Having problems with your Air Conditioners ?

Wall A/C only SPORADICALLY blowing cold air. Turn it off and back on, you can feel it's cold, but only if you're 5 inches from it. After a couple of minutes, fan is only blowing warm air again. Vacuumed front of A/C, still doing the same thing. Filter is clean. It is over 100 degrees outside with very low humidity the last few days.(Los Angeles) ; since it's a wall a/c, of course 1/2 of it is outside in the heat. As I noted, if you put your hand right up against the front, you can feel cool air


Answers :

If it blows be not with force like it used to it can be fan motor capacitor not boosting fan speed. but if speed is not the issuse. remove and clean both coils water hose

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Wall A/C only SPORADICALLY blowing cold air. Turn it off and back on, you can feel it's cold, but only if you're 5 inches from it. After a couple of minutes, fan is only blowing warm air again. Vacuumed front of A/C, still doing the same thing. Filter is clean. It is over 100 degrees outside with very low humidity the last few days.(Los Angeles) ; since it's a wall a/c, of course 1/2 of it is outside in the heat. As I noted, if you put your hand right up against the front, you can feel cool air


If it blows be not with force like it used to it can be fan motor capacitor not boosting fan speed. but if speed is not the issuse. remove and clean both coils water hose ... Air Conditioners

E6 error I have a new Friedrich split A/C unit (ten days old). Just ran it for the first time and after a couple of minutes, E6 shows up on the display panel on the wall mounted unit. After some detecting, I discovered that the unit outside never comes on. The wall unit does blow but it seems to just be blowing air (yes, I have the remote set to "snowflake"...but the "snowflake" light on the display panel also turns off after the initial couple of minutes. I HOPE the problem is not in the wall (


... Air Conditioners

I have a rheem hvac unit that is not cooling the air that is blowing into my house. The air feels like it is the same temperature as the air outside.


The compressor isnt running you would need to check capacitor maybe not enuff freon how does your filter look ... Air Conditioners

Our air conditioner seems to be working fine yet t won't blow cold air. Its just room temp air actually feels like you're standing in front of a small fan.


Check outside unit large pipe should be cool or even very cold small pipe should be warm to touch that will eliminate some questions in order to solve problem also check circuit breaker for outdoor unit see if fan on outdooor unit is running an ... Sunbeam Air Conditioners

My 5000 BTU GE window AC is making sporatic loud popping or cracking sounds when the compressor is on and running. It has stopped blowing air! When I put my hand in front of the air vent I can feel cold air but it is not being projected out like it normally is. Do these units freeze up? What causes it, if so? And how can I check? What can I do to get it working right again? We are burning up! Thank you so very much!


Fan inside blower unit stuck or seized. The compressor noises are because liquid refrigerant is coming back because it's not picking up heat from the room. Check/ clean the filters and spin the motor of the fan WHILE SWITCHED OFF. If it spins, it's p ... Air Conditioners

I live in Florida, my a/c system, I believe it is a Rheem, has been heating the house fine all of this winter no problem. With this last recent cold spell, I turned on the heat and all that is blowing from the vents is air that feels a few degrees warmer than the air in the house, it does very slowly start to raise the temperature in the house but is taking a very long time. I have stopped using the heat for fear of damaging the inside and outside units, need help


I would call someone that knows how to check the pressure in the outside unit. I would run emegency heat if it gets to cold. Switch the thermostat from heat to emergency. If the outside unit was running when the temperature was to cold and not going ... Ruud Central System Air Conditioner

I have a fujitsu halcyon inverter evaporator that isnt working. The indoor wall mount is blowing air, but the evap outside isnt working. The fan doesnt seem to be working. I have another 2 piece fujitsu, same exact model that is working fine, drawing air into the evap. Dont know much about trouble shooting, any tips would be appreciated because its hard to find info on these things.


... Fujitsu Air Conditioners

Our inside unit Coleman EB20B (outside unit Goodman GKL 49-1) keeps blowing the in-line 3 amp thermostat fuse. We've rewired the wires in the wall, rewired the contactor wires, and the contactor was broken so we replaced it. We're still blowing the fuse. Could we have reversed the thermostat wires at the contactor? Or could the short be in the Blend Air box-this box is coupled to the thermostat wires? Thanks Ken Rohm


Hi,Mark\015\012 all your wires using tape or by writing it down to ensure you will be \015\012able to hook them back up exactly the way you found them. Remove all the\015\012 wires from your board again. Tape off the ends so you don ... Coleman Air Conditioners

My goodman ac unit is not blowing cool air inside, well not hardly blowing air at all but the outside unit is blowing cool air outside


... Goodman Air Conditioners

I am living in a home with a carrier furnace. The furnace is in the back part of the house in a store room. It has two- 2 1/2 inch plastic pipes. One that suppplies air to the furnace and the other is venting air out. Both picpes go though an outside wall. Also above the furnace in the ceiling of the room is an air supply vent bringing in outside air through an outside wall. Is there a purpose for having this second vent in the ceiling as it brings in so much cold air into the room & into the ho


As long as the fresh air intake pipe to the furnace is not plugged up the second vent is not needed some homes when they are new are air tight and need a fresh air circulation system ... Carrier Air Conditioners

Air Conditioning I have a ruud system with the air conditioner outside and the air handler upstairs in the attic. My systems appears to be running, and I can feel cold air at the vents, but I can barely feel it. Like there is no flow. The fan outside is running and the unit in the attic is running. I have no clue what the problem is. The large coil coming from the heat pump outside is cold and has condensation on it. It also seems to have a little ice. It has been extremely hot here in Ge


Open the access panel on the air handler in the attic and take a look at the evaporator coil. If you have no airflow, and you just changed the air filter, then you probably have a buildup of airborne crud on the coil that's blocking airflow. \015\01 ... Ruud UAKA030 Air Conditioner

Have a 1984 trane heat and air gas furnace unit ..always freezes up...repair people always come and put freon in it over and over.. and of course blows out pipe. Had new outside unit put in this is a "goodman" in 1996. ...still freezes and repairmen come over and over again to repeat same thing.. The inside coil is in attic.. behind a wall. no one has gone up in there since we've lived here in since 1992.. is this the problem?


Could very well be.\015\012Seems to me when they replaced the outdoor unit in 1996 someone should have found out that there was a leak when a vacuum was supposed to be pulled and held on the existing line set and and the unit in the attic for a ... Air Conditioners

The coil outside is 45 degrees but the air blowing in the house doesnt feel cool


Is this a heat pump? If so it sounds like a stuck reversing valve.\015\012Sometimes cycling the thermostat between heat and cool will free it. ... Goodman CKL42AR42 Air Conditioner

My Unit is dripping water and it appears that cool air is not blowing from one side of the wall mounted unit. I have checked the outside hose (dripping slowly) and it does not appear clogged but obviously it is clogged somewhere. I have cleaned the unit but to no avail. help


The evap could be frozen due to dirty filters or a low charge. run just the fan for about an hour and see if you get air flow on the other side. ... Mitsubishi MSZ-A09NA Air Conditioner

Frigidaire 18,500 btu installed about 2 weeks in the wall and has been working great...It is tilted down on the outside, however this evening it started blowing drops of water inside the room..About 1 drop every 3-4 minutes..... It is in a room 30x20 and there was no stove or anything on, however there was a door wide open leading into a out 40 feet of the house at the time was not air conditioned....any suggestion...Doug Hogan


Sounds like over condensation caused by the uncooled area but may also be a clogged drain hole on the outside of the unit ... Air Conditioners

I have a Mitsubishi Electric wall mounted heater TYPE KPOA To set for heating should the Mode read I feel Cool OR Heat then set temperature required. Both settings seem to blow cold air. Many Thanks, for your assistance. Marc Moss. Marc @toorak.net


... Air Conditioners

When I set tstat to call for a/c, compressor outside comes on. Blower on furnace does not. When I manually rotate fan limit switch on furnace wall, blower comes on, blows cold air, and then goes off when I release the fan limit switch. I have a Honeywell 83251008a low and high voltage transformer, and Honeywell (I think) limit on off switch. I also noticed the 2 wires coming from the Honeywell Gas regulator are off. They were connected at the onset of the problem. I am not sure where to re


Sorry, you mean gas valve control? when you have only 2 wires, usually it doesnt matter which terminal as there,s no polarity differentiation at that locationYou should never rotate this dial by hand, you will bend the helix inside and fan will not o ... Air Conditioners

Air conditioner blows air but dosen't cool house. at first fan wasn't turning outside because curitbreaker poped reset all curitets outside, upstairs by unit. reset curitet beaker turn on thermosat curit poped again reset. fan came on outside air blows but house dosen;t get cold.


Clean outside fins and check freon level ... Carrier 38CKC024 Air Conditioner

I have 1994 Chevy Lumina 4dr 3.1 Multi Point, Front W/D, F1, 6cyl. My air conditioner was blowing warm air @ 2mos ago & my husband added freon & a/c began blowing cooler air but, not as cold as originally had cooled but, was able to use to keep cool enough! A/C stopped blowing cool air again just a few days ago..Air was actually blowing warm. I bought 2 cans of freon & husband put 1 can of freon in & a/c still was blowing but, now like a fan. He then added the other can & both cans were able t


You have a Freon leak because all the fittings, seals, coils rubber, compressor seals and entire AC system will need to be checked out by someone that can find the problem and resolve them or you will never get this fixed. A/C in cars get hot in the ... Air Conditioners

My toshiba split system will blow cold air for about 30min then it will blow what seems to be cool air but not air con cold air when it is quite hot outside. The timer light operation and filter light will flash. I have turned it on and off reset remote cleaned filters. When it's cooler outside it seems to work fine???


... Fujitsu 9RLS 9000 BTU Split System Air Conditioner

My unit is running but not blowing cool air. I went outside and the condenor fan was not moving. Took a stick and shoved a blade and the fan started moving but the air is still not cool inside. I did notice the air coming through the unit outside after fan was blowing was cooler than my 2nd a/c unit that was working fine. I wondered if the entire unit was frozen. I turned off unit at thermostat and figured I would see what happens tomorrow


Sometimes on new units it is common for the fan to not start until you give it a push. Did you happen to hear if the compressor was operating? If the unit was froze-up the Insulated Suction line would also be iced over as well. If it wasn`t it is mor ... Carrier 38CKC024 Air Conditioner

My heat unit will not blow hot air unless we go outside and hit a button on the back bottom of the unit. Once we do that it will blow hot air for that cycle. when it is time for it to come on it is cold air again and the unit outside is not working.


If it does not have a furnace or heating elements for heating, then it is a heat pump, which is rare for a central AC system, but makes sense of the fact that it blows warm air when you reset the pressure switch, which may indicates freon pressure ch ... Ruud Central System Air Conditioner

2000 isuzu rodeo, ac blows outside air temp, i tried to recharge. when i connected unit the gauge read 70 psi. i let out psi to 50. put the charge in and it took 90% of can and read 55 psi. it still blows outside temp air. (if the temp is on hot and while running switch to cold ac, i get a brief 1/2 second spurt of cold air) which unit might be bad; compressor or condenser?


You may have a clogged expansion valve. ... Air Conditioners

Hi, I have an Armstrong A/C that blows cool air when the outside temperature is around 75 even up to 77. When it goes hotter then it blows just air. Is there a setting that needs to be changed in order to get cool air when outside temp is greater than 80 ? or I should get a technician to check the A/C Thanks


It could be that the unit needs to be cleaned, it could\015\012be that the compressor is tripping on an internal overload because the internal part of the compressor\015\012is surrounded by high ambint air. It does not sound like a freon ... Air Conditioners

My 2005 odyssey A/c blows cold air but sometimes it blows warm air for no apparent reason. When it is blowing cold air, i press the rear A/C button to turn the rear A/C on. The A/C then blows warm air from the front and rear....It is fully charged BTW...


... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific