Having problems with your Air Conditioners ?

Can a Goodman AC unit with a model number of a 24BTU-2 ton unit be upgraded to a 3 ton unit by changing the piston and the settings on the blower? They are also going to install a 3 ton compressor outside. Would this provide the same cooling capacity and performance of changing the actural HVAC unit to a 3 ton unit and would Goodman give me directions stating as much?


Answers :

They would need to change the coil indoors to a 3 ton. If the blower speed can be increased it should be fine.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Can a Goodman AC unit with a model number of a 24BTU-2 ton unit be upgraded to a 3 ton unit by changing the piston and the settings on the blower? They are also going to install a 3 ton compressor outside. Would this provide the same cooling capacity and performance of changing the actural HVAC unit to a 3 ton unit and would Goodman give me directions stating as much?


They would need to change the coil indoors to a 3 ton. If the blower speed can be increased it should be fine. ... Air Conditioners

Purchased Goodman 5 ton unit in 2007. The problem we are having is: When you turn the unit on and set it at 76deg. the temp states on the controller it set at 81 deg in the house, BUT it would not cool enough to bring the house temp up to 78deg. the unit stayed on all evening, and remained at 86 deg without ever shutting off.... I know thta is going to hurt at bill time. Any help you can provide would be appreiated..... My email address is: [email protected]


Your system could have lost its refrigerant charge through a leak. Check for visual signs of oil at any soldered joints. This would indicate a leak at a point where some oil is visible. Also check for frost on the big line that returns to the outside ... Goodman Air Conditioners

I have a Goodman 2.0 model no. ck24-1B and would like to change it to a 2.5 Ton 13 SEER R-410A Air Conditioning Condensing Unit. My furnace is a Goodman model # GMS8, GDS8 or GHS8 are they compatible


If it is a 410a system now you would have to change orfice. if its a r22 system now no way. ... Goodman Air Conditioners

Compressor motors are constantly grounding each time the compressors are replaced. A new run capacitor is installed with compressor. A thorough cleanup and evacuation is performed with each compressor change. Why is this continually happening. The system is within one year old. It is a ton and a half straight cool unit.


Dear sir\012\012please make sure your electrical connection to the compressor is correct and tighten. electricity supply is straight and not fluctuate i mean constant supply for unit and then change new r ... LG LS180HE Split System Air Conditioner

AIR CONDITIONER MY GOODMAN AIR CONDITIONER IS NOT WORKING WELL. IT IS NOT GIVING OFF ANY COOL AIR. I ALREADY CHANGED THE FILTER HOPING THAT WOULD WORK BUT IT IS STILL DOING THE SAME THING. MY UNIT IS ONLY ABOUT A YEAR OLD. WHAT COULD BE THE PROBLEM?


Do you have any frost on the lines going to the outside unit. If the large line is frosted your evaporator (Cooling coil in the furnace) could be frozen up. Operating it with the fan in automatic with the cooling on will sometimes be the cause of thi ... Goodman CLQ36AR49 Air Conditioner

I just installed a Goodman GSX130421 3.5 Ton R410a unit alnog with a Goodman CAPF3642c6 3.5 Ton Evap. The outside unit cam with a #076 oriface, along with instructions to put it in. The Evap came with a #78. I put the #76 in, I evacuated the Evapand lines back to the O/S unit. It held 1050 microns for 10 min. The unit hardly cools the Discharge is 430psi, Suction is pegged, outside temp is 93 deg F. High humidity. Where do I go from here?


Since you got it new i think the best way to get this fixed would be to cotact the manufaturer instead of playibg around with things, however these are the causes of the problem : your condenser may be dirty and the evaporator coils should be cleaned ... Goodman Air Conditioners

Unit runs but will not cool. Fanruns fine but when turn dial to cool the compressor kicks in for about a second or two the kicks out. Fan works on cool but it will not produce cool air at any temp setting. I have cleaned filter and removed cometic facing and vacuumed the coil face. It was pretty dirty but after all that still would not cool, Unit is installed in a RV and power is provided from house. Gen4erator is also available for power. Unit is difficult to remove from RV and space to get at


You may need to install a hardstart kit if you can get to the compressor.\012go to your nearest appliance parts store to get the part and the instructions are usually on it. If not ask the parts man.\012\012If this was helpful pleas ... Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

Why would cool air be blowing out of my central ac unit condensor that sits outside? The other unit I have next to it blows out warm air and responds well to thermostat changes. The unit blowing cool air still cools the rooms it contros... but much slower than the other unit does.


It probably has a low refrigerant charge. The air coming out of the outside unit should be warmer than the outdoor temperature when in the cooling mode and if it's a heat pump it should be colder than the outdoor temperature in the the heating mode. ... Goodman CKL24AR24 Air Conditioner

I replaced my outside unit with a 3 ton goodman heat pump unit. My old unit was a 3 ton bryant and the compressor burned up in it. I left the old unit under the house since it seemed to be in good condition. the pump worked fine on ac to start off. But then you had to switch it in heat and back to ac for it to work. So the tech replaced the expansion value and put filters in both lines. I still have to switch it back to heat to get the ac to work. The tech told me that i would have to repla


You said it had rwo filers on the line. I know one is a liquid line drier. If you have one on the suction line it need to come out ASAP. The trash in the line can be removed by running in cool.pump down unit replace drier. While the unit is pumped ... Air Conditioners

Have two new 5 ton Infinity air conditioning units with gas furnace in residential installation. Repeatedly getting "change filter" warning. Indicated CFM is 1400 on high cool. This seems low to me. Shouldnt the CFM be closer to 400 to 450 CFM per ton? Could the problem be caused by undersizing the ducts? What CFM is recommended for the 5 ton unit on high? Hank Haeseker, PE


Hi,\015\012Yes, you are correct... the air flow should be at least 400 CFM/Ton for good efficiency. 350/ton if you have a dehumidification mode....\015\012But under 300 is totally unacceptable...\015\012The problem probably is the d ... Carrier Air Conditioners

Just bought a new 3 ton 16 seer Trane for a 1700 square foot house, but it is not cooling properly. I can't get the unit to drop below 75 degrees. I had the unit on for 2 ½ hours starting at 8:00am and it dropped from 76 degrees to 75 degrees. The installer failed to change the AC amps in the circuit breaker to 45. Currently the amps I have now is 36. Does that make any difference. It is 86 degrees outside. Any advice to my cooling problem. ? Thanks


Hi,\015\012I would not get too excite4d about this yet...if you are 10 degrees cooler then the outside you are definetly cooling and the mass of the house is also warm because you have just started the unit...give it at least a day...more impor ... Air Conditioners

Looking for freon capacity for 5 ton goodman package unit, cannot read serial or model number.. unit is 1998-2000 model ,, we just replaced the accumulator and we are not sure how much freon to put in.. Goodman offers no help whatsoever.


Check low side which is the bigger of the two, make sure you tighten the hose good. your reading should be 65 psig.If not add refrigerant/r22 . if r410a 110 to 115. ... Goodman GPC1342H21A Air Conditioner

To whom it may conern, I live in a 2 bedroom/ 1 bath 760 sq. ft apartment with a 2 Ton A/C unit. We had trouble with our a/c unit and the maintence (which is A/C licensed) replaced it with a 410A unit. He only replaced the outside unit and it did not want to cool. The manufacturer of the unit said that it already came with the right amount of refrigerant. So he cleaned the coil inside and it didn't work. Then the manufacurer of the unit recommended to change the coil which he did and i


He has really screwed it up you got problems you cant just replace the outdoor unit if he knew his job he would know that also those systems uses two different kinds of refrigerant oil and 410a must be pulsed in alittle at a time. I woul ... Air Conditioners

I have a Coleman roof mounted AC unit on a travel trailer. The unit model is 83338715. The unit just blows cool air not cold air like it should. I was told to replace the "Hard Start Capacitor" and "PTCR Start Device" which I did. This did not remedy the problem. Any thoughts would be appreciated. Could the problem be the "Compressor Run Capacitor"? Reason being that I hear no change in the blower sound when the unit kicks on???


Blowing 'cool air' could mean - room temperature air or it could be 'cool' because the system is low on refrigerant, and just barely doing any 'cooling' at all.\012\012To determine which is which - you need to know "for sure" if the compressor ... Air Conditioners

Hello, my HVAC is constantly freezing, even after freon is added. I was told that I have a leak in the coils and need to chance the air handler - the outside unit is about 10 years old - air handler about 18 years old. I would like to get only the air handler for my R22 outside condensing unit. My question is if in the future can I use this same 3.5 ton air handler with a new 410 condensing unit once my outside unit needs to be replaced. In other words can a Goodman air handler be used firs


I'm new at this and I can't tell how old the post is but I'll contribute anyway.You probably have fixed the problem by now. I wonder what part of the system is freezing up. I don't have a lot of experience but I know you can get frost where there ... Goodman CKL42AR42 Air Conditioner

I have a 5 ton Goodman unit two years old. We moved the outside unit from one spot to an other,and we're having problems now. The comresor went out on it. I replaced it with a new compressor and it went out again. It starts to make a wird noise,and it freezes on the outside unit. I also changed the dryer on it


When charged was it charged by weight ? Was a low ambient kit installed? Have you monitored the amperage draw ? ... Goodman CLQ36AR49 Air Conditioner

I have a 3.5 ton Ruud UBHC-Series Heat Pump, with fan coil unit UBHC-17J11SFA. It was installed in 2004. It has not been cooling well this summer, nd my bills were high last winter. I did not properly change filters for the first couple years, as I thought they were to protect ME, not the UNIT. (I care less about ME than the UNIT!) Recently got it diagnosed with this info: 1) Coils slightly dirty 2) Rozz(I can't read his handwriting) levels: 45.9 / 210.3 psi 8.8 degrees subcool 56 degrees super


Hi I hope this will help, if toy have a air compressor you can clean the coils yourself by bloing air across the coils to the outside of the unit. If there is dirt in the coils and leaves in the condensor coil, once you clean it may be ok but Rudd ha ... Air Conditioners

Have a 15 year old Ruud 2.5 ton condenser that broke down (one of 2 units - the other is still working fine0. The furnaces are 4 years old. They are interconnected - not zoned for our 4200 sq. ft. house. Do i need to replace BOTH condensers because of the freon 410 requirement? Also thinking of going to a 3 ton since the upstairs is never very cool when its hot out. Would this help? If we go to 3 ton, do I need to replace the 2.5 that's working at the same time?


I am not sure what you mean by "interconnected". Basic cooling capacity should be figured on 1 ton of cooling per 500 sq. ft. of space. That would be 4 tons per 2000 sq. ft. You currently operate on 5 tons totally. You require 8 tons of cooling. Othe ... Ruud UAKA042 Air Conditioner

I have a window air conditioner. When it runs for several hours it will trip the breaker. I have had the unit for 5 years. I bought it used and even though it has always shaken when the air compressor comes on it has cooled fine. Recently, however, my landlord changed the circuit breaker (had an electrician come out to do this and supposedly everything is working find). However when I pluuged the unit back into the plug for this circuit, the unit would not even operate for 10 mintues withou


It's probably fine even though it jiggles and makes noise. I would ask the landlord to change the circuit breaker again and ask the electrician what the amps were for the breaker he took out and the one he put in. \015\012\015\012Hopefull ... Whirlpool Air Conditioners

Hi, I have an 8,000 BTU unit. The unit is about 5 years old. It was running fine, no problems at all. Then whan I went to turn it back on after a few days-nothing. No noise, no air, nothing. It just did not turn back on. Before this happeend it cooled, it reponded to degree changes all was fine. The green light button on the test and retest comes on, but there is not a sound from the unit itself. Its like you would hit a power button that was not plugged in (but it is). This problem occur


After changing or cleaning your Filter, you need to reset the A/C. Follow the procedures below:\015\012\015\012Disconnect the power plug from the power supply.\015\012Clean the air filter.\015\012 ... Sharp AF-S80FX Air Conditioner

I have a Goodman AR61 and it is not cooling. I have recently had the system recharged, because I thought it may have been low. When the service guy came out he said I had plenty of charge in the unit, but he went ahead and topped it off to be safe. He told me that the unit was not circulating because of a frozen coil. Which happens because it may be dity. I told him time were a little tight how much would it be to clean it out. He said give it awhile until it melted and I could clean it myself.


Coils get frozen when freon is low or a restriction on a capillary.The reason he got good readings was because the unit evaporator was iced up. He should have run the system on fan only to melt all the ice and get true readings before charging it. ... Air Conditioners

I have an AMCOR model # KF9000E. The unit provides cool air for the audio visual equipment room. It's been doing fine for the last 18 months but now it only blows warm air. I have cleaned the filters, checked the exhaust tube, checked the inlet and outlet. The unit has not moved since I installed it. Nothing has changed in the room in which it operates. Is it low on freon?


Dear sir \012\012it can be low freon problem on your aircon sytem contact to maintenance personnel for refill freon.\012\012thank you \012hope answer the question ... Amcor PLM-14000E Portable Air Conditioner

I have a Goodman CPLE42-1 split system. I had a power outage and my first floor unit would not cool anymore. The air handler/blower in the ceiling is working fine, but the fan outside is not turning on. When I went to look for an overload reset on it, I switched off the breaker on my second floor unit by accident, and now it is doing the same thing. Both fans on the outside will not turn on. Both thermostats will turn on the air handlers in the ceiling. Seems like I re-created the same exact pr


... Goodman CPLE24-1 Air Conditioner

I have a 2002 year model trailer, it has a Duo Therm Quick Cool High Efficiency by Dometic. Because the fan motor would not start by itself, it popped the breaker after a couple minutes the first time I turned it on this year. I took the top off the unit and give the fan a little spin and it would then run. Once again after a few minutes the breaker popped. I changed the capacitor for the fan but it does the same thing. Could it be the armature in the motor causing the problem? Any sug


Does the fan turn freely? Some oil might help but it sounds like you need a new fan motor. ... Dometic Rooftop RV Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific