Having problems with your Air Conditioners ?

I was looking at a 4 ton split system,goodman indoor and outdoor fans come on but no compressor think it's the relay but didn't see 1 in the furnace control board,is the relay inside the contactor on the condenser,thought i could change out the contactor but wanted to ask a tech 1st.


Answers :

Try to put a booster cap in parallel with the compressor capacitor ,but if still the compressor won't start it has a problem and because it's hermetic it has to be replaced.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I was looking at a 4 ton split system,goodman indoor and outdoor fans come on but no compressor think it's the relay but didn't see 1 in the furnace control board,is the relay inside the contactor on the condenser,thought i could change out the contactor but wanted to ask a tech 1st.


Try to put a booster cap in parallel with the compressor capacitor ,but if still the compressor won't start it has a problem and because it's hermetic it has to be replaced. ... Air Conditioners

Our inside unit Coleman EB20B (outside unit Goodman GKL 49-1) keeps blowing the in-line 3 amp thermostat fuse. We've rewired the wires in the wall, rewired the contactor wires, and the contactor was broken so we replaced it. We're still blowing the fuse. Could we have reversed the thermostat wires at the contactor? Or could the short be in the Blend Air box-this box is coupled to the thermostat wires? Thanks Ken Rohm


Hi,Mark\015\012 all your wires using tape or by writing it down to ensure you will be \015\012able to hook them back up exactly the way you found them. Remove all the\015\012 wires from your board again. Tape off the ends so you don ... Coleman Air Conditioners

I have a mitsubishi air conditioning unit model MUH-12v. The fan on the machine outside has stopped and of course inside the air is not cold. Could this be a problem with replacing the gas or could it be a technical problem with the outdoor unit. Also I have noticed when I switch on the unit on the inside with the remote control that instead of two green lights comimg on I only have one green light flashing. Does that mean anything?


Hi,Here is a tip about Mitsubishi Air Conditioners and how to get the manuals for all of the mitsubishi line. The manual include both troubleshooting and installation. ... Air Conditioners

Carrier 38 leo 30320 ac unit....when the compressor shuts off the fan keeps running. a rap on the control panel shuts it off. I when changed the contactor the inside unit stopped working so I put the


Hello, if the indoor blower runs nonstop a relay in the intergrated control board faulty and the whole board must be replaced, you can get tap the board to stop the blower but eventually the board will need to be replaced. If the contactor is clicki ... Carrier Air Conditioners

Rudd central unit , turn A/C on[therm. inside] all U can hear is a Buzzing noise coming from the outside unit , found that [1] capacitor wire had been BURNT , changed wire , then changed capacitor , turned unit on[inside], 1st nothing ???? went inside & ck'd *breaker box* , fuse is operated by "dual arm[tied together] flipped off then on & went back turned a/c back on , came on for [maybe couple of minutes] then STOP'd , tried '1' more time , all U hear is the BUZZ noise? U could smell SMOKE & H


Hello\015\012Before you buy a new condensor fan motor check the contacts to the motor are not worn or pitted.\015\012\015\012Hold or push the contactor in by using an insulated screwdriver and see if the fan motor turns.\015\0 ... Air Conditioners

Hi, just replaced the capacitor thinking that would solve the problem but it appears it did not. The motor outside would kick on the unit inside would kick on but the blower motor inside works sometimes and wont other times. Basically, the unit will work just fine all day then we notice the house is getting warm, check the inside unit and everything is running fine but the blower motor is not circulating the air. I have a goodman a30-10 unit. I read where some people said the relay could be bad


Turn off the power to the air handler(indoor unit). Remove the access panel. From the motor,trace the wires back to the fan relay. One wire will probably trace back to the incoming power terminal. The other is the fan relay. It could be intermittent ... Air Conditioners

Ruud heat pump outside unit not starting. Open and found contactor disengaged even though I have system on from inside. Low voltage wires come out of a circuit board checked for 24v, none. Then bypassed board by unplugging same yellow and brown wires plugged into the board and exiting but now I have 24v getting to contactor but it does not engage contactor. What could the problem be. I know a little a/c but these heat pumps are very complicated. Help please, I want to learn.


If you are getting the low voltage to the relay and it is not closing, then the relay may be either bad or stuck. Disconnect the 220v and see if the contacts can be manually closed. I always use a piece of wood or something non-conductive. If the ... Air Conditioners

Twice the heat went out LG 18000 5 year warranty. 1st time unit sparked inside the unit, Tech came out couldn't repair was given a new unit (2 weeks out of service) had to buy 2 floor heaters at a cost 125.00 as temporary measure. 2nd time out was a year later. (used twice for heat) Waited for tech 1 day called to cancel that day for the next day and would be at house between 6 - 8pm. Never showed called at 7:30pm and asked me some questioned. Tech ordered updated heater core. He state


Was the first unit a different model ? what the repairman said is pretty much right but they should be more ontime and communicate if they want a good name. the unit should work fine after replacing if it doesn't dont pay for the part ... LG LWHD1807HR Thru-Wall/Window Air Conditioner

I have four Daewoo DSC-097L split A/C in my house in Mexico. One unit turned on with controller, then quickly turned off. Will not turn on again. Controller is O.K. Works on other three units. I had a short in rooftop wiring to unit's compressor. Short is fixed. Is there a fuse which could have blown or a relay which switched off. Where do I start? Thanks- Mike Z. [email protected]


... Daewoo Air Conditioners

Condensing unit staying on intermittently after inside unit switched off.Condensing unit relay on relay board replaced to no avail.Would like to know if control board is still available and price. Thanks, Dave.


Hi, you can use this site to know where and how to get the control board for the air conditioner.globalsources.com/manufacturers/Air-Conditioner-Control-Board.html,orhimfr.com/buy-air_conditioner_control_boar ... Air Conditioners

Had a tech over they put in freon because all had left unit he told me the compressor was bad so i went in the basement and i heard hissing and the inside unit had frost below it and the upper coils were sweating is there something i could put in the unit or have a tech to put something in to stop the leakage ?


Hello,Since you have detected the leakage and the sweating of the coil.You can get the technician to install a new coil into the air conditioner from below it to the upper coil.Also ensure that the coil does not ha ... Haier HPAC9M Air Conditioner

My 1996 Motorhome Dometic 4 button Comfort Control suddenly does not recognize that the furnace is present. After wiring in a manual thermostat the Comfort Control suddenly recognizes the furnace. I take out the manual thermostat. I clean all the external contacts and then it continues to recognize the furnace thourgh about 15 test over 6 weeks. Pause 2 weeks and suddenly it does not recognize the furnace. What is going on. Could it be a sticky relay in the suburban Furnace?


... Dometic Air Conditioners

My very old carrier 38 GR just twitches the contactor a few times every 2-3 seconds. Barely enough to cause the fan to move a quarter turn. If I jump the 29v coil supply from the control relay to the main contactor it starts and runs fine for an hr or as long as I leave it jumped. This is not an open hi or lo pressure switch. The transformer secondaries are all good. Does that leave me looking for CPCS board 38GR503344kK ? Thanks, Dan


... Carrier Air Conditioners

My heat pump will not come on in HEAT or A/C. I thought I might have a simple defrost control board problem, but still no go after replacing the board and the defrost relay. I checked the pressure switch and it is not tripped. I've checked all the circuit breakers and they, too, are all set. I've checked the outside unit using the "test" switch inside on the start relay and the unit will come on, but won't stay running on it's own. When I select HEAT, I wait the necessary five minutes for the un


Hi; Need more info. How old is the equipment,look on the outside unit data plate it will give the built date usually in the top right corner. Also heat pumps can run with a faulty defrost board. I would check for control voltage at the secondary side ... Ruud UBHC Air Conditioner

Fan Hello, my ac unit blower on the inside is working fine but, the outside fan isn't. i just bought a new relay switch due to that what it was a few years back. but, it's not working the outside fan. so, my question could it be another relay switch? or the compressor? Thanks


Hi wild 36.\015\012I think the problem may be a bad run capacitor. If the outside unit is humming with no action, that may be it.\015\012\015\012This could also cause the outside unit circuit breaker to trip.\015\012\015 ... Air Conditioners

Got a 3 ton ruud heat pump that is freezing up. I first checked voltage at my board and had voltage i then checked the defrost control relay for voltage and i had 120 volts and when i put my meter leads on the 24 volt side it immediately with into a defrost is the relay bad or could i have a bad defrost thermostat or board


... Ruud Air Conditioners

I have a Carrier infinity model 38tdb037-3. The outside unit will not come on. the control board on the outside unit shows an amber led on status 2.it is a steady constant flash.the error is an apparent stand by/on demand.munualy depressing the contactor forces the unit to run and seem to work fine. communication is good. the inside unit shows two green leds and one amber constant flash. any ideals. maybe bad control board?


... Carrier Air Conditioners

AC unit outdoor fan motor does not come on as it should, but if I manually start the contactor relay / coil by pressing and holding the manual button on it the fan then comes on and goes off with the thermnosat; however, the air stays cool (that is blowing outside) and warm inside. The large capacitor does not look bad though.


It sounds like the contacts of the contactor are burnt/pitted. When this occurs, it can allow enough current to operate the fan motor but not enough to operate the compressor. ... Carrier 38CKC036 Air Conditioner

Mitsubishi MXZ- 3A30NA 20 Amp fuses blown at disconnect, replaced, energized no responce fuses did not blow, no LED lit on PC control Board. Page 41, 10-6 Troubleshooting Flow of Tech Manual, Outdoor Unit Does not operate. (LED display: display off) Input power to Noise filter board good. output power to reactor not reading 240VAC between legs TAB1 and X-64 pin located on contactor on noise filter power board, however I do get 120V each leg to ground. Replace noise filter power board? I removed


Have you checked the reactor board for a defective M.O.V. thyristor that way have a burned spot on the side of this component that normally would have, due to a lightening strike,over-voltage or under-voltage,if they open they will kill one leg,or po ... Air Conditioners

630515.331c Duo therm replacing an old Briskair 59516.531, My question is, I want to use the inside ceiling part with the switches and non ducted registers. There are wires for 120 volt and a 6 pin connector for the unit at the control box. How would I wire up the new unit to the six pin connector so I could use this set up. nw unit has 2 blue 2 yellow, black, red, looking at a wire diagram looks like the red and black need not be used, and the 2 yellows go to what they call load shed (????), w


... Dometic Rooftop RV Air Conditioner

Ok I had the problem with ruud uaka-030jaz. I think i hit the wrong buttons when sent your solution so im not sure my response went to u. I checked the outside disconnect..says on the panel it does not have fuses inside. I checked behind the plastic panel anyhow and there weren't any. Did check the screws on the wires to be sure they were tight. I also was looking close at the contactor and there does appear to be some scorching under the contacts that are controlled by the spring loaded p


Very bad - the burned part signals that there has been an short somewhere. The fact that the burned part is black signals that the short has been massive so it's probably in the compressor itself which means that the repair will be costly. Call a pro ... Air Conditioners

I suspect my ripple control receiver type ro3 is faulty.Sometimes of late i've been left with no hot water in the morning.I assumed that the pulsing for off peak overnight didn't happen so i have been manually switching the "override/test" switch.This generally will give me hot water in a few ours then the switch/relay resets to "off".I tried this "quick fix" this morning and after about 2 minutes the relay turns off.We have had regular thunder storms in the area which could cause false "trigger


Hi, an welcome to FixYa,\015\012\015\012Your Air Conditioner is to small for your purpose, Id recommend you to upgrade to the 5000 model.\015\012\015\012Regards\015\012/Teis ... Air Conditioners

Amana AC model MBR2000, installed mid May 2009. When outside temp gets above a certain level the AC does not cool. fan keeps running and it keeps trying but not work. When outside air gets cooler then starts to work again. Tech here twice. 1st time when AC was working - could not find problem, 2nd time when problem was occurring. 2nd time found burnt wire and replaced. Same problem started again 2 days later. AC unit is large enough for our house, is 18 Seer 2 stage. Any suggestions as to proble


Hi it sounds to me like what actvates the 2nd stage of the compressor is not turning the compressor on when the ambeint temiture reaches the point that it calls for the 2nd stage to start it may be an out door thermostat or a ambient senser and I wou ... Air Conditioners

We have a GE-Zoneline AZ38H07DABM2. Since the storms passed though it has not run. I have checked power all the way to the yellow plug inside the unit and it is good. The wall control has power from the unit and I can hear the relay click in it when I plug the unit in. I am unable to even get the fan to run. Looking for any suggestions on where to head next.


... GE Zoneline AZ38H12DAD Split System Air Conditioner

I have a rheem condenser that the contactor does not pull in.I have changed the relay control board


Have you checked for 24volts A.C. from thermostat two small wires on the magnetic coil on contactor,w/o this voltage the contactor will not pull in to energize compressor with 240 volts A.C.it needs ... Air Conditioners