an electrical tester, and wires to outside unit hot, as well as inside unit. No flashing codes, nothing. Unit won't turn on,even with power. Is there a fuse somewhere in the inner unit or outer unit?


I had this same problem. I disconnected the thermostat wire out side at the condenser and reconnected it and it started working. A couple days later it blew the breaker again this time I found the bus where the L1, L2. GR wire connect at the condense ... AmcorAire UCHW-H24AF2 Split System Air Conditioner

I thought the blower motor on my electric furnace was out so I replaced it with a GE 1075, 1/3hp new blower motor. I still have the same problem though. When the outside unit turns on the blower motor inside will not turn on.


It could be a bad thermostat. remove the front cover, take a jumper wire from r to g to see if the fan will come on, if does then its the thermostat is bad, if don't, then the fan circuit board is bad. ... GE Air Conditioners

Replaced the blower motor on a Carrier a/c unit x421892 after motor seized and tripped breaker. New motor runs fine but runs continuosly when put in the auto position. The motor still runs even when thermostat is turned off. Breaker must be off to stop blower motor. Any suggestions on how to fix this problem?


Hello The new motor sounds HOT wired.It must have one leg connected to the blower relay.If it is off the relay(correctly) ,the relay is stuck/welded and should be replaced.In the blower unit. ... Carrier 38CKC036 Air Conditioner

Hello i have Carrier Weathermaker 38tkb air conditioner unit. It's about 6 years old and when i got home today, the unit itself wasn't working. Although the blower fan in the furnace inside was blowing, the fan on the a/c unit outside was not moving. I can hear a humming sound coming from it and once in a while, you hear it trying to kick in (the lights in the house even dim a bit, which is unusual), but it never kicks in. The top center of the unit is extremely hot to the touch. I've checked


The humming noise and dimming of the lights is an indication something in the outdoor unit is locked up or has failed.Check the capacitor as it may have gone bad. If the capacitor is good, then you either have a failed motor, a failed co ... Air Conditioners

Unit runs but will not cool. Fanruns fine but when turn dial to cool the compressor kicks in for about a second or two the kicks out. Fan works on cool but it will not produce cool air at any temp setting. I have cleaned filter and removed cometic facing and vacuumed the coil face. It was pretty dirty but after all that still would not cool, Unit is installed in a RV and power is provided from house. Gen4erator is also available for power. Unit is difficult to remove from RV and space to get at


You may need to install a hardstart kit if you can get to the compressor.\012go to your nearest appliance parts store to get the part and the instructions are usually on it. If not ask the parts man.\012\012If this was helpful pleas ... Air Conditioners

The outside unit is running but the inside blower motor will not come on. removed the blower and cleaned it up and plugged it in outside and it ran. the unit is 13 years old rheem crition unit. Where is the fan relay switch


There is no relay for the inside fanmotor.\015\012Switch the elektrical power off, then check the fuse on the inside circuit board.\015\012Goodluck! ... Air Conditioners

I have an old RUUD central AC unit that started blowing hot air. I set the thermostat to off and set the temp gage higher than air temp to turn the unit off and save money, but inside blower unit runs constantly. I'm trying to save money to have it serviced, but noticed my electric bill was higher that last month when the ac was working. The bill was about 4 times higher than the winter when ac is off and the gas heat kicks in. Can the blower running constantly cause this power usage and what is


HelloOkay did you check your thermostat to see if you have the fan switch on auto? The switch must be on auto or the fan will continue to run. If the thermostat fan switch is on auto then there is a malfunction in the thermostat probably ... Air Conditioners

I have an ultra sx90 unit. the compressor kicks on just fine and runs for about 10 seconds then the fan motor goes to kick in and it starts then stops about 3 to 4 times before it finally stas on. then when compressor stops the fan motor continues to run for about 20 sec then kicks off and on 4 or 5 times.


Hi,\015\012That fan is running off of either a pressure or temperature sensor....could be either one...\015\012bottom line is that this switch is going bad and the "deadband" is too small causing the unit to cycle too often...\015\0 ... Air Conditioners

I noticed some straining noise coming from my a/c unit today. The fan on top of the condenser runs fine but as soon as the compressor tries to kick on the fan stops for a split second and you get a kind of surging noise from the condenser unit. Then the fans kicks back on, the the process repeats itself every couple of minutes. Meanwhile no cold air is being produced inside the house. Any ideas?


You amy ahave a bvad capacitor on the outside unit. It starts the fan and the compressor. You can change this yourself. Open the outside panel and you will see a silver canister with terminals out the top. Replace this and I think your problem will g ... Goodman CKL24AR24 Air Conditioner

Our Coleman Central heat and air unit EB20B keeps blowing the inline 3 amp fuse. How should I troubleshoot the fan relay and blower motor to look for defects that would draw too many amps. The relay and blower motor are 11 years old. Thanks Ken Rohm


The transformer is blowing the fuse because somewhere down the line two thermostat wires are shorted together. You gotta trace that out till you find the shorted wiring first. It is unlikely a component would blow that fuse. Most of the time it is wi ... Air Conditioners

Just cut on 8 year old Goodman CPLE24-1 AC for the summer. Ran 8 hours fine, Next morning noticed outside unit running, very little cool air blowing out of inside floor vents (like the blower fan was broken). Outside unit frozen. Capicitor replaced last July. (2) separate filters inside house returns clean. Whatz the problem? Help? Advice? Gotta fix it fast! By myself hopefully. Thanks!!!!


Due to the many different questions I see about Air Conditioning, I am including this overview to help us better understand each other for trouble shooting. A basic air conditioning system has a Thermostat, Air Handler or Furnace Fan and a Condensin ... Goodman CPLE24-1 Air Conditioner

I have a Ruud Acheiver 90, I'm having some problems, the rollout (burner) limit switches are opening, and there is an electrical burning smell. It seems that sometimes the squirrel cage isn't kicking on, but when I reset manual limits and give the squirrel cage a manual turn, the heater runs fine, sometimes. I guess what I'm asking is: would the fan motor only work sometimes, would the ignition plug give off an electrical burning smell (it's lighting fine), there is a separate thermocoupling, it


Thanks for your question,yup your fan motor is bad, if you need to manually start it each time then the motor winding are bad and it is not getting the air across the coils, which in turn are over heating, thus causing a burning sm ... Air Conditioners

Ruud Problems I have a Ruud Acheiver 90, I'm having some problems, the rollout (burner) limit switches are opening, and there is an electrical burning smell. It seems that sometimes the squirrel cage isn't kicking on, but when I reset manual limits and give the squirrel cage a manual turn, the heater runs fine, sometimes. I guess what I'm asking is: would the fan motor only work sometimes, would the ignition plug give off an electrical burning smell (it's lighting fine), there is a separate ther


Ive seen this this year several times. first off take the combustion blowe loose from the ducting and look inside to see if theres any thing causing the blower to not run (water) what happens is that the flue gasses condense and run back into the bl ... LG LW1200ER Air Conditioner

My carrier air conditioner is not working. We have two exterior units. One for upstairs (smaller) and one for the downstairs(larger unit). That being said we have two seperate thermostats inside our home. The upstairs unit is working fine. The downstairs thermostat shows on Auto that the unit should be kicking on based on the temp. However, the outdoor unit for downstairs is not working. So far I have checked the downstairs vents and they are blowing air although not very cool. I also tu


Hi,The problem is in the outdoor unit...The compressor could be locked up, the condenser fan could be bad... or from what you are saying the contactor for the outdoor unit is either not pulling in or is bad...that also can be a result of ... Air Conditioners

My unit is running but not blowing cool air. I went outside and the condenor fan was not moving. Took a stick and shoved a blade and the fan started moving but the air is still not cool inside. I did notice the air coming through the unit outside after fan was blowing was cooler than my 2nd a/c unit that was working fine. I wondered if the entire unit was frozen. I turned off unit at thermostat and figured I would see what happens tomorrow


Sometimes on new units it is common for the fan to not start until you give it a push. Did you happen to hear if the compressor was operating? If the unit was froze-up the Insulated Suction line would also be iced over as well. If it wasn`t it is mor ... Carrier 38CKC024 Air Conditioner

I have a Coleman roof mounted AC unit on a travel trailer. The unit model is 83338715. The unit just blows cool air not cold air like it should. I was told to replace the "Hard Start Capacitor" and "PTCR Start Device" which I did. This did not remedy the problem. Any thoughts would be appreciated. Could the problem be the "Compressor Run Capacitor"? Reason being that I hear no change in the blower sound when the unit kicks on???


Blowing 'cool air' could mean - room temperature air or it could be 'cool' because the system is low on refrigerant, and just barely doing any 'cooling' at all.\012\012To determine which is which - you need to know "for sure" if the compressor ... Air Conditioners

Ruud AC unit outside won't start, furnace and blower inside work.


... Ruud Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1246 seconds