Having problems with your Air Conditioners ?

I have a Danby DPAC10030 air conditioner. It was working fine until yesterday, when we moved it to another room. Now it blows cold air for 5 minutes and then the air turns hot. The a/c motor continues to run even though the air is no longer blowing cold air. The current ambient temperature is 25 degrees C and I have the a/c set to cool to 17 degrees C. The timer has been turned off (0:00 on and 0:00 off). I noticed that the hoses (exhaust) feel quite hot. Not sure if that it normal within


Answers :

Clean you filter and clean the area under the intake duck it will solve your problem

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Danby DPAC10030 air conditioner. It was working fine until yesterday, when we moved it to another room. Now it blows cold air for 5 minutes and then the air turns hot. The a/c motor continues to run even though the air is no longer blowing cold air. The current ambient temperature is 25 degrees C and I have the a/c set to cool to 17 degrees C. The timer has been turned off (0:00 on and 0:00 off). I noticed that the hoses (exhaust) feel quite hot. Not sure if that it normal within


Clean you filter and clean the area under the intake duck it will solve your problem ... Air Conditioners

The air conditioner is emitting cool air instead of cold air. I have the setting on cold and the temperature setting at 60 degrees. On these days that have been near and over 100 degrees, that cool air offers no relief. When we first got the unit, it emitted cold air. We've changed nothing. The unit is not installed in a window but rather in a hole made for it in the wall.


... LG LWHD1009R Air Conditioner

Room temp 78 degrees with unit setting at 68 degrees. The unit is running (i.e. compressor) but unit not pumping out cold air. To be specific the unit is pushing out cool air just not cold with such a difference in room temp and temp setting. Any suggestions other than having an HVAC service contractor out.


Sounds like it could be low on freon I believe these units have about 1.5 pounds of freon in them and are critical in not undercharging or overcharging them if it is a freon 410 ac unit the pressures should be about 135 and both lines cold if is l ... LG LAN240HSV2-LAU240HSV2 24000 BTU 20 SEER Art Cool Ductless Heat Pump Air Conditioner

Not cooling Have a Dometic 13500 roof top air cond. We are full timers in our 2004 Open Road 5th wheel. Lately the air will not cool below 81 degrees and it keeps kicking off because the compressor overheats. wait 4 minutes and it comes on again. Air is col but not cold. Have cleaned the coils, etc. Good airflow just not cold air. HELP!!!!


Check the and see if the condenser fan is running. you will find it if you take the top off also check and see if the condenser coil is clean. if it is dirty or the fan under the top is not running it will cause the compressor to short cycle on lim ... Dometic Rooftop RV Air Conditioner

I have a maytag nmpeb08f2a portable ac, just started it up for the season. cleaned the filters and coils by wiping down . I also emptied bottom resevior. Im not getting cold air when on cool setting, tried lowering temp all the way. when i turn it on it will be cold for a short time, doesnt fell cold like befor, the temp will go down maybe 1 degree then, no more cool air. can i add refrigerant to this unit?


Frank, refrigerant is what it needs, but it should be done by a pro. Unless you have experience with this sort of thing, it's not a DIY project, ... Maytag Portable Air Conditioner M6P09S2A

Hi. I have a Sanyo rcs-tm80bg heating and cooling system I my house BUT when the outside temp is very cold, say 2 degrees or less, it doesn't want to throw out hot air. The fan speed does what it wants no matter what speed I use. So, today I set for 24 degrees on high speed and I get a dribble of cold air. My room is freezing! Please help.


... Air Conditioners

I have a Dometic 15,000 btu, ducted air conditioner in my 30 ft fifth wheel. It seems like the unit has never cooled very efficiently. Dealer has checked out. I noticed yesterday, outside air over 100 degrees, that the air conditioner would put out good flow of cool air, but once in a while compressor would stop running even though not close to thermo setting. Fan would continue running. Any suggestions?


Not sure what the pressure sensor should ohm at but i would suspect a faulty sensor if everything else checks out. Its very common for these sensors to exhibit issues when they get hot. Also you may have a filter in the system that may be restricte ... Dometic Rooftop RV Air Conditioner

Good after noon i have a Starway Split Wall Mount Reverse Cycle Air Con. the problem i have is when i need to warm my house the air coming from the system is cold. even with the temp setting on the sun icon and set to 28 degrees it's still blowing cool air. kind regards Kerry Grace


Hello,it is due to a bad thermostat,so sll you need to do is just to get a new thermostat and replace it with the bad one,after this is done you will then enjoy your air conditioner as normal,wish you good luck,take care. ... Air Conditioners

Good after noon i have a Starway Split Wall Mount Reverse Cycle Air Con. the problem i have is when i need to warm my house the air coming from the system is cold. even with the temp setting on the sun icon and set to 28 degrees it's still blowing cool air. kind regards Kerry Grace


Hello,Examine the condenser. The condenser pushes the air and expels the warm \015\012air from the air condition to the house.\015\012Also check the fan heater on your system to see if it is functioning, because if it is not, it will circ ... Air Conditioners

Daewoo DOZ-1206G Brand new, just installed. This replaced an older a.c. unit in our apartment that was not blowing any cold air. The technician said that one was broken and replaced it with this one. Once it was installed, the technician turned it on and left. After 5 minutes with it set at 16 degrees celsius the cool air (which was never freezing) just became normal air. We have tried everything on the controls, we cannot get it to cool our very small studio apartment. We live in Sth Korea by t


... Air Conditioners

Had heat pump replaced roughly a month agoworked fine until yesterday.the wife says it was 85 degrees on the thermostst when it was set at 78. Told her to check breakerfreon line at air handler and compressor;breaker was good line was not cold or condensating said fan was on but not compressornothing was frozen.told her to turn thermo to off till it cools down.this am said it was cool then it wasn'tnow it is.this is a 3 ton 13 seer r-12 unit...thx rob


Call the install company back out. along with the new heat pump i wouls say they installed a leak. you stated r12 i assume you ment r22 if they installed an r22 unit and didnt change the a coil it might not be their work leaking but the a coil migh ... Goodman CLQ36AR49 Air Conditioner

8,000 BTU FRIGIDAIRE MODEL FAA085P7A2. Have air conditioner on but not sure what temp I should set it on. It's 90 degrees outside with 80% humidity. Also, what is clean air button for and auto cool button. HELP!! THANX


... Air Conditioners

I have an electric furnace and heat pump that will at times blow only cold air during the heating season. I have checked the filter and don't believe that to be a problem. I usually have the temperature set to 74 degrees. When the outdoor temp. is extremely cold the axillary heat indicator will be on and still no heat. I can turn the heat pump off by switching to emergency heat and will get some heat from that but not as warm as I think it should be and even that will at times only blow cool


You are losing operation to your heat strips.\015\012\015\012In heat pumps, there is a secondary heat source. Usually electric heat strips. (Sometimes a gas furnace, this is known as a "dual fuel" system)\015\012\015\012The he ... Carrier Air Conditioners

My Kenmore 72059 unit is blowing cold air but is not cooling the room (the room is not the big either). It is set at 60 degrees. Why is the room not getting cool?


Physics, friend. \015\012Ideally any cool input would be enough to effect the temperature, but other things are working against you. \015\012Check the air filter behind the case cover and clean it if necessary. This may improve your ai ... Kenmore 72059 Air Conditioner

My air conditioner delivers cold air only in spurts. It then goes into fan mode for a few minutes, then to cold air in a few more minutes. It is over 100 degrees outside and the inside of the house is 85 or so. I have the temperature set at 74 degrees. Why does the cold air not pump out consistantly?


Hi,The\012 unit is probably low on freon and so it is running too cold....this \012trips the freeze stat and shuts down the compressor till it warms up The unit will \012need to be recharged or replaced...\012Here is a t ... Fedders AED24E7F Wall/Window Air Conditioner

Air not cold...model MSH-18NV no operating manual for remote . Not sure how to set to cool air when remote reads "I feel..." choices are cool dry or warm but when set on cool 20degrees, luke-warm air blows out. have checked and cleaned filters.


Hi FixYa team. After about 2 hours on the internet I managed to find a PDF file of the operating manual for my air con.\015\012Thankyou for your prompt response. I'll be using your services again! ... Mitsubishi Air Conditioners

My problem is when I turn on my air only kick in for a minute of cold air then it shuts down then warm air comes out for five minutes maybe less. my setting are at max cool thermostat at 7. at these setting my room should be ICE cold.


If it is in the middle of winter that you are doing this it has still got a very slim chance of doing what you want... it is a thermostat afterall which is preset by the manufacturer, take the settings off automatic and turn onto cool only.... atleas ... Air Conditioners

When calling for cold air, the fan in the cooling unit hums, but does not spin. With a nudge, the fan does spin. Looks to be smooth and normal speed. However ambient outside air 80 degrees. the air through the register is 72 degrees. Is there a switch that will not allow the fan to start on its own if the coolant is too low? Do I have two problems, fan starting AND insufficient cooling? Unit worked well the last two days.


Sounds like start capacator possibly bad ... Air Conditioners

After a cooling cycle, when the thermostat call for more cooling, it take up to 5 minutes after the air handler starts for the compressor motor to restart. The top fan operates on the outside unit, but since the house is not circulating cold air, only the room tep air the house heats up about 3 degrees before the compressor comes back on and cool air begins to come from the ducts. Yes. I know there is a safety feature to protect the compressor, but can the cycle be shortened?


No, this cycle cannot be shortened due to the simple fact that this feature is in place to protect your system. Even if it could be, I wouldn't recommend it.Mat ... Coleman Air Conditioners

My LG Lan125HV works fine on air conditioning ( cool) but heat pump does not trigger when I move to heat or combined settings. Tried all temperature and fan settings, tried waiting to see if unit waiting so as not to blow cold air, nothing works. Switch back to cooling and everything works fine.


I talked to LG customer support (800) 243-0000. The tech told me that this model had a problem with the indoor thermistor. It doesn't fail with an open-circuit condition, so you don't get an error code. The thermister just goes out of range and be ... LG Heat cool Window Air Conditioner

For my window air conditioner timer, do I turn off the unit by the switch, plug it in to the dial timer, set the pins to the start time and then set the override dial to on or off? Ny Samsung window AC Model # AW0891L- suddenly started blowing hot air and requires one hour to cool down and work properly. What's wrong?


YOu will need to set the start time override dial to off. Otherwise it will run on it's own setting. Then you need to allow an hour in between times to cool down. Otherwise the freon heats up and won't be of the same viscosity causing problems of war ... Air Conditioners

Warm Air My Fleetwood motorhome Dash air is giving me problems. After I turn on the controls Blower, outlet position, AC on button and re circulate button I may or may not get cold air. After continually operating the controls mainly blower & AC button, I can some times get the AC to cool down. When it is warm it's about 80 degrees, when I do get it to start cooling it will go down to about 60, Checked with an IR thermometer at the vent. Once it does cool down it may work the remainder of the d


... Air Conditioners

My toshiba split system will blow cold air for about 30min then it will blow what seems to be cool air but not air con cold air when it is quite hot outside. The timer light operation and filter light will flash. I have turned it on and off reset remote cleaned filters. When it's cooler outside it seems to work fine???


... Fujitsu 9RLS 9000 BTU Split System Air Conditioner

Conia air conditioner reverse cycle - not blowing cold air; checked setting its correct.. it seems to blow cool air, but house is not cold. It was working fine last summer, not sure of problem.


If you feel cool air near blower, you have to service your unit completely. Because it's giving cool but not removing heat from room due to coil and air filter blocking. Helpful? ... Air Conditioners

Our total line thermostat was set on 73 degrees and all of a sudden it went to 99 degrees and I counld not turn it off, it just kept running. So I turned off the breaker and turned in back on and now I can't set the temperature. It's just set on 99 and won't do anything. When I turn the fan on, the air won't get cold.


Hi, it sounds as though you have a faulty thermostat that failed before your eyes. The circuitry in the sub-base has failed. If the stat is set in the off posistion and you turn the fan switch on, just the fan will run. If it is on cool and you turn ... Air Conditioners