Having problems with your Air Conditioners ?

Need recommended sub-cooling and superheat for condenser models # MSS-30-E, 9 seer with Copeland compressor model# SRD6-0225-PFV with indoor evap. coil model # MEVC-30. Also MSS-36-E, 9.15 seer with Copeland model #CRH3-0275-PFV with indoor evap. model # MEVC-36 . Both compressors have a suffix -C1. Both are split units with electric furnaces. This info. would be very helpful. Thank you, David


Answers :

Superheat should be 8 to 12 degree's. Sub cooling around 18-22. I like to use superheat that way I know the coil is doing all it can do.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Need recommended sub-cooling and superheat for condenser models # MSS-30-E, 9 seer with Copeland compressor model# SRD6-0225-PFV with indoor evap. coil model # MEVC-30. Also MSS-36-E, 9.15 seer with Copeland model #CRH3-0275-PFV with indoor evap. model # MEVC-36 . Both compressors have a suffix -C1. Both are split units with electric furnaces. This info. would be very helpful. Thank you, David


Superheat should be 8 to 12 degree's. Sub cooling around 18-22. I like to use superheat that way I know the coil is doing all it can do. ... Air Conditioners

I have a split system sanyo heat pump model # kmh0922. The evap. fan will not come on when called for in fan mode. When i put it to heat the indoor fan will also not come on. The compressor runs but the reversing valve seems to stay in the cooling mode. When it is put into cooling the indoor fan goes off after 15 seconds and will not come back on. (The condenser fan and compressor seem to act normal in cooling.) Any ideas as to what the problem could be? Thank you, Mike


Sounds like the blowers capacitor has gone bad ... Sanyo Air Conditioners

Do I only need a new condenser, or a whole new split central air conditioner system? I currently have a Bryant 340AAV with a Bryant evaporator coil model no. CD6AXW036021ABAA, outside I have a Goodman Condenser model no. CE36-1GB, My compressor has failed, HVAC said replacing compressor would not be worth it. I was about to buy a used Rheem 10 seer condenser, but I read that the minimum is 13 seer and that if the inside is a different seer from outside that would result in it breaking down. I do


Hello!The HVAC shop is likely accurate when they told you it would not be cost effective replacing a compressor alone. My advice is to contact the HVAC contractor back, and ask him what they would recommend that the condenser ... Goodman CKL42AR42 Air Conditioner

Coil piston I have a goodman evap coil, model# capf3642c6aa, and the condenser that I bought for it, is a model# gsc130421ac but didn't come with the replacement piston for the indoor coil. So my question is if I can use the piston that comes in the indoor coil with this condenser.


If you purchased it as a package the right piston may already be installed in the indoor Evaporator coil. When shipped the extra piston if needed is packaged with the outdoor section condensing unit. ... Goodman Air Conditioners

Several years ago I purchased 2 Split-Type Room Air Conditioners--Models RSW-17 (Indoor Unit)/ROW-17 (Outdoor Unit) and RSW-12S (Indoor Unit)/ROW-12S (Outdoor Unit). The airconditioners themselves are fine, however,the Remote Controls for both these units, Model AR-DJ15, have gone bad and may not be repairable. How/where can I purchase replacement remote units? Alternatively, where/how can I send my remote units for repair? Chester D. Copemann [email protected] or [email protected]


Type in the mfg. name in the search bar and see if you can find resources. ... Air Conditioners

I purchased an Amcoraire split system unit for my 2 story garage. Licensced electrician did the wiring and licensed HVAC co. installed the 2 indoor units and outside unit. Outdoor unit is Model # AOM 243 HX 24000 BTU Indoor units are both Model #AWM123 HX, 12000 BTU each When I turn the unit on, it runs for about 60 seconds and then I get an error code on the inside wall unit that says P7. My manual says this has something to do with voltage. I had the power company come out and they show the


Since the manual says the error code has something to do with voltage it means the voltage is either too high or too low. And as the electric company says the voltage is within limits the the error is as a result of the voltage fluctuating. All you h ... Amcor Air Conditioners

I have a Mitsubishi split system with 2 indoor units (MS09TW) and one outdorr (MU09TW). The evaporator coil on one of the indoor units has been diagnosed by a A/C repair company as having a pinhole leak. I would rather repair the entire indoor unit but I can't find an avaialable replacement unit. Is there a model that will directly replace my existing unit. The evaporator coil PN is E02 462 620


The following link includes service manuals for your air conditioning system: http://usa.mylinkdrive.com/uploads/documents/2388/document/MS-09~17TW,TN__MU-09~17TW,TN_Service_Manual.pdfI'm sure you find the solution inside the manual. ... Mitsubishi MS09TW Air Conditioner

I have fujitsu Air conditioner Model- ASY24UBBN Serial No.- E000476 IPXO Problem- we have the problem in Indoor Split Ac. The indoor unit fan not getting speed while we operate by remote.


You can also check the coil and see it is dirty ... Air Conditioners

We installed a 4 ton downflow coleman air handler with evap coil Model number 1854s2m we did not change out the outside unit. the outside unit is a 13 year old 3 1/2 ton intertherm condenser the system is only generating a 10 degree delta T. My question is, this coil came with a factory TXV I am trying to find out is this a 10 seer or 13 seer coil is it compatable with the outside unit.


You have a missmatched system, for it to work try removing the orfice on the high side txv it is not allowing the evaperator coil to fill with refrigerant properly coleman and intertherm dont like each other since they control a large market in the ... Air Conditioners

Considering an Amcoraire dual zone mini split. $700 price for the 18K 15 SEER dual zone combo looks too good to pass up. I understand anything branded Amcor is probably a year or two old, since they've been bought out by Pridiom. My AC guy tells me all of the major Japanese brands are comparable and outstanding. He doesn't have experience with a Chinese-made model like the Amcoraire (now Pridiom). For 1/3 the price of a Toshiba or LG do I role the dice on the Amcor/Pridiom model? Or am I just


My personal knowledge of this company is extremely limited. When I was in business I did plumbing heating a.c. remodeling and several other things so I asked a friend of mine who is a hvac specialist and he says they are not worth much in his estimat ... AmcorAire UCHW-H12AF2 Split System Air Conditioner

I got 1 customer having conia air cor split type Model CA30001,when you turn it on,on indoor unit it shows red power LED on and on side green light blinking takes 3seconds to blink and indoor blower not working what will the problem can u help me thanks regards


... Air Conditioners

I have a fujitsu halcyon inverter evaporator that isnt working. The indoor wall mount is blowing air, but the evap outside isnt working. The fan doesnt seem to be working. I have another 2 piece fujitsu, same exact model that is working fine, drawing air into the evap. Dont know much about trouble shooting, any tips would be appreciated because its hard to find info on these things.


... Fujitsu Air Conditioners

Hi the outdoor unit turns on ( fan runs) the indoor unit does open, no heat or cold air blowing. In just fan mode the unit works fine etc speed setting ok. Its a sharp split type air model # ae-a244j outdoor,ay-a244j indoor unit what would be the problem, theres only two parts in the outside unit behind the side plate where the wires info is,small black box three wires and a round unit with wires. I hope this is help full cheers andrew


My gut says that this is evidence of a bad control board(circuit board). As usual, double check that your batteries are good in the thermostat. I have seen some weird things happen when the batteries are low. This one may be a job for your local con ... Sharp Air Conditioners

Hi I have an NEC Split Air Conditioner. Model RIH6867. Power rating - 6.8Kw Cooling Capacity 8.2Kw Heating Capacity. Single Phase for 240Volt environment. I only have the outdoor unit. It is new. But missing the complete indoor assembly unit and remote. Can I substitute other indoor units to make this work. NEC no-longer supports their appliance division. Regards Ash


Hi Ash,Off the cuff, I would say no to being able to use any other indoor unit. But, with a bit of work and research, you might be able to connect 2 systems, even if different manufacturers, together. The compressor / conden ... Air Conditioners

Split wall A/C equipment model indoor unit AS1AH18GW001, outdoor unit ASOH18GW051 requires an indoor receiver board, where can I get one please. From [email protected]


... GE Air Conditioners

I have a samsung split ac model as12whwd. all 3 flash lights are glowing in my indoor unit.i need to set the option code for this model.can u tell me the option code for that my mail id is gayathri_re


... Air Conditioners

I am looking for a price for a mitsubishi mini split air conditioner called mr slim model plh18fk seral 56f00429c indoor unit outdoor unit puh18ek need a price for resale.


... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

Would u please help me the indoor unit compatible to Split type Air conditioner outdoor unit model 38KGC018703?


... Carrier Air Conditioners

I purchased a ductless amcoraire mini split system. I believe the models are AWSO91HX (inside unit) and AOSO91HX (outside unit). I am getting a F1 error (indoor outdoor communication failure). Please advise me and my licensed installer on how to correct the problem or who I can contact for a house call repair.


... Air Conditioners

I have an Intertherm split unit A/C and electric heat I need a ladder diagram for the indoor fan relay and I also need to know which part number it is my intertherm model number is e2ebo15hb any help would be greatly appreciated.


Hi, the schematic would be in the indoor unit, but I am assuming its gone since you are looking for the ladder schematic for the heat strips and fan control. You might try this number for a schematic, 1-888-441-6942, Route A/C and they may be able to ... Intertherm Air Conditioners

Indoor Sanyo ductless split Model # KHS 2432 serial # 0012832, Works fan on and off functions and speeds. As soon as you set the remote to heating or cooling the unit beeps 5 times quickly and then the unit no longer responds to remote control. The blower will then run for 1 minute and then the the unit no longer will work. Power must be reset for blower operations to function again. Out door unit, has enough charge, Ambient temp 39 M#CH2432 S#0012424


... Sanyo Air Conditioners

Hello just replace the pcb for a mini split model# AQV12JA but not I have all the lights on indoor unit blinking. What's going on? Thanks In Advance


Make sure that all of the plugs are seated - take them back off and reseat them. Second, start looking for a dead short in the controls. If that doesn't fix, I would suspect a bad replacement board..... ... Samsung Air Conditioners

I have a Westpoint split A/C Model WSC-09. The unit turns on but the fan (the indoor side that blows cold air) does not operate.


Most likely a broken fan capacitor.\015\012When you follow the wires from the fan you will find it. Try to replace it. (electronical store)\015\012I'm an airco service engineer, in 95% of the cases this is the cause.\015\012\0 ... Air Conditioners

I have a mr slim split unit model mxz-2a20na and i cant get the indoor units to power up also the compressor does not com on i do have 220 volts going to unit. on the pc board i have solid lights on led1 and led 2 which are red and yellow on led3 which is green it goes on and off but cant find in manual what led3 is for? can anyone give me a tip what i should check for? thanks


Normal\012 0\012 \012 \012 \012 \012 \012 \012 MicrosoftInternetExplorer4\012 \012\012\012\012\012\012 /* Style Definitions */\012 table.MsoNormalTable\012\011{mso-style-name:"Table Normal";\012\011mso-tstyle-rowband-size:0;\012\011mso-ts ... Mitsubishi Air Conditioners

I have a central air conditioning unit in the apartment where I live. It is a split unit - somewhere outside is my outdoor unit (and everybody elses too). Anyway I seem to get way too much humidity in my apartment. The air conditioner I suspect is 15 or 20 years old or more. The label on the indoor part is almost unreadable. Carrier is the maker. The model might be 40AC02450052. There are also other numbers 40AC901190 ? or 40709010 ? Can anyone identify what I have? I would like to know how old


The humidity problem is from the condesation drain. It is more than likely to be clogged up keeping water in the condensation pan causing the humidity problem. This can be cured by a wet vac put onto the outside drain for the inside condensation pa ... Carrier 38CKC030 Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1337 seconds