Having problems with your Air Conditioners ?

I have a Noma/ DeLonghi portable air conditioner. 3 Modes-fan-dehumidify-air conditioner.When I try the Dehumidify or air conditioner mode the mchine strains to start up and then blows a fuse. Fan still works fine.Tia


Answers :

Compressor is not starting, it could be a bad or shorted run capacitor, start capacitor and relay, low voltage, loose or disconnected wire or a shorted compressor.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Noma/ DeLonghi portable air conditioner. 3 Modes-fan-dehumidify-air conditioner.When I try the Dehumidify or air conditioner mode the mchine strains to start up and then blows a fuse. Fan still works fine.Tia


Compressor is not starting, it could be a bad or shorted run capacitor, start capacitor and relay, low voltage, loose or disconnected wire or a shorted compressor. ... Air Conditioners

I have a frigidare FAM157S1A Air Conditioner, when plugged in the fan blows air but not cold air. Compressor not working, I pushed control panel to cool air, blows cold air for a few seconds, then unit blows the breaker. How do I fix it. It has been only used for two weeks and this started.


Your compressor motor is no good Time to replace unit ... Frigidaire FAH085N1T Air Conditioner

Hello my air conditioner is not blowing cold air. It seems like only the fan is working. I set the temp to between 16-18 celcius and the temp that is showing is 28 celcius. Also is showing E5 on the ac small screen. It was serviced about 3 weeks ago and was working fine. This problem started about 2 days ago. Nothing has changed and nothing has been tampered with. Hope you can help Thanks :)


What did they do when it was serviced?It sounds like there may be a leak if it does not get cold at all anymore.Although,lasting 3 weeks,depending on how much you used it,it would be a very tiny hole leaking.The other most likely suspect would be the ... Air Conditioners

Problem I turned on my air conditioner this spring. I turned the switch to cool on and the air conditioner fan not going. I took cover off and got new capacitator didn't work. I took fan motor into electric shop and checked out fine. When I turn switch on the contact switch engages and there is a humming noise. But the fan does not work. the compressor doesn't start up. The model is at least 10 years old. How do we tell what the SER rating is?


Hi,\015\012There are two things to check....\015\012\015\012Do you have power coming into the contactor???\015\012\015\012Do you have power coming out of the contactor???\015\012\015\012If you have power goin ... Air Conditioners

How do I know if compressor of my house air conditioner is turning on when I start my air conditioner? When I start my air conditioner the fan outside the house turns on, the air is blowing from the vents in the house but the air is not cold at all.


If the compressor is starting there will be a very small dimming in the house lights,if you go outside to the unit and start it from the outside disconnect when the compressor starts you will hear a whine type noise coming from the outside condenser ... Air Conditioners

Air conditioner runs for a few hours and it works - it cools the house. Then it stops cooling - the fan still runs but it doesn't blow out cool air any more. It seems like it's overheating or something. It will blow out cool air if it has not been turned on in a while but once it's on too long it stops. I was told it could be the fan motor and the a/c guy changed the fan motor today but that didn't fix the problem. Now he says it might be the compressor or that I need a new system. I'm jus


The things I would check:\015\012Is the system properly charged with freon? Sytem may be overcharged.\015\012Is the compressor out on internal overload at the point of failure? If the overload isnt tripped and the compressor is having tro ... Air Conditioners

Air Conditioner was working fine last summer but outside fna not working. Not hearing any sound at all. I can move the fan amanually and it seems fine. There is an electrical box next to the main electrical box on the back of the house with 2 fuses in it but I can't tell if they're bad. I thecked the thermostat and it apears to be fine. The air conditioner furnce kicks on and blows air out of the registers. It's just the main unit outside that's not working.


There is a relay in the outside unit. Check for 24 volts a/c at the two wires coming from the furnace. also there may be a mouse nest in the control comartment where the relay is and they tend to chew up wiring insulation and sometimes wires get disc ... Carrier 38CKC042 Air Conditioner

My unit is running but not blowing cool air. I went outside and the condenor fan was not moving. Took a stick and shoved a blade and the fan started moving but the air is still not cool inside. I did notice the air coming through the unit outside after fan was blowing was cooler than my 2nd a/c unit that was working fine. I wondered if the entire unit was frozen. I turned off unit at thermostat and figured I would see what happens tomorrow


Sometimes on new units it is common for the fan to not start until you give it a push. Did you happen to hear if the compressor was operating? If the unit was froze-up the Insulated Suction line would also be iced over as well. If it wasn`t it is mor ... Carrier 38CKC024 Air Conditioner

Have an amana central air duelfuel heat system.when aux heat[gas] heats the house and shuts off the fans still blow for 3 to 5 minutes with the last couple of minutes being cold air which cools the air it just heated. also heatpump will start heating when it comes on then after 3 or 4 minutes it starts blowing cold air like when the air conditioner is running.i have had problems from day of install 4 mounths ago with problems that keep coming up. please i need help fast i do not think comp


Change your heating delay to shut off sooner, you can find this in the installation manual. Also the Thermostat may have delay after heat as well. It is true there could be many variables, but it also sounds like the Heatpump is not charged properl ... Amana Air Conditioners

Danby DB98-26786A window air conditioner will start up and blow cold air..frost forms on the tubes..after a few minutes the frost disappears and the compressor shuts off .. the fan still blows; but no cold air ..the compressor doesn't start again unless it is turned off for quite awhile


Hi,Here is a tip about troubleshooting your air conditioner...\012There are many things that can cause your air conditioner not to cool... ... Danby Air Conditioners

Amana air command 80 SSE started makeing humming sound id shut it off and wait a few minutes and it would work again been doing this for about a week and now its not working what so ever it was blowing cold air but when humming it wasnt blowing anything at all i checked to see if the fans were binding up but their spining freely any ideas i see a sensor light but i dont know how that works either. please help im melting thanks


Sounds as if the motor is heating up and shorting.Call a pro to find out for sure. ... Air Conditioners

My air conditioner has started leaking and has very poor air flow. It worked fine in winter but when I switched it to cool water is coming out of it. Sometimes the fan will work (no cold air) for about 20 minutes before it starts to leak, other times it leaks straight away. Any help appreciated.


This sounds like an air restriction inside the evaporator probably caused by a dirty filter or dirty evaporator coil. ... Air Conditioners

Air conditioner not starting at all....plugged in, everything assembled correctly, everything on keypad and display works, but nothing inside is starting and no air is blowing out. This air conditioner is 3 years old.


... Danby DPAC120061 Portable Air Conditioner

I have/had 2 GE 8000btu wall air conditioners and at 3 years old, both of them within 2 weeks of each other had stopped blowing out cold air, just now the way a fan would blow. It almost seems to me that GE has purposely made these air conditioners to stop working properly at a certain time so I should buy new ones. I replaced one of them already with another brand, now I have to replace a 2nd one. I can't really afford to do this. Is it possible that they have both run out of Freon? Otherwise I


I doubt the freon would be gone its a sealed system unless someone was pokin the coils kids love to bend the fins for some reason could need a capacitor is the compressor starting ? humming ?running ... GE AJCQ08ACB Air Conditioner

Great site. I have a Simplicity SPAC 8499-5 Portable Air Conditioner and it was working fine up until yesterday (~2 years old). The unit is running and the fan operational but while the green light for Cool/Dry is illuminated that actually cooling unit for the air conditioner is not kicking in. The system is just blowing air (like in Fan) mode. I have checked the water reservoir and it is empty and placed properly in the unit so the switch is engaged but no AC.


... Air Conditioners

I have a fujitsu reverse cycle air conditioner,it wasnt working(not blowing cold air only room temp air like a fan).air con tech came over,re-gassed it,tried air con that day,worked fine.didnt need to use it for a few months,re-tried it,no cool air again,i am thinking of a leak.My question is the air con is about 10 years old,if cause of problem is a leak,is it worthwhile fixing it(i would need to pay someone parts and labour,could not do this job myself),or to just bite the bullet and get a rep


Hi,\015\012\015\012The A.C is 10 years old which is a ideal shelf life for the A.C. If there are any leaks I would never ever try repairing it at home becuase if there is a leak then that means that the entire GAS which helps in the cooli ... Air Conditioners

My haier room air conditioner (hwr08cx7) just stopped working. The power goes on, the electronic displays light up, but fan does not blow. I also cannot adjust the mode--fan, cool, energy saver, dehum. I can adjust the temperature/speed but it doesn't do anything. Using the remote gives me the same results. The air conditioner is about a year old....


The Haier A/C unit has a small, electronic keypad on the front, right corner of the cover. There is very little you can do with it but check the wires going to it. Make sure nothing is broken or pinched going to it. The electronic module can be repla ... Haier hwr10xc6 Air Conditioner

My Ruud Air Conditioner Model UAMB-048JAZ is not blowing cool air. The fan blows, but it doesn't blow cool air. It worked this morning, and now it doesn't. I found a red reset button and pushed it, but nothing seemed to change. Can you help me? Cheryl


3 things it could be:\015\012\015\012#1 problem with AC units - dirty coils, this leads to many other problems and is caused by neglecting to change filters monthly. You can buy coil cleaner commercially, but it is not the coils you see ... Ruud UAMB Air Conditioner

Contactor not engaging to start condenser unit . When setting the thermnostat, i hear the click from the unit starting inside the house. Fans start and air starts blowing inside the house, but the condenser unit never starts. I tryed pushing the contactor by hand and then everything works find (cool house) as long as i keep the contactor pushed manually. Seems alike the 24 V (coil) bobine in the contactor is not been energize. When I tried the 24 V outside with a 24 V surce it worked fine. Thank


I would replace the contactor if you are getting 24 volts to the contactor and it isn't engaging therefore the magneto on the contactor is out and the contactor will need replacement. If you don't have 24 volts at the contactor then the transformer ... Air Conditioners

Sometimes, when the inside blower shuts down, the outside compressor and fan motor continue to run for some time. Other times, when the inside fan motor is running, the outside fan and compressor motors are not ... if I press the outside reset button, it starts up When both inside fan motor and outside fan and compressor motors are running, it works fine ... warm air blows out of registers. Other than that problem, both units work great!


Sounds like you have a dirty condenser. You are going to need to disconnect the power at the outside unit on the wall by pulling the fuse block out. Take a good look at the louvered covers that are attached to the outside of the unit. Remove the scr ... Ruud UAKA060 Air Conditioner

Tempstar 5000 This spring I turned on my air conditioner for the first time and it would not start at all... The fan did not turn on either. I turned off the main 220A breaker and puller the control fuses and put everything back and the unit started working fine. now fast forward to yesterday... house started feeling warm so I did the same thing... Tripped the breaker. Pulled the control fuses, and this time made sure I had new batteries in my thermostat. Started to work again. All was good. pus


... Air Conditioners

My air conditioner is blowing hot air. The fan outside sounds like it is going to start but we get nothing. The air is blowing from the vents but it is not cool air.


Well that because the condenser is not turning on. you might just have burnt fuse should be right next to the unite or circuit breaker. ... Air Conditioners

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


... Air Conditioners

My central air conditioner was working fine but the power went out for about 2 hours and when it came back on, my air pump runs and the air conditioner fan is running but it blows warm air. What gives?


Mcdevito75 here, Your A/C units control board is most likely transisterized or computer built, in which case when power went out so did the memory in your A/C control board. Simply shut down your A/C unit, re-start and make adjustments again for your ... Air Conditioners

Air conditioner My window air conditioner is blowing hot air, however the fans are working. What should i do??


That sounds like the compressor is not kicking-in. Now you need a service tech to diagnose & locate the problem and solve it! ... Whirlwind FH-778 Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific